Rigid wall installation Applique installation frame
The wall is composed of concrete blocks
(minimum density of 550 kg/m³) or reinforced
concrete (minimum density of 2200 kg/m³) and
with a minimum thickness of 100 mm.
Installations
INSTALLATION
1. Create a wall opening according to the dimensions
in the table below.
Damper blade must be closed during installation!
2. Insert fire damper into wall and fasten with screws
(8 pcs, 4.8 x 60 mm).
Test the operation of the damper blade!
1
2
Wall opening dimensions
Damper diameter Ø d (mm)
Applique frame diameter Ø D (mm)
Wall opening (mm)
100
Ø d + 105 mm
Ø d + 115 mm
125-180
Ø d + 95 mm
Ø d + 105 mm
200-315
Ø d + 80 mm
Ø d + 90 mm