Specification and Technical Data
Model
KFIHP-09-ID
KFIHP-09-OD
KFHHP-12-ID
KFHHP-12-OD
Function
Cool / Heat
Accessory Air
Cleaner
Cooling capacity (Btu/h)
9000
12000
Heating capacity (Btu/h)
9500
13000
Power Supply (V)
115V~
208~230
Frequency (Hz)
60
Cooling/Heating rated current(A)
12/13.6
9/10
Cooling/Heating rated power(W)
1250/1450
1700/1750
Cooling/Heating power input(W)
730/840
1100/1200
Recycling air Volume
(
m
3
/h
)
550
Refrigerant and weight(lbs)
R410A 2.6 lbs
R410A 2.8 lbs
Water proof level
IP24
Noise(Indoor/Outdoor)dB(A) 43/55
Climate type
T1
Anti-electric shock protection
I
Weight Indoor/Outdoor)(lbs) 24.3/99.2
24.3/99.2
Dimensions
(W x D x H)
Indoor unit
30.31”
×
7.48”
×
9.84” 32.68”
×
8.86”
×
11.22”
Outdoor
unit
33.39”
×
12.6”
×
21.26” 33.39”
×
12.6”
×
21.26”
Connection Pipe:
Length (ft)
19.68
Gas additional charge(oz/ft)
0.16
Liquid Pipe (mm)
Φ
6(1/4”)
Outer Diameter
Gas Pipe (mm)
Φ
12(1/2”)
Height (ft)
16.4
Max Distance
Length (ft)
49.21
1.
All above are tested and certified to ETL specification.
2.
All above could be changed without notice; the latest specifications are on the nameplate of your air conditioner.
3.
When the unit is restarted after it stopping, it can automatically resume the last running mode, and the outdoor unit
starts later.
Working temperature range:
Indoor side DB/WB(°F)
Outdoor side DB/WB(°F)
Maximum cooling
89.6 / 73.4
109.4 / 78.8
Minimum cooling
69.8 / 59
69.8 / -
Maximum heating
80.6 / -
75.2 / 64.4
Minimum heating
68 / -
23 / 21.2