Installation
and
Operation
Manual
PVI
Series
Inverters
DOCR
‐
070365
‐
E
Page
42
of
57
9.2.7
Power
Dispatch
“ActivePower”
and
“PowerFactor”
parameters
can
be
set
up
through
the
LCD
as
well
as
remotely.
NOTE:
These
parameters
are
only
adjustable
with
permission
from
the
local
utility.
Figure
9.5
–
Active
Power
and
Power
Factor
Settings
NOTE:
When
prompted
for
a
password,
enter
the
following:
UP
,
DOWN
,
UP
,
DOWN,
then
ENT
.
NOTE:
It
is
often
common
at
sites
with
High
AC
voltage
above
1.05p.u
that
the
Utility
would
like
to
modify
the
power
factor
to
reduce
the
voltage
at
the
point
of
common
coupling.
This
can
be
done
by
setting
the
inverter
to
absorb
vars.
For
the
PVI
23
‐
28TL
this
can
be
achieved
by
setting
the
inverter
to
a
negative
value.
For
example,
one
would
set
the
power
factor
to
‐
0.95
which
will
help
reduce
the
AC
voltage
at
site
by
allowing
the
inverter
to
absorb
vars.
If
you
are
interested
in
enabling
these
features
or
in
further
understanding
their
capabilities,
please
contact
us
at
for
more
details.