Note:
There are cases where the RVS-AXO returns Normal response, but the requested action
cannot be performed, or is modified by the RVS-AXO. Few examples are:
Requested Action
Performed Action
Writing Setting parameters during start process
Ignored.
Writing few parameters (Function 16), some are out of range
Limiting to allowed
range.
Start command (Function 05) while Stop Hardwired Input is open Command ignored
It is the user responsibility to verify that the requested action was performed, by reading
the value of the modified parameters or the status of the command Coils.