SET PAGE - MENUS
Page 35 of 67
Power Settings
POWER
*** SETTINGS ***
Display
Description
Rated PF at FLC
0.88 Lag
Motor rated (Nameplate) power factor. Required for calculating rated power (based
on motor FLC and line volts).
Range: 0.5 – 0.99. Increment of : 0.01
Under Pwr Level 1
45%
Under power level 1.In percent of rated power, calculated by:
√
3 * Line Volts * Motor FLC * Rated Power Factor
Range: 5 - 99%. Increment of : 1%
U/P Level 1 Delay
30 Sec.
Under Power Level 1 time delay.
Range: 1 - 120 Sec. Increment of : 1 Sec.
Under Pwr Level 2
25%
Under power level 2, in percent of rated power.
Range: 5 - 99%. Increment of : 1%
U/P Level 2 Delay
30 Sec.
Under Power Level 2 time delay.
Range: 1 - 120 Sec. Increment of : 1 Sec.
Low Power Factor
0.80 Lag
Low Power factor level. Fault occurs when PF is below the set parameter for more
than Low PF Delay.
Range: 0.20 - 0.98. Increment of: 0.01
Low PF Delay
30 Sec.
Low Power Factor Delay
Range: 1 – 120. Increment of: 1
KWH Per Pulse
OFF
KWH pulse relay. Set required KWH for each relay pulse.
Range: OFF, 1 – 100. Increment of: 1
Summary of Contents for MPS 3000
Page 1: ...MPS 3000 MOTOR PROTECTION SYSTEM Version 18 7 2006...
Page 7: ...WIRING DIAGRAM MPS3000 Page 7 of 67 WIRING DIAGRAM MPS3000...
Page 8: ...WIRING DIAGRAM MPS3000 C Page 8 of 67 WIRING DIAGRAM MPS3000 C...
Page 9: ...REAR PANEL MPS3000 and MPS3000 C Page 9 of 67 REAR PANEL MPS3000 and MPS3000 C...
Page 66: ...TECHNICAL SPECIFICATIONS Page 66 of 67 CASE AND CUTOUT DETAILS...