SET PAGE - MENUS
Page 32 of 67
O/C Level 2 Delay
0.5 Sec.
Time delay for Over Current Level 2
Note: When set to 0, actual delay is less than 70mSec.
Range: 0 - 4 Sec. Increments of : 0.1 Sec.
Unbalance Level 2
15 % of FLC
Unbalance Current. Fault occurs only if actual Unbalance is greater than the set
value. See Figure 6 for time delay.
Note - Unbalance Current level 1 will be activated when Unbalance Current
exceeds 50% of the Unbalance Level 2 for more than 1 second (fixed time
period).
Range: 10 - 40 % of Motor FLC. Increments of : 1%
Unbalance Min T
5 Sec.
Unbalance Minimum response time for both Alarm and Trip.
Range: 1 - 30 Sec. Increments of : 1 Sec.
U/B Level 2 Max T
30 Sec.
Unbalance curve selection. see p37
Time delay at 10% of Unbalance. Fault time is inversely related to the actual
unbalance (See page 37).
Range: 20 - 120 Sec. Increments of : 1 Sec.