Setting
Setting
60
61
3-6-1-9)Self Test (applies to CEI 0-21 only)
3-6-2-1) Charger
Here the user can set the parameters of charger on this page. Users can
set the charge & discharge parameters, min capacity and awaken function .
For the detailed parameters , please refer to below table.
>Min Capacity
20%
Charger
Charge Max
Charger
Current 25A
Discharge Max
Charger
Current 25A
>Battery Awaken
Charger
NO
•
If user wants to use lead acid battery, please contact SOLAX for
future reference.
NOTE!
The charge current can be set for 0-30A.
The remaining minimum capacity of the battery.
The discharge current can be set for 0-30A.
Battery Awaken
When the battery voltage drops too low to work, choose this
option “Yes” to make battery charging from PV or grid forcbily.
The self test function allows user to test the following items.”ALL test” , ” Ovp(59.S2) test”,
” Uvp(27.S1) test”, ” Uvp(27.S2) test”, ” Ofp(81>.S1) test”, ” Ufp(81<.S1) test”,
” Ofp(81>.S2) test”, ” Ufp(81<.S2) test”, ” Ovp10(59.S1) test”.
In the self test interface, user can
test
choose “ALL test” or individual test item.
Please make sure the inverter is grid-tied before testing test.
For all test, it needs about 6 minutes. And it will display”success” then “Pass” on the
display.
For individual test item, it needs about several seconds or minutes.
Click test report to obtian all items test result.
ALL Test
Test report
Uvp(27.S1) test
Ft: 51.50Hz Tt:1000ms
Fs: 0.00Hz To: 998ms
F0: 0.00Hz pass
>Ofp2(81>.S2)result
Vt: 264.5V Tt: 300ms
Vs: 0.0V To: 200ms
V0: 0.0V pass
>Ovp2(59.S2)result
Vt: 92.0V Tt: 200ms
Vs: 0.0V To: 196ms
V0: 0.2V pass
>Ofp2(27.S2)result
Vt: 195.5V Tt: 400ms
Vs: 0.0V To: 200ms
V0: 0.0V pass
>Uvp2(27.S1)result
Ft: 50.50Hz Tt: 100ms
Fs: 0.00Hz To: 96ms
F0: 0.2Hz pass
>Ofp2(81>S1)result
Ft: 49.50Hz Tt: 100ms
Fs: 0.00Hz To: 98ms
F0: 0.02Hz pass
>Ufp2(81<.S1)result
Ft: 47.50Hz Tt: 400ms
Fs: 0.00Hz To: 3999ms
F0: 0.02Hz pass
>Ufp2(81<.S2)result
Vt: 253.0V Tt: 600ms
Vs: 0.0V To: 598ms
V0: 0.0V pass
>Ovp10(59.S1)result
>Grid-tied Min Limit
Charger
Grid-tied Min Limit
The remaining minimum capacity of the battery when gird is on.
When the battery capacity reachs the min capacity in
on-grid
mode(no PV power), battery
will stop discharging and the system will go into IDLE mode.
When the battery capacity reachs the min capacity in
off-grid
mode, battery will stop
discharging and the inverter will stop exporting power from EPS port with showing “BAT
power low” on LCD display.
There are two ways to exit from “BAT power low”.
-Press ESC button can exit from “BAT power low” manually.
-Enter EPS system setting page( refer to 3-6-2-2 section) to exit from “BAT power low”
automatically.
Ø
Min capacity
•
Please con rm the Inverter setting for maximum charge/discharge
current is within the range of battery rated charge/discharge current.
NOTE
!