WARNING
DANGER the operation of the 240V AC thermal cut out indicates a possibly
dangerous situation. Do not reset the 240V AC thermal cut out until the water
heater has been serviced by a qualified person.
PV ARRAY WARNING
Maximum array power of 3.84kW must not be exceeded. Current must not exceed
22 Amps, array design must not exceed 2 strings. Voltage must not exceed 270V,
String length must not exceed 6 panels.
Max power must not be exceeded.
3.84kW can be either 270V @14.2A or 174V @ 22.0A or in between.
P=IR (Volts x Current), 3840W must not be exceeded.
WARNING
The controller has no user serviceable parts. Opening the cover will void all
warranty and may expose dangerous voltages.
Removal of the covers on the storage water vessel will expose live electrical wiring.
Covers must only be removed by an authorised service person and only once dual
supply power has been isolated.
ATTENTION
Ensure all glands from the control box are firmly tightened to ensure ingress
protection.
ELECTRICAL WARNING
All electrical work and permanent wiring must be carried out by a qualified person
and in accordance with all current relevant Australian installation standards and
local authority requirements.
Means for disconnection must be incorporated in the fixed wiring in accordance
with the wiring rules.
All electrical connections must be terminated before switching any component on.
The power to the Solatherm solar control unit and water heater must NOT be
switched on until the water heater is completely filled with water and all air bled
from the system.