14
ASSEMBLY & INSTALLATION
GAS CONNECTION
GAS CONNECTION
GAS CONNECTION
GAS CONNECTION
1.
Verify that the gas type is correct for the fireplace by looking at the rating plate that is attached
to the right side of the fire-place, adjacent to the control battery pack. Note: The fireplace is
shipped from the factory equipped to burn the fuel listed on the rating plate. Fuel conversion in
the field is not allowed.
2.
The gas connection should now be made from the gas supply line to the 3/8 OD Tube fitting on the
fireplace. Only a qualified gas installer is to make the connection.
3.
The gas supply piping should have a separate
gas shut-off valve and a 1/8” NPT plugged
tapping upstream of the valve. We recommend
installing a shut-off valve between the gas
supply line where it penetrates the wall /
fireplace mounting plate and the inlet on the
fireplace. This will allow gas to be shut-off to
the fireplace by simply removing the fireplace
surround to gain access to the shut-off valve.
4.
The fireplace and its main burner valve must be
disconnected from the gas supply piping
system during any pressure testing of that
system at test pressures in excess of 1/2 psi
(3.5kPa).
5.
The fireplace must be isolated from the gas supply piping system by closing the gas shut-off
valve during any pressure testing of the gas supply system at test pressures equal to or less than
1/2 psi (3.5kPa). After the gas supply has been connected, use a commercial gas leak detector or
apply a soapy water solution to all the fittings to check for gas leaks. Never use a flame to test for
leaks
.