Just as with any other vented device, vertical vent rise 

creates draft (negative pressure) in the firebox as the 

exhaust gases heat up. If this draft becomes excessive, 

it can affect the performance or appearance of the 

fire. The SÓLAS Gas Fireplace includes an integrated 

air restrictor that can used to balance the draft in the 

fireplace to the optimal level for installations where 

excessive draft might occur. The SÓLAS Gas Fireplace 

will ship from the factory with the air restrictor set to the 

#1 position. If the licensed fireplace installer determines 

that draft reduction is necessary, loosen the fastener on 

the dial and make small adjustments from #1 to #4 until a 

satisfactory result has been achieved.
The air restrictor dial is located on the flue side of the 

firebox when viewed from the front. To access, remove 

the lower air screen and side panels. Once satisfied 

with the air restrictor adjustment, secure its position by 

tightening all hardware.

A

DETAIL A

SCALE 1 : 3

SÓLAS Flue Restrictor Kit, Part #11210

Some vent configurations may create excess 

draft within the fireplace. Excess draft can cause 

issues such as a rapid, or “nervous" flame picture, 

undesirable flame color, or pilot lifting which may 

prevent the fireplace from staying lit. In these 

circumstances it may be necessary to install the flue 

restrictor kit part #11210 in the venting system. It is 

permissible to install this restrictor at the vent cap 

should the venting system already be installed. 

Secure the restrictor plate with the included #10 

sheet metal screws.

SÓLAS FORTY8 Flue Baffle Kit, Part #11273

Certain vent configurations for the SÓLAS FORTY8, 

particularly those with a significant amount of vertical 

in relation to the amount of horizontal vent pipe, may 

cause the flame to be unbalanced, or biased toward 

the flue outlet side of the fireplace. Installation of this 

flue baffle, part #11273, will help to resolve this issue. 

It may be necessary to use this restrictor on its own, 

or in addition to the SÓLAS flue restrictor kit, part 

#11317 shown above. This flue baffle kit snaps into 

the fireplace as shown below. For use in FORTY8 

Slim-Line Built-In Models only.

FINAL ASSEMBLY

Summary of Contents for BI-48-SSL

Page 1: ...FLAMMABLE MATERIAL ON OR NEAR THE APPLIANCE WARNING Improper installation adjustment services or maintenance can cause injury or property damage Refer to this manual For assistance or additional info...

Page 2: ...___________________________ Brand of Venting Used _________________________________________________ Model of Vent Cap Used ______________________________________________ Fuel circle one Natural Gas NG...

Page 3: ...MUST BE FOLLOWED EXACTLY PLAN YOUR INSTALLATION IN ADVANCE BY CAREFULLY REVIEWING ALL THE INFORMATION CONTAINED IN THIS MANUAL The information contained in this manual is believed to be correct at th...

Page 4: ...i les r glements locaux le permettent Cet appareil doit tre utilis uniquement avec les types de gaz indiqu s sur la plaque signal tique Cet appareil ne peut tre converti d autres gaz sauf si une trous...

Page 5: ...combustible materials gasoline and other flammable vapors and liquids The flow of combustion and ventilation air must not be obstructed Adequate accessibility clearances must be maintained for servic...

Page 6: ...f the appliance be kept clean Warranty void if not WARNING Do not operate the appliance with the glass door assembly removed or if the glass is cracked or broken Replacement of the glass should be don...

Page 7: ...IDE Left side vent exit MODEL NO BI 48 SSL FORTY8 SINGLE SIDE Right side vent exit MODEL NO BI 48 SSR SIXTY0 SEE THRU MODEL NO BI 60 ST SIXTY0 SINGLE SIDE Left side vent exit MODEL NO BI 60 SSL SIXTY0...

Page 8: ...on at elevations up to 2000 feet in the U S and 1370 meters 4500 feet in Canada without change If your installation is at an elevation greater than those noted consult with the local authority having...

Page 9: ...LP FORTY8 SIXTY0 SEVENTY2 Typical Installation Steady State Efficiency 62 2 68 4 69 73 9 72 6 76 4 Steady State Efficiency 61 63 4 64 8 70 8 70 4 74 8 Annual Fuel Utilization Efficiency AFUE 59 61 4...

Page 10: ...nal Heat Redistribution Outlet Horizontal Vent C L Nailing Flanges Vertical Vent C L Utility Access Panel The Horizontal and Vertical vent centerline dimensions account for the use of a 45 elbow The g...

Page 11: ...rear face of the fireplace must be non combustible Allow clearance for removal of fireplace trim screen and glass The fireplace must be secured to the framing studs using the nailing flanges as shown...

Page 12: ...e requirement 39 93 1 014mm 44 93 1 141mm 51 93 1 319mm GG Minimum wall space required to center viewing area 71 85 1 825mm 81 85 2 079mm 95 85 2 435mm HH Minimum wall space required to center viewing...

Page 13: ...electing non combustible materials for use in the installation take note of the material s propensity to absorb and conduct heat Materials such as metal stone and ceramics may transmit heat more readi...

Page 14: ...pounds used within areas marked as non combustible zones are required to be rated for minimum of 500 F It is normal for the exposed surfaces around the fireplace viewing area to be hot to touch Refer...

Page 15: ...from the junction box outlets attached to the utility access panel 4 Have a licensed electrician hardwire the junction box provided in accordance with local codes The electrical supply required is 120...

Page 16: ...nto your heating zone while remaining quiet With the increased air speed of levels 3 and 4 there will be a noticeable difference in sound We recommend during the annual service on your fireplace Comfo...

Page 17: ...system for installation Before installing the vent kit the installer must read this fireplace manual and vent kit instructions Only a qualified licensed installer service technician shall install the...

Page 18: ...oor level In the event that this requirement cannot be met at the time of completion of the installation of the appliance the owner shall have a period of thirty 30 days to comply with the requirement...

Page 19: ...ratios when using 45 elbows The appliance is approved for use with three 90 elbows maximum or a combination of 90 and 45 elbows up to a maximum of 270 FOR HORIZONTAL TERMINATION All horizontal runs of...

Page 20: ...ustion air inlet to other appliance for appliance 100 000 BTU H 30 KW 12 30 cm 12 30 cm L Clearance to forced air supply inlet 72 183 cm 36 91 cm above air inlet M Clearance above paved sidewalk or pa...

Page 21: ...will include at least one 90 elbow Up to three additional 90 elbows or equivalent 45 elbows may also be used The total venting may not exceed 30 feet of vertical rise and or 12 feet horizontal run Ref...

Page 22: ...Measured as total vertical distance between flanges of elbows used in vent system See Diagram _____________ Feet B TOTAL HORIZONTAL VENT RUN Measured as total horizontal distance between flanges of e...

Page 23: ...terminations are counted as 2 90 elbows D Total Number of 45 Elbows in excess of 1 __________ E 90 Elbow Horizontal Equivalent C x 3 _____ F 45 Elbow Horizontal Equivalent D x 1 5 _____ G Total Horiz...

Page 24: ...GV V GVS GV GV GV GV PV PV PV GV GV GV GV GV GV GV GV V GVS GV GV GV GV PV PV PV GV GV GV GV GV GV GV GV V GVS GV GV GV GV PV PV PV GV GV GV GV GV GV GV GV V GVS GV GV GV GV PV PV PV GV GV GV GV GV GV...

Page 25: ...GV GV GV GV GV GV GV GV V GVS GV GV GV GV PV PV PV GV GV GV GV GV GV GV GV GVS GV GV GV GV PV PV PV GV GV GV GV GV GV GV GV GV GV GV GV GV PV PV PV GV GV GV GV GV GV GV GV GV GV GV GV GV PV PV PV GV G...

Page 26: ...4 Allow the screen to rest in the fireplace opening confirm that the latches are in the home position and engaging the latch magnets 5 Lift the screen up so that the bottom of the screen clears the b...

Page 27: ...lass assembly toward you from the bottom to remove Refer to the next page for instructions on burner media placement GLASS INSTALLATION 1 Insert the glass frame assembly into the fireplace by angling...

Page 28: ...edges that form a tray to hold the glass media 4 Starting at one end pour the glass media onto the burner tray keeping the pouring spout on the poly bag toward the center of the burner to avoid spill...

Page 29: ...CALE 1 3 S LAS Flue Restrictor Kit Part 11210 Some vent configurations may create excess draft within the fireplace Excess draft can cause issues such as a rapid or nervous flame picture undesirable f...

Page 30: ...any reason the pilot flame goes out This device incorporates a fixed probe which senses the heat from the pilot flame If the probe is cool the device will prevent any gas flow unless manually lighting...

Page 31: ...automatically lights the pilot Do not try to light the pilot by hand 3 Using the Remote or the optional Wall Touch Pad push the ON OFF button until you hear an audible signal to ensure the appliance...

Page 32: ...and hold the Control Module s RESET button until you hear one short beep and one long beep After the second beep release the reset button 5 Within the subsequent 20 seconds press and hold the button o...

Page 33: ...breaker Automatic Shut Off in certain conditions Your fireplace s Remote is equipped with an automatic shut off mechanism which is activated in certain conditions See page 38 in the Remote Control Op...

Page 34: ...lower Program Mode Temperature Time Auxiliary Feature not used Countdown Timer Battery Status Split Flow Mode not used F or C DO NOT leave the Remote on the hearth mantel or on top of the fireplace Us...

Page 35: ...al tries call your local service technician or gas supplier TO TURN OFF FIRE Press to turn OFF When the pilot is off it will take 2 minutes before it can be lit again NOTE There is a 2 minute delay af...

Page 36: ...ild Proof is now inactive and the Remote has full function COUNTDOWN TIMER You can set your fireplace to automatically turn off at the end of a timer To set a Countdown Timer 1 Press and hold until is...

Page 37: ...s the temperature for the ON time in Program Mode Changing the Thermostatic Mode set temperature also changes the ON time temperature in Program Mode Default Settings ON TIME Thermostatic TEMPERATURE...

Page 38: ...NOTE The batteries in your S LAS One Touch remote control and control module are to be replaced annually Only use brand name alkaline batteries such as Duracell or Energizer Remote The battery icon w...

Page 39: ...wn No gas supply Air in pilot supply line No spark Reversed polarity in thermocouple wiring F06 F06 4 seconds 3 failed ignition sequences in 5 minutes Fire is not responding no pilot flame No gas supp...

Page 40: ...I LPC SIXTY0 LP CONVERSION KIT 27 PILOT ORIFICE 56 LP BURNER ORIFICE 2PCS 60BI NGC SIXTY0 NG CONVERSION KIT 35 PILOT ORIFICE 49 NG BURNER ORIFICE 2PCS NG INLET TUBE COLLAR 2PCS 8 SCREW 2PCS 72BI LPC S...

Page 41: ...pilot assembly Take extra caution to not damage ceramic electrode on pilot assembly 9 Using a 10mm wrench remove the pilot gas line and swap the pilot orifice with the one supplied in the conversion...

Page 42: ...ng with conversion Close the pressure tap 5 Install a pressure gauge on the outlet pressure tap on the valve 6 Light the fireplace using the remote control 7 With the fireplace set on the highest flam...

Page 43: ...the floor of the fireplace to the left of the Comfort Blower assembly 2 Affix the supplied rating plate conversion label to the rating plate Be sure to not cover the Model and Gas Pressure informatio...

Page 44: ...air system and out the air grills Do not place objects against the fireplace that will block the convection air inlet flow or in front of any air outlet CLEANING GLASS AND PORCELAIN ENAMEL PANELS WAR...

Page 45: ...ne batteries We recommend a name brand such as Duracell or Energizer 5 Replace the battery cover slide control module back into the fireplace and tighten silver thumb screw 6 To reinstall the safety s...

Page 46: ...n n Clean Burner Firebox n n Clean Control Area n n Clean Convection Air System n n Leak Test Gas Connections n n Other___________________________________ Date of Service ____________________________...

Page 47: ...ce LP LPBI 48 Burner LP 48BI 302 Burner Glass Media Clear Mixed 48BI 200 Burner Conversion Kit NG 48BI NGC Burner Conversion Kit LP 48BI LPC Lower Air Trim Panel 48BI 550 PART NAME P N PART NAME P N B...

Page 48: ...ectrode Ignition Cable Module for additional function Connecting Cable Receiver Module Thermocouple GV60 Gas Valve Thermo Current Red Cable UP DOWN ON OFF PM AM Caution Label all wires prior to discon...

Page 49: ...pliance can cause serious damage and will nullify this warranty This warranty is void if a The unit has been operated in atmospheres contaminated by chlorine fluorine or other damaging chemicals b The...

Page 50: ...__________________ Date Purchased __________________ Date Installed ________________________________ solasfires com We recommend that our gas hearth products be installed and serviced by professionals...

Reviews: