25
3. Under “Mode” select the “Pac electric meter” operating mode.
4. Configure the parameters:
Parameter
Description
Value range
Unit
Enable threshold
Activation value
1 000 … 10 000
W
Disable threshold
De-activation value
1 000 … 10 000
W
Enable delay
Activation delay
0 … 60
min
Start time
Activation time
00:00 … 23:59
hh:mm
End time
De-activation time
5. Use MaxTalk 2 Pro to configure the S0 interface (energy counter).
Procedure using MaxTalk 2
1. Start MaxTalk 2
2. Connect MaxTalk 2 to the inverter.
3. Select the inverter in the plant tree.
4. In the “Device” menu, click “Settings”. The “Settings” tab will be opened.
5. In the “Mode” menu (Multi-function relay) select the “PacEm” setting.
6. Configure the parameters.
5�3�2 Configuring the "Pac inverter" operating mode
The functionality of the “Pac inverter” operating mode is illustrated in Figure 12.
5000
4000
3000
2000
1000
0
t
Pac [W]
Disable threshold
Enable delay
On
Off
Status of
multi function relay
Status of multi function relay [on/off]
Output of the inverter - Pac [W]
Start time
End time
Enable threshold
Figure 12 "Pac inverter" operating mode