14
WARNING!
Fatal electric shock hazard!
Cables conducting mains voltage must be covered by the contact protection
inside the inverter.
■
■
Always route the cable through the middle cable glande (Figure 5/Pos. 2).
2. Connect the wires as follows:
– Wire stripping length: 7 mm
Contact
Description
K1
Control signal relay K1
K2
Control signal relay K2
K3
Control signal relay K3
K4
Control signal relay K4
K5
Control signal relay K5
K6
Control signal relay K6 (this input is not evaluated for the external output
control if the SPI logic is used at the same time)
N
Neutral conductor
3. Close the unused holes in the cable gland using the locking pins.
4. Tighten the cable gland (wrench size: 34 mm).
5. Check the cable strain relief.
6. Close the inverter:
– engaging the contact protection;
– then tighten the cover.
You can now switch the inverter on as described in the instruction manual.
4�4�3 SPI logic
With this interface it is possible to connect the inverter to an external SPI frequency
monitoring device ("Segnale Esterno" is only available when "Italy" is selected in the
country setting).
The interface is configured with the free MaxTalk 2 Pro service software.
Procedure
1. Open the inverter as described in the instruction manual.