background image

3

3. Product appearance and installation dimension

 3.1Dimension of indoor unit

3.2 Dimension of outdoor unit 

A
B
C
D

Size

Units: mm

MODEL

390
405
106
500

A

B

575
415

 A
 B

Size

Units: mm

MODEL

MAFP060A

A

B

615
395

MAFP020A

 A
 B

Size

Units: mm

MODEL

MACHRW010W/(B01)
MACHRW020W/(B01D)
MACHRW030W/(B01D)

 C

 D

A

B

615
395

MAFP040A

 A
 B

Size

Units: mm

MODEL

Summary of Contents for SunPump MACHRW010W

Page 1: ...DC INVERTER AIR TO WATER HEAT PUMP INSTALLATION INSTRUCTION MANUAL Sun Sun tm Pump Pump ...

Page 2: ......

Page 3: ...regulations and instruction in this manual 1 3 Please check whether the distribution power capacity switch and socket are compliance with the requirements of our unit power Details please refer to the rating label or parameter table in this manual 1 4 The power should be equipped with leakage protection separately Power cable should be chosen in accordance with the operation requirements of the un...

Page 4: ...stallation drawing 2 Air condition floor heating water system installation drawing 3 V Maintenance and repair 1 Note 2 Malfunction indicating table 3 VI Wiring diagram 1 Indoor Unit wiring diagram 2 Out door Unit wiring diagram 3 4 Three way valve wiring diagram The user interface and function shows as below Use of wire controller 4 Air condition floor heating and hot water side water system insta...

Page 5: ...CR Air cooling and heating CHR Air heating cooling and hot water Energy exchange medium A Refrigerant W Water Z Integrated type W Split type indoor unit A Horizontal fan direction B Upward fan direction Omit the split type unit model B DC Inverter E EVI Without inverter or EVI omitted The figure represents the horse power of unit eg 010 means 1 horse power P With built in pump Without built in pum...

Page 6: ...e IndoorunitNetDimensions L M H IndoorunitShippingDimensions L M H OutdoorunitNetDimensions L M H OutdoorunitShippingDimensions L M H IndoorunitNetWeight IndoorunitShippingWeight OutdoorunitNetWeight OutdoorunitShippingWeight MACHRW kW BTU h kW A kW BTU h kW A kW BTU h kW A KW A A V PH Hz dB A inch m h mm mm mm mm kg kg kg kg 030W B01 7 5 25600 2 34 10 7 10 5 35800 4 15 2 53 11 5 8 3 28400 3 6 2 2...

Page 7: ...door unit 3 2 Dimension of outdoor unit A B C D Size Units mm MODEL 390 405 106 500 A B 575 415 A B Size Units mm MODEL MAFP060A A B 615 395 MAFP020A A B Size Units mm MODEL MACHRW010W B01 MACHRW020W B01D MACHRW030W B01D C D A B 615 395 MAFP040A A B Size Units mm MODEL ...

Page 8: ...connector Needle valve valve plug valve plug nut Needle valve nut Adapter connector nut Indoor unit and outdoor unit copper connecting pipe Stop Valves 2 The refrigerant piping connection for split type unit 2 1 Each component s names and function of refrigerant stop valve Adapter connector Needle valve Valve plug The connecting pipe joint of indoor unit and outdoor unit To discharge the air in th...

Page 9: ... valve valve plug High pressure side Indoor unit Outdoor unit Needle valve valve plug valve plug nut Low pressure side Needle valve valve plug High pressure side Big pipe Small pipe 2 1 As the picture show 2 2 The unit refrigerant pipe connecting A According to the indoor and outdoor unit fixed location and location of holes through the wall choose a good direction lead topipe Then begin the indoo...

Page 10: ...ak detector or soapy water to test all the connectors in the indoor and outdoor unit 2 6 Leak check As the picture show connect the vacuum pump with the pressure gauge and then connect the vacuumed connecting pipe with the needle valve on the indoor unit low pressure side B Unscrew the valve plug nut on the stop valve and unscrew the needle nut on the indoor unit low pressure side C Open the stop ...

Page 11: ...n be used 30mm thickness of glass fiber or high density fire retardant PE for thermal insulation and moisture to prevent cold heat loss and condensation 4 14 The unit water inlet and outlet must install a thermometer water pressure gage to facilitate inspection when operate 3 Installation of terminal equipment 3 1 Indoor terminal equipment installation such as fan coil radiator heater or floor hea...

Page 12: ...ion Circuit breaker Voltage 2 2 5mm 10AMP 2 2 5mm 2 2 5mm 14AMP 20AMP 208 230V 1PH 50Hz 8 The head of sensor The heat conduction silica gel The first step The second step The third step The fourth step The heat conduction silica gel The head of sensor 5 pin 5 pin The heat conduction silica gel 5 pin Detector Tank Tank Tank Tank Detector The head of sensor Detector Detector The head of sensor Note ...

Page 13: ...ystem pressure is normal at the same time 7 2b Check whether the input power and current of the unit are compliance with the parameter in this Instruction If not stop to check the unit 7 2c Observe whether the outlet water temperature is normal 7 2d Parameter of the remote controller has been set before leave of the factory Never alternate them personally 9 6 3 Caution of Ground The internal motor...

Page 14: ... In air conditioning mode it is inlet water temperature Note When manually open auxiliary electrical heating the icon will flash 1 2 3 III USE A B C E F D G H I K J L N O M S R Q P T M M Auxiliary electrical heating icon 4 3 2 The user interface and function shows as below Cover the face covering in the reverse procedures as shown in Illustration 2 and Illustration 1 to complete the mounting of th...

Page 15: ...ight side is the actual temperature of water inlet Hot water mode Air condition mode the unit default priority hot water mode So the unit running hot water mode at first the temperature on the left side of the wire controller is the set temperature of hot water tank and on the right side is the actual temperature of the hot water tank When the hot water tank temperature reaches set temperature the...

Page 16: ...g of minute symbol flickers and the display flickers Press again the hour display flickers Press the button to adjust the setting of the hour Press button again to complete the timming boot setting and enter the timming shutdown setting by this time the hour and the symbol flickers Y Press again the hour display flickers Press the button to adjust the setting of the hour Finally press button to ex...

Page 17: ...ss button again to set value you need Parameter setting as below 4 Parameters Setting Number Means Range Default 20 55 15 45 5 35 1 10 0 1 20 55 2 90min 1 10 55 0 1 0 45 30min The water tank temperature setting of hot water tank mode The water inlet temperature setting of heating mode The water inlet temperature setting of cooling mode Hot water tank mode water tank temperature difference between ...

Page 18: ...e Exit the defrost status setting of coil temperature Heating defrost cycle setting The difference setting of solar cycle pump start working The compensation of water inlet and outlet temperature 5 5 0 2min 20min 8min Model 0 Hotwater 1 Heat 2 Hotwater Heat 3 Cool 4 Heat Cool 5 Hotwater Cool 6 Multifunction Number Means Range Default Note If the unit is with electric heater this parameter is 1 oth...

Page 19: ...ing valve 3 Water supply return valve Hot water tank Water supply cycle pump Unit Water pressure switch Air break switch A B Water supply return temp Hot water tank temp 6 Bath room 7 Hot water cycle pump 8 Outdoor unit 9 Solar water cycle pump C Solar collector temp Note Solar water cycle pump and solar collector temperature effective for the unit with the solar function 2 2 15 Wire controller Un...

Page 20: ...vice Water collection device 3 4 5 Room 1 electrothermal actuator 6 Room 2 electrothermal actuator 7 Room 1 floor heating 8 Room 2 floor heating 9 10 Room 3 electric three way valve Room 4 electric three way valve 11 12 Room 3 Radiators Room 4 Radiators Room 5 electric three way valve Room 6 electric three way valve 13 14 15 Room 5 fan coil 16 Room 6 fan coil 17 Swimming pool three way valve 18 Wa...

Page 21: ... 16 Water collection device Room 1 electrothermal actuator Room 1 floor heating Water distribution device Room 2 electrothermal actuator Room 2 floor heating 15 16 17 18 Room 3 electric three way valve Room 4 electric three way valve Room 3 Radiators Room 4 Radiators 19 Solar A Hot water tank temp B Solar collector temp 5 4 Hot water side and floor heating side system installation drawing by three...

Page 22: ...in or change it in time 1 8 This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons The instructions includes a warning to disconnect the appliance from its power source during service and when replacing 1 Note Means Means Resolution Resolution Wire Controller display Wire Controller display Failure to read and w...

Page 23: ...enish water remove the air of the water system 2 Change anther pump 3 Open the valve of the water system 4 Clean the water filter and the pump Unit heating capacity is low or compressor working too long 1 Shortage of refrigerant or leakage 2 Poor thermal insulation of water system 3 Poor air flow into the air heat exchanger 4 Shortage of water flow 1 Check the system for leakage fix leak and re ga...

Page 24: ...n water until all air expelled 3 Call refrigeration mechanic to reduce refrigerant 4 Call Siddons Service Centre Compressor suction pressure too low 1 Shortage of refrigerant or leakage 2 Filter or capillary blocked 3 Poor condenser heat dissipation 1 Call refrigeration mechanic to check the system for leakage fix the leak and re gas the heat pump 2 Replace capillary tube or filter 3 Clean the hea...

Page 25: ...nput 208 230VAC 1 2 VA2 Compressor U V W Blue White Red Hot water cycle pump power output 208 230VAC KA1 E1 Wiring diagram MB3044 0101 Legend L N L N KA1 Outdoor fan power output 208 230VAC SW1 LCD CONTROLLER LCD CONTROLLER E2 E1E2 VA3 Capacitance Electric expansion valve 4 way valve Unloading valve Water pump relay Crankshaft heater HP1 LP1 SW1 SW2 T1 T2 VA1 VA2 VA3 KA1 CH1 High pressure switch L...

Page 26: ...g diagram MB3043 0101 Legend L N L N KA1 Outdoor fan power output 208 230VAC SW1 LCD CONTROLLER LCD CONTROLLER E2 E1E2 Aux electric heating power input 208 230VAC L1 L2 L1 L2 Y G KM1 Auxiliary electric heater Y G KM1 FP1 L1 L2 VA3 Electric expansion valve 4 way valve Unloading valve Water pump relay Aux electric heater A C contactor Crankshaft heater HP1 LP1 SW1 SW2 FP1 VA1 VA2 VA3 KA1 KM1 CH1 Hig...

Page 27: ...iagram MB3039 0101 Legend L N L N KA1 Outdoor fan power output 208 230VAC T1 SW1 LCD CONTROLLER LCD CONTROLLER E2 E1E2 Aux electric heating power input 208 230VAC L1 L2 L1 L2 Y G KM1 Auxiliary electric heater Y G KM1 FP1 L1 L2 VA3 Electric expansion valve 4 way valve Unloading valve Water pump relay Aux electric heater A C contactor Crankshaft heater HP1 LP1 SW1 SW2 FP1 VA1 VA2 VA3 KA1 KM1 CH1 Hig...

Page 28: ...utdoor fan power output 208 230VAC 3 Between outdoor unit and indoor unit connection Ambient temp Ambient temp Outdoor unit electric box Outdoor unit electric box Coil temp Coil temp Ambient temp Ambient temp PCB PCB 24 2 Outdoor unit wiring diagram WIRING DIAGRAM F04 L N Black Orange Red Fan Y G White Capacitor Coil sensor Ambient sensor Outdoor fan Power input 220V 1PH 50Hz ...

Page 29: ...B and outflow from A When the unit running air condition mode T for three way valve shown in figure 1 the water inflow from the AB and outflow from B Attention and Explanation 1 heck whether the model of electric three way valve is that mention above 2 heck whether electric three way valve T port is as shown in the picture f not Please adjust the 3 way valve T port with forceps as shown in the pic...

Page 30: ......

Page 31: ......

Page 32: ...laris Warehouse LEI 456 Humber Place Annacis New Westminster B C V3M 6A5 TEL 604 5223 5100 Solaris Geothermal Inc Office 3222 Comox Court Abbotsford B C V2S 7B4 tel 604 758 2012 www solar hot water ca admin solar hot water ca Solaris Warehouse LEI 456 Humber Place Annacis New Westminster B C V3M 6A5 TEL 604 5223 5100 DC INVERTER AIR TO WATER HEAT PUMP ...

Reviews: