48
L20, L30
OUTPUT dry contact:
Contains a total of 4 output dry contacts. User can choose different
function for OUT 01~04. And choose Normally Closed/ Normally Opened, the default value
is Normally opened.
Each dry contact has 16 functional options, including UPS Warning, Online Mode,
Battery Mode, Bypass Mode, INV Overload, Fan Fault, BATT Fault, BATT Disconnect,
BATT Low Volt, Mains Abnormal, BYP Not Available, EPO, Maint Mode, Parallel Comm
Fault, ECO Mode, Close.
OUT 01:
The default value is UPS Warning.
OUT 02:
The default value is Bypass Mode.
OUT 03:
The default value is BATT Low Volt.
OUT 04:
The default value is Online Mode.
NOTE!
Each output dry contact can be N.O or N.C.