SolarEdge L20-IB00 User Manual Download Page 50

41

L20, L30

NOTE!
This operation is recommended to be operated by professionals, or under the

guidance of professionals.

Summary of Contents for L20-IB00

Page 1: ...Uninterruptable Power Supply for 400VAC Grid L20 IB60 L20 IB00 L30 IB60 L30 IB00 User Guide Version 2 0 March 2022 Cat No 2MUM...

Page 2: ......

Page 3: ...ssion of SolarEdgeInc All company and brand products and service names are trademarks or registered trademarks of their respective holders Patent marking notice see http www solaredge com patent The g...

Page 4: ...d maintenance of the UPS and batteries allowing you to correctly set up your system for the maximum safety and performance Included is information on customer support and service if it is required If...

Page 5: ...14 4 1 2 Battery mode Stored energy mode 14 4 1 3 Maintenance mode Manual bypass 15 4 1 4 Bypass mode 15 4 1 5 ECO mode 16 4 2 UPS OPERATION 17 4 2 1 Start procedure 17 4 2 2 Test procedure 17 4 2 3...

Page 6: ...ing 44 4 3 7 5 Dry contact setup 46 4 3 8 Maintenance Touch correction and battery self test 48 4 3 8 1 Battery self check 49 4 3 8 2 Timing daily 49 4 3 8 3 Timing weekly 49 4 3 8 4 Cycle mode 50 4 3...

Page 7: ...PAGE 13 FIGURE 8 MUSER5000APPEND EQUIPMENT MANUAL SETTING PAGE 13 FIGURE 9 NORMAL MODE 14 FIGURE 10 BATTERY MODE 15 FIGURE 11 MAINTENANCE MODE MANUAL BYPASS 15 FIGURE 12 BYPASS MODE 16 FIGURE 13 ECO...

Page 8: ...DIMENSIONSAND WEIGHTS 10 TABLE 4 COMMUNICATION PANEL 11 TABLE 5 LCD ANDLED DISPLAY 23 TABLE 6 OPERATIONAL STATUSAND MODE S 55 TABLE 7 FAULT INFORMATION 56 TABLE 8 ALARM INFORMATION 58 TABLE 9 RELAY C...

Page 9: ...ons in this document are according to IEEE 280 Standard Letter Symbols for Quantities Used in Electrical Science and Electrical Engineering 1 2 Safety Symbols Information The following safety symbols...

Page 10: ...not proceed beyond a warning note until the indicated conditions are fully understood and met 1 3 Technical Support You can contact technical support via any of the following methods SOLAREDGE Inc Cr...

Page 11: ...electrical shock do not remove cover No user serviceable parts inside Refer servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is not i...

Page 12: ...ed in a service access area 1 Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions 2 Risk of explosion if battery is replace...

Page 13: ...PS indicator is on the unit s outlets may have a dangerous amount of voltage even when not plugged into the wall outlet because the battery may continue to supply power Care should be taken to underta...

Page 14: ...L20 IB00 20 kVA L20IB A6G0V09001 L20 3PH 4W UPS 400V 20KVA 20KW IB00 L20 IB60 20 kVA L20IB A6G3V09001 L20 3PH 4W UPS 400V 20KVA 20KW IB60 L30 IB00 30 kVA L30IB A6G0V09001 L30 3PH 4W UPS 400V 30KVA 30K...

Page 15: ...al Control This series UPS is controlled by Digital Signal Processor DSP hence it increases reliability performance self protection self diagnostics and many more Battery is Configurable The battery v...

Page 16: ...r internal batteries make up the system Depending on the site and load requirements of the installation certain additional options are available for the solution Planning a UPS system the following sh...

Page 17: ...9 L20 L30 3 4 Cabinet view Figure 1 Front view Side view of L20 and L30...

Page 18: ...oor and Rear View of L20 and L30 Table 2 Cabinet overview 1 LCD panel 2 Terminal block for Input output GND 3 Bypass Switch 4 Mains Switch 5 Maintenance switch 6 Output switch 7 Communication panel 8...

Page 19: ...10 L20 L30 3 5 Dimensions and Weight Figure 3 Dimensions Table 3 Dimensions and Weights Model Width Depth Height Net weight L20 IB60 250mm 900mm 868mm 237kg L20 IB00 250mm 900mm 868mm 77kg...

Page 20: ...panel Table 4 Communication panel 1 Cold start button 2 USB port for LCD upgrade 3 RS232 port 4 USB port for computer connect 5 RS485 port 6 BAT_T dry contact Temperature sensor port for NTC 7 REPO po...

Page 21: ...the USB port on the UPS 2 Open the software Muser5000 click system button Figure 5 Muser5000 homepage 3 A window of Software Parameter Setting comes out as below COM chooseaccording to the UPS baud ra...

Page 22: ...e 5 Fill the UPS name field with Equipment Name and UPS ID address fieldwith Equipment address Figure 8 Muser5000 Append equipment manual setting page 6 Click the button Append then the connection bet...

Page 23: ...oosting charge the battery simultaneously Then the inverter converts the DC power to AC and supplies to the load SINGLE INPUT Mains Input DUAL INPUT Mains Input and Bypass Input Figure 9 Normal mode 4...

Page 24: ...l bypass 4 1 4 Bypass mode In case the inverter is out of order or if overload occurs the static bypass will be activated to transfer the load from the inverter supply to bypass supply without interru...

Page 25: ...ECO mode to increase the efficiency of the power supplied At ECO mode the UPS works at line interactive mode so the UPS will transfer to bypass supply When the AC is out of set window the UPS will tra...

Page 26: ...ctifier fails at startup the fault LED will light up When the inverter starts up the UPS will transfer inverter mode then the inverter LED lights up 5 Make sure that the batteries parameters match the...

Page 27: ...e jump to Step 5 1 Open the cover of maintenance switch the UPS switches to maintenance bypass mode automatically At this time the bypass source will supply 2 Turn on maintenance breaker 3 Switch off...

Page 28: ...ed from bypass mode to normal mode 4 2 6 Cold start procedure CAUTION Follow these procedures when the input AC Utility Failure but battery is normal The model is connected to the battery docking term...

Page 29: ...n the inverter navigate to common inv on off single off see4 3 9 1 2 Switch off the battery breaker 3 Switch off the mains breaker 4 Switch off the bypass breaker 5 Open the output breaker 6 To comple...

Page 30: ...l setting Connect the UPS with computer Power on the UPS Open Muser5000 software after connecting with the UPS successfully click System User Set Figure 14 Muser5000 homepage Click Set at User Set win...

Page 31: ...as shown in below picture If the UPS sounds a beep that means the setting is correct Figure 16 Muser5000 work mode setting page At the window of Data Set click Ups ID write a value for the parallel U...

Page 32: ...quipment might be interrupted If it happens re connect in accordance with the instruction above CAUTION Parallel cable cannot be connected when setting the parallel parameters After setting the UPS sy...

Page 33: ...24 L20 L30 4 3 LCD control panel 4 3 1 Overview Figure 18 LCD control panel introduction Table 5 LCD and LED display 1 Fault LED 2 Bypass mode LED 3 Battery mode LED 4 Inverter work LED 5 LCD display...

Page 34: ...bed in this manual This chapter describes the UPS GUI its functions and navigation On any screen click return to return to the previous window click home page to return to the main window CAUTION The...

Page 35: ...iew the voltage and current of the main bypass output battery can also be entered through by real time data block View the status of the switches dry contacts through clicking on the block enter the c...

Page 36: ...27 L20 L30 4 3 4 1 Main Click the main block to enter the main data display window...

Page 37: ...28 L20 L30 4 3 4 2 Bypass Click the bypass block to enter the bypass data display window 4 3 4 3 Output Click the output block to enter the output data display window...

Page 38: ...29 L20 L30 4 3 4 4 Battery Click the battery block to enter the battery data display window...

Page 39: ...30 L20 L30 4 3 4 5 Status info Click the Status info to enter the Status info display window...

Page 40: ...31 L20 L30...

Page 41: ...32 L20 L30 4 3 5 Alarm View the alarm and history of the UPS and open or close the buzzer 4 3 5 1 Current alarm Click Current alarm to enter the current alarm display window...

Page 42: ...4 3 5 3 Buzzer Click the Buzzer mute the buzzer will mute and the red block will change to green if the buzzer is on then click the icon the buzzer will turn on and the button will change to red Click...

Page 43: ...34 L20 L30 4 3 6 Setting There are two levels of access The basic setting for user settings Advanced setting for technical personnel...

Page 44: ...35 L20 L30 4 3 6 1 Basic setting Click basic setting log in with the correct password The user password is 111111...

Page 45: ...4 3 6 3 Password Click password icon enter user password setting page input old password and new password then click save confirm to save the change Password format is six digits Password lock time wh...

Page 46: ...ue Brightness Click the text to input new value and click the save config icon to save Value range is 10 63 default value is 63 Backlight time LCD backlight delay time click the text to input new valu...

Page 47: ...TE For the time to be saved even when the system is in shutdown install a small battery CR32 on the motherboard 4 3 6 6 Communication setting Click the text to select other value or input new value an...

Page 48: ...es that the bypass voltage is not normal and that the bypass is unavailable NOTE When the voltage level is 220V the value range is 10 15 20 25 and 25 default When the voltage level is 230 V the value...

Page 49: ...number of transfers between bypass mode and normal mode within 1 hour which ensures system security The value can be 3 to 10 and is 10 by default EPO Transfers To BYP Specifies whether transfers to b...

Page 50: ...41 L20 L30 NOTE This operation is recommended to be operated by professionals or under the guidance of professionals...

Page 51: ...e text to select other value or input new value and click save config icon to save Working Mode Select the work mode of UPS Single mode Parallel mode ECO mode Eco Parallel Machine Mode Aging Load Rate...

Page 52: ...485 for multiple and fardistance Inter Power Walk in s When UPS systems are in parallel mode this enables the UPS to control the interval that each UPS transfers from battery mode to normal mode which...

Page 53: ...redundancy cabinet number can modify the redundancy cabinet number after set work mode to parallel mode The value canbe 0 1 default value is 0 maximum allowed value is 1 because only two UPS systems o...

Page 54: ...to actual configuration For L20 IB00 the value can be 16 26 For L30 IB00 the value can be 30 50 Default value is 20 for L20 IB00 and 30 forL30 IB00 Single Battery Capability AH Must modify the value...

Page 55: ...oat voltage value can be 2 20 2 29 V cell and is 2 25 V cell by default Cell boost volt The battery equalized voltage value can be 2 30 2 40 V cell and is2 30 V cell by default Aver charging Duration...

Page 56: ...is enabled by default 4 3 7 5 Dry contact setup INPUT dry contact Contains a total of 4 input dry contacts User can choose different function for IN 01 04 Each dry contact has 16 functional options in...

Page 57: ...tional options including UPS Warning Online Mode Battery Mode Bypass Mode INV Overload Fan Fault BATT Fault BATT Disconnect BATT Low Volt Mains Abnormal BYP Not Available EPO Maint Mode Parallel Comm...

Page 58: ...49 L20 L30 4 3 8 Maintenance Touch correction and battery self test...

Page 59: ...y Timing Daily Timing Weekly Cycle Mode The default value is Timing Self Check Close 4 3 8 2 Timing daily Modify the check date time and check time 10S default 10min EOD 4 3 8 3 Timing weekly Modify t...

Page 60: ...51 L20 L30 4 3 8 4 Cycle mode Modify the check date time and check time 10S default 10min EOD...

Page 61: ...ar 4 3 9 1 INV ON OFF Single OFF turns the Inverter OFF and transfers the load tobypass Single ON Inverter ON Parallel OFF Inverter OFF all parallel UPS systems all UPS systems in parallelwill transfe...

Page 62: ...53 L20 L30 4 3 9 2 Battery test 10S battery test for 10s 10min battery test for 10min EOD battery test to EOD 10 battery test down 10 capability...

Page 63: ...54 L20 L30 4 3 9 3 Fault clear Clear the current fault not for all faults 4 3 10 Monitor and LCD software version...

Page 64: ...55 L20 L30...

Page 65: ...Alarm Bypass Battery Inverter UPS Initialization Beeps Only ring once No Blink 0 5s Blink 0 5s Blink 0 5s Blink 0 5s UPS Online Mode Normal NO Beeps NO Beeps Off Off Off On UPS Battery Mode Beeps 2s Y...

Page 66: ...EC Over Current Beep continuously Fault LED lit 4 005 REC Power Fault Beep continuously Fault LED lit 5 007 Input SCR Fault Beep continuously Fault LED lit 6 00A Battery SCR Fault Beep continuously Fa...

Page 67: ...t Circuit Once per second Fault LED blinking 24 054 INV Comm Fault Once per 2 seconds Fault LED blinking 25 057 INV Initializes Fault Beep continuously Fault LED lit 26 05A INV self test Fault Beep co...

Page 68: ...per second BATTERY LED blinking 3 105 Battery Reverse Twice per second BATTERY LED blinking 4 106 Battery EOD Once per second BATTERY LED blinking 5 107 Battery Voltage low Once per second BATTERY LED...

Page 69: ...per 2 seconds FAULT LED blinking 19 141 Bypass Switch to Num Once per 2 seconds BYPASS LED blinking 20 142 Unit quantity mismatch Once per 2 seconds FAULT LED blinking 21 143 Parallel Overload Once p...

Page 70: ...multiple operating systems Windows Mac Linux UPS can be monitored remotely through the network Can realize web based user interface Support e mail alarm Multi user permission management Support DHCP...

Page 71: ...of Bypass Utility Failure Inverter On Battery Low UPS fault UPS Alarm and UPS Shutdown The relay communication card contains six dry contact outputs and one dry input The inputs and outputs are facto...

Page 72: ...ontacts communication card Pin Function Description Input or Output 1 Utility Failure Output 2 Battery Low 3 4 Bypass On 5 UPS Fault 6 Inverter On 7 Summary Alarm 8 common 9 Remote Shutdown Input 5 12...

Page 73: ...echnical rating 20kW power module x1 30kW power module x1 Efficiency with linear load Normal mode Up to 95 5 ECO mode Up to 99 Short circuit capacity Icc KAIC 10 Parallel system integrated parallel St...

Page 74: ...A Battery Battery types VRLA Build in battery 60pcs 9Ah 60pcs 9Ah 120Vdc 180Vdc Battery block flexibility Optional Voltage 96 108 120 132 144 156Vd c 16 18 20 22 24 26pcs optional 192Vdc 312Vdc 16 26p...

Page 75: ...Output PF 1 Output voltage 380 400 415Vac 3Ph N PE Static regulation of output 1 Slew rate Maximum frequency variation 0 5 2Hz s Bypass source voltage windows setup and Frequency windows setup Frequen...

Page 76: ...63A 3P Internal output 40A 3P 63A 3P User interface Display Color touch screen 7 inches SNMP card optional Megatec SNMP Relay card optional Relay card Communicati on port USB S232 RS485 Parallel Batte...

Page 77: ...tical Noise from 1M distance 58dB Altitude Up to 1000 m without derating Physical Dimension D W H mm See Table 3 Service Access Back 500mm Right side 1000mm Left side 1000mm Front 1000mm Top 500mm Ter...

Page 78: ...69 L20 L30 Model L20 L30 STANDARDS Safety Approvals EN 62040 1 2008 A1 2013 and IEC 62040 1 2008 EMC Approvals EN IEC 62040 2 2018 IEC 62040 2 2016...

Page 79: ...ge low The input switch of the UPS is not switched on Measure if the UPS input voltage frequency is within the window Check if UPS input is switched on 2 Utility normal but Utility LED does not light...

Page 80: ...ircuit Make sure the load is not in short circuit and then restart the UPS 8 The UPS only works on bypass mode The UPS is set to ECO mode Set the UPS working mode to Normal mode 9 Cannot Black start B...

Page 81: ......