L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40,
L15US-IB60 L15US-IB00, L20US-IB60, L20US-IB00 UPS
CAUTION!
An unused battery must be recharged every 6 months. Temporarily connecting
the UPS to a suitable AC supply main and activating it for the time required for
recharging the batteries.
•
The highest altitude that UPS may work normally with full load is 1000 meters (3281 ft).
The load capacity should be reduced when this UPS is installed in place whose altitude is
higher than 1000 meters, shown as the following table:
(Load coefficient equals max load in high altitude place divided by nominal power of the
UPS)
Table 2 Load coefficients
Altitude
(m/ft)
1000/
3281
1500/
4921
2000/
6562
2500/
8202
3000/
9843
3500/
11483
4000/
13123
4500/
14764
5000/
16404
Load
coefficient
100%
95%
90%
85%
80%
75%
70%
65%
60%
•
The UPS should be kept in a well-ventilated room. There are many ventilation holes on
front and rear, they must not be blocked by any obstacles.