background image

                 MAN-01-00028-1.1 

 

 

Appendix A – Multiple SolarEdge Devices, RS485 Bus and GSM Modem Connection 

This configuration enables you to connect multiple 
SolarEdge devices through the same bus in a master/slave 
configuration. In this configuration, only the master is 
physically connected to the Internet through the GSM 
modem. 

Recommended Cable Type and Distance: 

 

RS232: 

 

Cable Type:

 Supplied with kit. 

 

Max. Distance: 

15 m / 50 ft (supplied cable plus 

extension).

 

 

RS485: 

 

Cable Type:

 Four-conductor cable (with RJ11 

connectors for older communication board 
versions).

 

 

Max. Distance: 

1,000 m / 3,000 ft

 

(from the 

master SolarEdge device).

 

 

Figure 5: Connecting Multiple SolarEdge devices 

 

Additional Required Equipment: 

 

Four-conductor cable (not supplied by SolarEdge). 

This section assumes that GSM modem communication is already 

configured, as described above. 

 

 

RS485 bus terminations: 

The two SolarEdge devices at the ends of the chain (meaning the first 
SolarEdge device and the last SolarEdge device) must be terminated by 
switching a termination dip-switch inside the SolarEdge device to ON. 
The switch is marked 

SW7

, as shown in Figure 6. 

 

Configuring the SolarEdge devices using the user 
buttons: 

First, configure the GSM cellular modem connection, as described 
above. 

For each of the slave SolarEdge devices, perform the remaining 
steps in this procedure. 

  

Figure 6: RS485 Termination Switch 

Verify that the SolarEdge device’s ON/OFF switch is OFF. 

Press the LCD Light button once to turn ON the backlight. 

 

WARNING! 

If the SolarEdge device worked properly before this action, the adjacent message 

is displayed. 

This message is displayed until the DC is safe. The default safety voltage is 50 V. 

Do not open the cover or open DC connectors until the voltage is indicated as 

safe or until at least five minutes have passed.

 

Short press the LCD button to scroll through the 
informative screens to show the ID status window and 
verify the CPU firmware version. Verify whether it is 
below or above version 2.250. 

I D    :    #  #  #  #  #  #  #  #    #  #         
D S  P  1  /  2  :  1  .  0  2  1  0  /  1  .  0  0  3 4 

C P  U  :  0  0  0  2  .  0  2  5  0   

           

C o  u  n  t  r  y  :  U  S  A                   

The following configuration procedures are performed 
with the SolarEdge device cover open.  

Four buttons for controlling the LCD panel menus are 
then accessible, as shown in Figure 4. 

 

Esc:

 Goes to the beginning of the currently entered 

parameter or to the previous menu. 

 

Up

 

(1):

 Goes up one option in a menu. 

 

Down

 

(2):

 Goes down one option in a menu. 

 

Enter (3):

 Confirms the entry or selection of a 

parameter. 

6

  Press the 

Enter

 button for at least five seconds. The 

following message is displayed:  

      P  l  e  a  s  e    e  n  t  e  r           
      P  a  s  s  w  o  r  d                   
          *  *  *  *  *  *  *  *               
                                       

The SolarEdge device is now in Setup mode and all its 
LEDs are lit. The SolarEdge device automatically exits 
Setup mode if no buttons are pressed for more than two 
minutes.

 

Use the left switch  

Summary of Contents for GenPro 20e SQB

Page 1: ...the AC power off and wait five minutes 5 Open the SolarEdge device cover as instructed in the device manual 6 Open gland 1 located on the bottom of the SolarEdge device as shown in Figure 2 Figure 2 shows the SMI as an example The procedure is similar for the inverter Figure 2 Cable Gland Location on SMI The smallest hole is for RS232 cable insertion The SolarEdge device glands come presealed from...

Page 2: ...ce cover Four buttons for controlling the LCD panel menus are then accessible as shown below Esc Goes to the beginning of the currently entered parameter or to the previous menu Up 1 Goes up one option in a menu Down 2 Goes down one option in a menu Enter 3 Confirms the entry or selection of a parameter Figure 4 LCD Panel Menu Buttons 5 Press the Enter button for at least five seconds The followin...

Page 3: ... Conf submenu select Set Password and then enter the password if required by the GSM service provider Press the Enter button for a long press to apply or press the ESC button for a long press to abort Verifying the Connection To verify the connection 1 Wait for the SolarEdge device to connect to the SolarEdge Monitoring Server This may take up to two minutes 2 Verify that the LCD panel displays a ...

Page 4: ...the remaining steps in this procedure Figure 6 RS485 Termination Switch 2 Verify that the SolarEdge device s ON OFF switch is OFF 3 Press the LCD Light button once to turn ON the backlight WARNING If the SolarEdge device worked properly before this action the adjacent message is displayed This message is displayed until the DC is safe The default safety voltage is 50 V Do not open the cover or ope...

Page 5: ...SolarEdge RS485 X Submenu D e v i c e T y p e S E P r o t o c o l M D e v i c e I D 1 S l a v e D e t e c t 15 Select the Protocol submenu and set it to Slave 16 Press the ESC button repeatedly to exit the Setup menu or wait for the device to automatically exit Setup mode if no buttons are pressed for more than two minutes This concludes the slave device configuration using the LCD button for firm...

Page 6: ... Yes A Detecting Slaves message is shown during the detection process The master should report the correct number of slaves on the LCD screen If it does not verify the connections and terminations 11 Press the ESC button repeatedly to exit the Setup menu This concludes the multi SolarEdge device setup using the user buttons Support and Contact Information If you have technical questions concerning...

Reviews: