MAN-01-00028-1.1
3
10
Scroll down to the
RS232 Conf
submenu and select it.
Communication Submenu:
S e r v e r < L A N >
B u s < Z i g B e e >
L A N C o n f
R S 4 8 5 C o n f < S >
Z i g b e e C o n f < S >
> R S 2 3 2 C o n f
M o d b u s C o n f
11
In the
RS232 Conf
submenu, select
Set Mode
and then select
GSM
. The SolarEdge device performs a reset immediately
after the selection is made.
12
Repeat steps
5
through
7
to enter Setup mode.
13
Scroll down to the
RS232 Conf
submenu and select it.
Follow steps
14
through
20
for firmware versions above 2.250. For earlier versions, complete steps
17
through
20
below.
14
Select the
Server
submenu, scroll down to the
RS232
option and select it.
15
Scroll down to the
RS232 Conf
submenu and select it.
16
In the
RS232 Conf
submenu, select
Protocol
and then select
GSM Modem
.
17
In the
RS232 Conf
submenu, select
Set Modem Type
and then select
SE GSEG-20E GSM
.
18
In the
RS232 Conf
submenu, select
Set APN
and enter your GSM service provider’s Access Point Name (APN). This
network address can be obtained by calling your service provider.
Press the
Enter
button for a long press to apply or press the
ESC
button for a long press to abort.
19
In the
RS232 Conf
submenu, select
Set User Name
and enter the user name, if required by the GSM service provider.
Press the
Enter
button for a long press to apply, or press the
ESC
button for a long press to abort.
20
In the
RS232 Conf
submenu, select
Set Password
and then enter the password, if required by the GSM service provider.
Press the
Enter
button for a long press to apply or press the
ESC
button for a long press to abort.
Verifying the Connection
►
To verify the connection:
1
Wait for the SolarEdge device to connect to the SolarEdge Monitoring Server. This may take up to two minutes.
2
Verify that the LCD panel displays a window similar to the following:
V a c [ v ] V d c [ v ] P a c [ w ]
2 3 0 . 7 5 . 2 V 0 . 0
< S _ O K >
O F F
NOTE:
If the
S_OK
indication is not displayed, then perform the following:
Use another method (unrelated to the SolarEdge device) to check whether the network and modem are operating properly. For
example, connect a laptop to the Ethernet modem and connect to the Internet.
Check the Server Communication status screen by short pressing the LCD button. If the
Modem Disconnected
message (appears
only in firmware version 2.250 and above) is displayed, verify the physical connection between the modem and the SolarEdge device
or reset the GSM modem.
Check the Server Communication status screen by short pressing the LCD button. If the
Absent or Locked SIM
message is displayed,
check that the SIM card is fully inserted in the right direction.
Verify with your GSM network provider that the SIM card is not locked for GPRS data usage.
Verify that there is cellular reception near the GSM modem.
Check the configuration of the SolarEdge device.
S_OK:
Verify that S_OK appears on the panel to
indicate a functioning connection to the SolarEdge
Monitoring Server, which was validated during the
last two minutes.