Notifications and Faults

Notifications and faults are found on the diagnostic screen. To access the diagnostic screen, push 

the refresh button once to refresh the display then a second time for the diagnostic screen.

Notifications:

Battery Offline

 – This notification indicates that the Battery Status Indicator lost communication with 

the battery. It may have taken itself offline to protect from over-discharge. Toggle the POWER switch 

to clear notification. If this doesn’t clear the fault, apply a charging source with the POWER switch 

turned ON for at least two (2) minutes. If this fails to clear the fault, contact Solar Stik.

Battery Voltage Low

 – “Battery voltage low” fault occurs when the ESM battery voltage falls 

below 20 VDC. It is only a notification. It does not cause the battery to shut off. This notification 

automatically clears after charging brings voltage to >20 VDC.

Faults:

The battery may report one or more faults at a time on the diagnostic screen. If a condition other than 

the ones shown below appears, contact Solar Stik for assistance. Faults place the ESM 2000 into 

Protected mode until the fault is corrected and the ESM returns to Operational mode 

or

, if the fault is 

not cleared in 60 minutes, the ESM 2000 will enter Storage mode even if the POWER switch remains 
in the ON position.

Table 1. Faults reported on diagnostic screen: and solutions

Fault Name

Value Exceeded 

Clear Value

Critical Cell Overvoltage for 2 
minutes

Max Cell V > 4.2000 V

Max Cell V < 3.8000 V

Critical Cell Undervoltage

Cell Voltage < 2.00 V @ < 120 A 
discharge (battery voltage < 16.0 VDC)

Automatically clears fault one time 
after 2-minute delay. If fault occurs 
again without charging battery for 2 
minutes, must clear by charging for 2 
minutes or toggling the POWER switch 
ON>OFF>ON.

Critical Cell Temp High

Max Cell Temp > 76 ºC

Reduce Cell Temp to < 65 ºC

Critical Board Temp High

Max Elec Temp 1 or 2 > 120 ºC

Reduce Max Elec Temp to < 90 ºC

Hardware Overload

Current > 3000 A

2-minute cool down, followed by toggling 
the POWER switch ON>OFF>ON

Fast Software Overload

Current > 1500A 30 ms

2-minute cool down, followed by toggling 
the POWER switch ON>OFF>ON

Software Overload

Max Elec Temp 3 > 135 ºC

2-minute cool down, followed by 
reducing Elec Temp 3 to < 90 ºC

ESM 2000 TROUBLESHOOTING

Frequent visual monitoring of ESM 2000 Battery Status Indicator for all batteries in a bank is the best 

method to ensure each battery is operating normally. The SOC should be approximately the same 

for each battery. The voltage reported in the upper left corner is bus voltage when the ESM 2000 is 

connected to an active system and battery voltage when it is disconnected from all other equipment. 

If a NOTIFICATION or FAULT is displayed on the screen take the prescribed corrective action to clear 

the fault.

Summary of Contents for 21-0202317

Page 1: ...l 2022 Solar Stik Inc OPERATOR AND MAINTENANCE MANUAL FOR THE 24VDC Li ESM 2000 Updated 20220408 DISTRIBUTION STATEMENT A Approved for public release distribution is unlimited Initial Release P N 21 0...

Page 2: ...ARNING IMPORTANT PRODUCT SAFETY INFORMATION AND INSTRUCTIONS This manual contains important safety instructions that must be followed during the installation and operation of this product Read all ins...

Page 3: ...the fire is out Move forward or around the fire as the fire diminishes Watch the area for reignition until the cause has been fixed Large fires use large quantities of water for the surrounding fire...

Page 4: ...es shown in this manual may not exactly match the unit purchased This equipment CAN BE USED FOR CONNECTION WITH LIFE SUPPORT SYSTEMS OR OTHER MEDICAL EQUIPMENT or devices however without limiting the...

Page 5: ...andling Requirements 9 Location and Description of Major Components 10 ESM 2000 Front 10 ESM 2000 Front Detail 11 ESM 2000 Right Side 12 ESM 2000 Left Side 12 ESM 2000 Bottom 13 ESM 2000 Top 13 ESM 20...

Page 6: ...s 24 Battery Status Indicator 24 In service Battery Status Information 25 Diagnostic Screen 25 ESM 2000 TROUBLESHOOTING Notifications and Faults 26 MAINTENANCE CHARGING INSTRUCTIONS In storage ESM sta...

Page 7: ...tor 21 Figure 11 Connecting ESMs to Inter Connect Strip 7 a battery bank 21 Figure 12 Connecting ESMs to Solar Stik power management examples 22 Figure 13 Activate ESM 2000 23 Figure 14 Battery Ststus...

Page 8: ...em CAN bus Controller area network CAN is a multi master serial bus standard for connecting electronic control units ECUs also known as nodes DRMO Defense Reutilization and Marketing Office EOL End of...

Page 9: ...82 Ah Energy Density 72 2 Wh kg Max Charge Rate 100 A continuous Max Discharge Rate 100 A continuous Cycle Life 1000 cycles to 30 capacity for loss at 38 C 500 cycles to 30 capacity loss at 50 C Batte...

Page 10: ...Maintenance Manual for the 24VDC Li ESM 2000 April 2022 Solar Stik Inc 10 ESM 2000 Front Figure 1 ESM 2000 front Detailed information provided in Figure 2 on page 11 Location and Description of Major...

Page 11: ...ery and provide CAN communications configuration and other necessary signals to and from the BMS Refresh Display Momentary switch push to update battery status display In case of fault push once to di...

Page 12: ...sure differentials between interior and exterior of case Auto stowing handle Handles one on each side of case return automatically to stowed position after use Breather valve Auto stowing lift handle...

Page 13: ...nd Maintenance Manual for the 24VDC Li ESM 2000 ESM 2000 Bottom Figure 5 ESM 2000 bottom Stacking Grooves Stacking Ridges Data and Information Placards ESM 2000 Top Figure 6 ESM 2000 top Detailed info...

Page 14: ...Operator and Maintenance Manual for the 24VDC Li ESM 2000 April 2022 Solar Stik Inc 14 ESM 2000 Top Data and Information Placards Figure 7 ESM 2000 data and information placards ESM 2000 Top...

Page 15: ...ravels with the shipment Li ESM Ground Transport Li ESM 2000 Air Transport The following information is a summary of the conditions that apply to the 24VDC Li ESM 2000 for air transport Dangerous Good...

Page 16: ...sposal process for the Li ESM it must be fully discharged Consult your local Hazardous Waste Storage Area HWSA Defense Reutilization and Marketing Office DRMO or other local authorities for the standa...

Page 17: ...atteries have an inherent finite cycle life and several factors determine how many cycles a battery can endure before it is depleted These include but are not limited to Operational environments and c...

Page 18: ...cuits engage and remove the cells from service disabling the battery at its terminals until proper operating conditions are restored Information from the BMS such as State of Charge State of Health an...

Page 19: ...useful capacity will decrease The SOH algorithm keeps track of many battery parameters and uses them along with characteristics from the cells themselves to estimate the battery s life Batteries such...

Page 20: ...ters a low power state While the ESM in is in Storage Mode the BMS does not communicate with the Battery Status Indicator because the circuitry is powered down to extend battery shelf life Note The ES...

Page 21: ...ip OPERATOR INSTRUCTIONS Prior to operating the ESM in an HPS for the first time charge it fully with a PRO Verter Power Hub or an other charging source such as a battery charger until the battery rea...

Page 22: ...PAK ONLY and may be treated as the functional equivalent to ESM ONLY Individual ESMs or a bank of ESMs can be connected to these ports ESM specific ports are metered and measure the energy flowing int...

Page 23: ...battery is in normal operating condition Figure 13 Activate ESM 2000 Safety pin POWER switch Battery Status Indicator Startup Screens 1 Firmware version and date 2 CAN bus auto termination status 3 C...

Page 24: ...y by a five segment fuel gauge Each segment represents 20 increments up to 100 Each segment fills completely when the SOC reaches the lowest percentage for that segment For example the segment on the...

Page 25: ...storage mode even with the POWER switch in the ON position Additional information about the fault s can be found on the second page of the Battery Status Indicator Figure 16 Battery Status Indicator h...

Page 26: ...torage mode even if the POWER switch remains in the ON position Table 1 Faults reported on diagnostic screen and solutions Fault Name Value Exceeded Clear Value Critical Cell Overvoltage for 2 minutes...

Page 27: ...If the ESM is stored at temperatures above 90 F 32 C then intervals between maintenance checks and or charges should be reduced to three 3 months In storage Battery Status Refresh Voltage SOC and SOH...

Page 28: ...t at less than 0 5 A At this point the ESM 2000 can be considered to be fully charged Maintenance Charging The 24VDC ESM 2000 has a high current capacity For this reason a constant voltage type mainte...

Page 29: ...gle POWER switch to refresh Battery Status Monitor Indicator 2 If SOC less than or equal to 50 charge to 100 SOC See Maintenance Charging If an Li ESM does not hold a charge after 48 hours of charging...

Page 30: ...s must be made to Solar Stik immediately after discovering the defect and within the warranty period or are forever waived The foregoing warranty is exclusive of any other warranties express implied o...

Page 31: ...on systems with detailed explanation of system components Advanced configuration options with hands on deployment of actual systems will enhance student understanding Solar Stik New Equipment Training...

Page 32: ...Operator and Maintenance Manual for the 24VDC Li ESM 2000 April 2022 Solar Stik Inc 32 SUPPLEMENTAL INFORMATION Replacement Battery SDS...

Page 33: ...33 April 2022 Solar Stik Inc Operator and Maintenance Manual for the 24VDC Li ESM 2000...

Page 34: ...Operator and Maintenance Manual for the 24VDC Li ESM 2000 April 2022 Solar Stik Inc 34...

Page 35: ...35 April 2022 Solar Stik Inc Operator and Maintenance Manual for the 24VDC Li ESM 2000...

Page 36: ...Operator and Maintenance Manual for the 24VDC Li ESM 2000 April 2022 Solar Stik Inc 36...

Page 37: ...37 April 2022 Solar Stik Inc Operator and Maintenance Manual for the 24VDC Li ESM 2000...

Reviews: