20
S O L A N e v e r S t o p s I n n o v a t i n g
ups 325
3.
Use the table below to decide which combination of
settings you need; note which LEDs must be lit for this
combination. Then, press the button shown briefly
(about 1 second) and release to move to the next
combination of LEDs. If you hold the button in longer
than ten seconds, the SOLA 325 will save the setting
that is displayed. Continue pressing and releasing the
button until the proper LEDs are lit.
4.
Once the correct LEDs are lit, press and hold the button
for ten seconds to save your changes. If the SOLA 325 is
running on AC input power, the display will change back
to the percent of full load. The new values will take effect
after the display returns to normal mode.
Press this button
for 10
SECONDS to
save your
changes.
Press this button
BRIEFLY to
scroll through the
settings.
LEDs Lit
To Inverter
(Input AC is Low)
Boost
Nominal
Voltage
Buck
To Inverter
(Input AC is High)
1, 2, 3
(Default)
197
221
240
254
283
2, 3, 6
170
191
230
244
271
3, 4, 5
181
202
220
233
259
3, 4, 6
167
187
220
233
259
1, 2, 4
193
216
240
254
283
1, 2, 5
182
204
240
254
283
1, 2, 6
178
199
240
254
283
2, 3, 4
189
212
230
244
271
2, 3, 5
185
207
230
244
271
2, 3, 5, 6
175
196
230
244
271
Table 5: Voltage Settings for SOLA 325 Models (400, 750, and 1000 VA)