ups 325
Appendix A: Adjusting Voltage Settings
When the unit is not sounding an alarm, you can use the button shown below to change the
following:
• Nominal Voltage — The normal voltage the UPS is programmed to expect, and the nominal UPS
output voltage under line loss conditions.
• Buck — The input voltage at which the SOLA 325 decreases voltage before providing output
because the input voltage is too high.
• Boost — The input voltage at which the SOLA 325 increases voltage before providing output
because the input voltage is too low.
• Transfer to Inverter — The point at which the UPS switches to inverter (battery power), either
because AC input voltage is very low or because it is very high.
Note:
Make sure you want to change these values before you start the procedure below. Once
you press the button shown for 10 seconds, the values will change to the default values,
and any previous changes you have made will be lost. If you have questions, contact the
nearest Sola office, or call National Service and Repair Centre on: 1800 034 401 (except
Melbourne); 9768 3105 (Melbourne only).
Do not change voltage settings when unit is operating on
inverter. To change the values, follow these steps:
1.
Press the button shown until the LEDs on the front of the
SOLA 325 blink (approximately 10 seconds). After the
LEDs blink, three or four will stay lit, and the SOLA 325
beeps for one second.
2.
The LEDs that are lit show which voltage settings are selected. The LEDs are numbered in the
drawing below to help you identify them. Table 5 on page 18 shows the voltage settings for each
possible combination of LEDs.
For example, by default, LEDs 1, 2, and 3 will be lit (see
diagram). You will find this combination of LEDs in the first
row of Table 5. This row shows the following:
• With 197 volts input or lower, the SOLA 325 switches
to battery power.
• When input voltage drops to 221, the SOLA 325 begins
to increase the output voltage.
• 240 is the nominal or expected input voltage.
• When input voltage rises to 254, the SOLA 325 begins
to decrease the output voltage.
• With 283 volts input or higher, the SOLA 325 switches to battery power.
Press this
button for 10
seconds (until
all of the lights
blink).
1
2
3
4
5
6
1
2
3
4
5
6
LED Numbers
Default Setting