                                                       Physical Installation 

 

Inverter Components 

 

A.

 

LCD Touch Screen 

 

 

 

F. Comms/Paralleling Ports  

B.

 

ON/OFF Button 

 

 

 

G. AC Terminal Blocks 

C.

 

PV DC Disconnect Switch 

 

 

H. Wi-Fi Connection 

D.

 

Battery Terminals (+/-) 

 

 

I. MPPT Charge Controllers  

E.

 

Sensor Pinout  

 

 

 

 

Deciding Backup Circuits

 

A.

 

We recommend subpanels and require them if you have Arc-Fault / GFI breakers 

B.

 

Ensure you keep the inverter within its amperage limits  

 

ON-Grid = 50A Continuous (pass-through) 

 

OFF-Grid = 37.5A Continuous | 67A Peak (10s) | 104A Peak (100ms) 

C.

 

Verify each load circuit by measuring typical and max Amps with a clip-on Amp meter. Amps x 120V = Watts 

D.

 

Install a subpanel for backup loads if you have Arc-Fault / GFI breakers, NOT a multi-circuit transfer switch 

 

Summary of Contents for L12K-Tr

Page 1: ... VOLTAGE ON EACH PV INPUT CIRCUIT 21 WI FI INTERNET CONNECTION 22 REMOTE MONITORING SETUP 22 IP ADDRESS SETUP INSTRUCTIONS PC OR SMART PHONE 25 PROGRAMMING GUIDE 27 MAIN SCREENS TOUCHSCREEN 28 BASIC SETUP 29 SYSTEM ALARMS 29 BATTERY SETUP 30 GRID SETUP 32 LIMITER SENSOR AUTOMATIC SETUP 35 INSTALL TIPS 36 OFF GRID INSTALL TIPS 36 GRID TIE NO BATTERY INSTALL TIPS 36 BATTERIES 37 BATTERY CHARGING INF...

Page 2: ...WHETHER DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK Sol Ark cannot be responsible for system failure damages or injury resulting from improper installation of their products The information included in this manual is subject to change without notice This version is for OUTDOOR M...

Page 3: ...ons should install the Sol Ark L12K Tr inverter The system must have Ground connections and Neutral connections Ground MUST be bonded to Neutral ONLY ONCE in the circuit Solar PV PV are UNGROUNDED Note you may ground PV Racking Mounts but doing so directly to the Sol Ark will likely result in damage in the case of a direct lightning strike to the PV array DO NOT connect the grid to the Load Output...

Page 4: ... CT sensors x2 Sold Separately C Limiter Sensors if purchased 2 CT sensors x2 Sold Separately D Battery Temperature Sensor for voltage adjustment E Battery Cable Toroid x2 F CAT 5 cable for parallel communications G WIFI Dongle For software updates and remote monitoring use M4x10 screws to hold in H French Cleat For wall mounting the Sol Ark L12K Tr You must note any damage due to shipping with de...

Page 5: ...April 22nd 2022 5 Spec Sheet 5 ...

Page 6: ...IN Lbs 1 2 Nm Gen Breaker 10 6 IN Lbs 1 2 Nm Neutral Ground Busbars 10 6 IN Lbs 1 2 Nm Cover Screws 26 5 IN Lbs 3 NM Battery Connection 216 0 IN Lbs 24 5Nm 3 3 minimum clearance 3 Temperature Derating DC 90C 100C Shutdown 100C AC 75C 82C Shutdown 82C Do Not Use Impact Drivers to Tighten Any Fasteners on the Sol Ark ...

Page 7: ...00 23 AWG CAT 6 Extensions for Limiter Sensors must be twisted pair Shielded CAT6 Recommended DC Battery Input 0 12 2 0 AWG 12 20 4 0 AWG All AC Inputs Outputs Neutral Connections 0 100 6 AWG 2 0 AWG Max 4 0 AWG Max Small Limiter Sensor Large Limiter Sensor 15 875mm 5 8in 10 AWG Max PV Panel Inputs 0 100 12 AWG 100 300 10 AWG 25 4mm 1 0in 10mm 4 0 AWG Max 15 875mm 5 8in 4 AWG Max 100A 50mA 100A 50...

Page 8: ...ring Diagrams These Single Line Diagrams SLDs are everyday use case examples of Sol Ark inverters Sol Ark does not provide custom diagrams however you may contact support sol ark com for any questions about an existing SLD ...

Page 9: ...April 22nd 2022 9 Sol Ark L12K Tr x3 Standard Wiring Diagram 120 240V ...

Page 10: ...April 22nd 2022 10 This page is left blank on purpose ...

Page 11: ...April 22nd 2022 11 GUI Screens Main Menus Basic Setup ...

Page 12: ...April 22nd 2022 12 c Battery Setup Grid Setup ...

Page 13: ...ng Backup Circuits A We recommend subpanels and require them if you have Arc Fault GFI breakers B Ensure you keep the inverter within its amperage limits ON Grid 50A Continuous pass through OFF Grid 37 5A Continuous 67A Peak 10s 104A Peak 100ms C Verify each load circuit by measuring typical and max Amps with a clip on Amp meter Amps x 120V Watts D Install a subpanel for backup loads if you have A...

Page 14: ... DC over current protector or disconnect device between the battery and the inverter for safe operation and compliance Switching devices may not be necessary for some applications but over current protectors are still needed We recommend that you use 1 0 AWG wire size A Please choose a suitable battery cable with the correct connector that fits well into the battery terminals M10 B Use a suitable ...

Page 15: ...MES to any ground in the Home via 12AWG wire E IF using Y Connectors Running two strings in parallel totaling 34A self limiting F Connect the solar panel strings as indicated by the following diagram 12AWG Positive to Sol Ark Negative to Sol Ark Sol Ark 8K is a 48V system Do NOT wire the battery bank to any other nominal voltage When using 12V batteries do not exceed FOUR 4 batteries in series Whe...

Page 16: ...rator you will want to adjust the GEN charge value Multiply value by of Sol Arks for actual current value into batteries Increase Gen Sol Ark efficiency 1 Select Limited to Load 2 Select General Standard 3 Increase Grid frequency range 55 65H Suppose PV production 0W Disabled TOU Enabled Grid Gen Charge the batteries will be charged to full using the Grid or a Generator if available until the batt...

Page 17: ...ig C 1 2 Batt Temp Battery Temperature Sensor has no polarity and is needed for voltage correction when using lead acid batteries 3 4 CT1 5 6 CT2 7 8 CT3 Current transformers used for limited to home mode and peak shaving CN2 1 2 Gen Start Relay Two wire start for generators simple open or closed relay 7 8 RSD 12V power supply for RSD transmitters RS 485 RS 485 port for battery comms CAN CAN port ...

Page 18: ... 3 Wi Fi Antenna Dongle Remote monitoring and software updates require an internet connection through the Wi Fi dongle Limiter Sensors CT Sensors Diagram Below Install sensors on incoming electrical service wires on L1 and L2 Limited to Home Mode meter zero and Peak Shaving Modes require CT sensors CT winding default ratio is 2000 1 however this ratio is programmable To ensure the sensors will fit...

Page 19: ...lease do not misconnect input and output connectors A Turn OFF the AC breaker or disconnector BEFORE making a grid load or gen connection B Remove insulation sleeve 10mm length unscrew the bolts insert the wires according to polarities indicated on the terminal block and tighten the terminal screws Make sure the connection is complete C Insert AC output wires according to the polarities indicated ...

Page 20: ...April 22nd 2022 20 Meter Connection ...

Page 21: ...r B Turn PV disconnect switch to the ON position C Press the ON OFF Button on the front and the blue light should turn on Indicator LED s DC A Green DC Solar Panels are producing B Off Solar Panels are not producing AC A Green Grid or Gen or AC Coupled is Connected B Off grid is not Connected Normal A Green Sol Ark L12K Tr is working properly B Off Sol Ark L12K Tr is not working properly Alarm A R...

Page 22: ... of the dongle S N C Password 12345678 D Follow the instructions in the upcoming pages Download PV Pro App You can access PowerView on a computer with the following link http www mysol ark com iPhone Will only show up as PV Pro https apps apple com lk app powe rview pro id1247121391 Android https play google com store apps details id com elinter app powervie w hl en_US gl US Attention Installers I...

Page 23: ... Sign In Add a Plant After filling the form click Create Account Scan the QR code on the dongle while plugged in On Plant Type ALWAYS select Energy Storage DC coupling Make sure to pick a unique plant name I E Last Name First four of Address ...

Page 24: ...Fi network that will be providing the internet connection to the system Do NOT select the dongle s Wi Fi network If Location Services are not enabled it will be requested If Wi Fi paired with 10 10 10 1 select Done The app will buffer for a few seconds It takes about 60sec for the lights to turn on after setup Red LED Connected to Sol Ark and has power Green LED Connected to Internet and Server Fl...

Page 25: ... use the app and or www mysol ark com Connect to the Dongle Network A Settings Wi Fi Select the Network with EAP The last 5 digits of your SN number Select your plant Password 12345678 Disclaimer The Wi Fi dongle does not have internet You still need to be connected to the dongle for this process System info and programming Graphed data Alarms This screen is the real time view ...

Page 26: ...NOT SELECT DONGLE NETWORK D Select Connect Save Your Information Disclaimer Connecting the dongle via the IP address only connects the dongle to the internet YOU MUST STILL CREATE AN ACCOUNT VIA THE POWER VIEW APP If Successful you should see a Red and Green light on the Dongle showing a successful connection Red LED Connected to Sol Ark and has power Green LED Connected to Internet and Server Fla...

Page 27: ...pacity Max A Charge Max A Discharge TEMPCO Start V Start Gen Grid Charge A Float V Day Hour Minute Second Use Batt V Charged Use Batt Charged No Battery BMS Lithium Batt Activate Battery Absorption V Equalization V Equalization Days Equalization Duration Shutdown V Low Batt V Restart V Batt Resistance Batt Empty V Use Gen Input as Smart Load Use Gen Input for AC Coupling Smart Load On Off V Smart ...

Page 28: ...Batt AC o PV Batt o AC Batt AC Temp Temperature of AC conversion electronics o Batt AC o PV AC Grid Column o If selling to the Grid Grid Watts negative o If buying from the Grid Grid Watts positive o HM power detected by the external current sensors on the entire home L1 L2 o LD power detected using internal sensors on AC grid in out breaker PV Graphical View A Displays power production over time ...

Page 29: ...efault value is always the Maximum output of the inverter Grid Peak Shaving Set the Sol Ark s threshold to begin contributing power to keep the power drawn from the grid below the threshold Can set your generator on Grid Breaker for this as well CT Ratio Set the CT ratio the Default value is 2000 1 DO NOT change this value unless you speak with support the use of 3rd party CT sensors requires our ...

Page 30: ... for the batteries connected to the system Absorption V Set value suitable for the batteries connected to the system Absorption will stop at 2 of the capacity of the battery bank and drop to float Ex 400Ah battery would be 8A Equalization V Set value appropriate for the batteries in use Days the period between equalization cycles Hours period taken to equalize batteries Note if Hours 0 system will...

Page 31: ...ceiving power Using Gen load for a water heater we recommend that only one leg 120V be connected to the bottom element This significantly reduces the power consumption of the water heater while retaining core functionality it will heat water only slower Solar Watts is for on Grid A The system waits to turn on smart load until enough PV power is produced when on grid AC Coupling Settings For AC Cou...

Page 32: ...y only at each time Batt The battery voltage or at which the system will limit selling to the Grid or Home from the battery The system will drain the battery until reaching that percent voltage Charge Enables grid gen charging up to the voltage or percentage specified on the line during a selected period PV will always charge 100 If using a generator select the charge box for the times that may ne...

Page 33: ... Setup Limiter Limited to Home A Pushes power to the whole Home without selling back any excess to the grid no net metering agreement required B This mode requires the use of the limiter sensors C Power source priority is the same as Grid Sell Back Grid Sell Main Menu System Settings Grid Setup Limiter Grid Sell A This mode allows Sol Ark L12K Tr to sell back any excess power produced by the solar...

Page 34: ...abled in Sell Control tab Puerto Rico Grid Compliance Settings Kauai Grid Compliance Settings HECO Grid Compliance Settings for O ahu Maui Hawai i HECO Grid Compliance Settings for Lana I and Moloka i PowFac Power Factor is programmable from 0 8 1 0 ...

Page 35: ...tly configured see Fig D if they are not correct repeat the learn function In Limited To Home Mode HM values will be close to zero HM values should never be negative If negative the Limiter Sensors are not installed properly Possible Limiter Sensor issues Sensors are facing wrong direction Sensors are on the wrong wire s Sensors are not fully closed on wire s Sensor Polarity is wrong White BLK Fig...

Page 36: ...are about 95 full this percentage is not programmable before turning the generator off ii When using the Sol Ark to control a generator an exercise function will turn on the generator once a week on Monday mornings at 8 AM by default F We recommend changing the Grid Reconnect Time under the Sell control tab of the grid setup menu to 30 seconds otherwise the Sol Ark will not charge from the generat...

Page 37: ... stage charges the battery fully the MPPT reduces the battery voltage to the float voltage setpoint If batts have 100 charge there can be no more chemical reactions and all the charging current turns into heat and gassing The float stage provides a meager rate of maintenance charging while reducing the heating and gassing of a fully charged battery The purpose of float is to protect the battery fr...

Page 38: ... Cell BMS Lithium Batt Not Selected Float V 55 6V Absorption V 56V Equalization V 56V Equalization Days 30 Equalization Duration 2 Hours tops off battery Recommended Shutdown V Percentage 50 2V 20 Recommended Low Batt V Percentage 50 6V 30 Recommended Restart V Percentage 51 0V 40 Battery Resistance 24mOhms battery Count Battery Charge Efficiency 99 Battery Empty Voltage 46V Time Watts SOC GridCha...

Page 39: ... own risk the warranty will not cover any damage caused by the improper use of the communications protocols Read Only Modbus Map available upon request at support sol ark com Incorporating 3rd Party ModBus Devices If your device utilizes BMS Lithium Batt 00 you need to set the inverter Modbus SN to 01 The default ModBus SN is 00 Find our full list of currently supported battery communications www ...

Page 40: ...e system alarms menu to identify the alarm Grid HM value is negative when it should be positive only applies in limited home mode Limiter Sensors are backward L1 L2 sensors are swapped or incorrectly wired L1 L2 sensors Try Auto Learn AC Overload Fault or Bus Unbalance Fault Check Transfer Switch Subpanel wiring Check for large loads that consume more than the inverter rating EX AC units over 3 to...

Page 41: ... calibrate the battery Generator setup is reading 0Hz Select General Standard instead of UL1741 Then widen the frequency range to 55Hz 65Hz Color Touchscreen is Frozen Press and hold the escape button for 7 10 seconds Troubleshooting Phasing Issues If the Sol Ark screen shows Grid Phase Wrong there is a phasing issue with your wiring and it may cause overload faults F18 F26 F34 even with the Load ...

Page 42: ...e leg L1 or L2 Vs the other leg or DC loads on the AC output when off grid Grounded PV wire can cause F20 F23 or F26 F29 Parallel_CANBus_Fault Usually a communication error for parallel systems check cables and MODBUS addresses F30 AC_MainContactor_Fault Contact Sol Ark com F31 Soft_Start_Failed Soft Start of large motor failed F34 AC Overload Fault AC Overload or load shorted Reduce heavy loads F...

Page 43: ...ole home power Y N F You have verified the limit sensors are correctly installed An auto learn function corrects any mistakes in CT limiter wiring provided you have batteries and in 120 240V Program in the correct Grid mode the customer will use 6 Did you program the correct Ah for the battery bank and max Amps charge discharge Y N 7 Did you program the correct battery charge voltages for your bat...

Page 44: ...S LIMITED WARRANTY IS THE EXCLUSIVE WARRANTY APPLICABLE TO SOL ARK PORTABLE SOLAR LLC PRODUCTS SOL ARK EXPRESSLY DISCLAIMS ANY OTHER EXPRESS OR IMPLIED WARRANTIES OF ITS PRODUCTS SOL ARK ALSO EXPRESSLY LIMITS ITS LIABILITY IN THE EVENT OF A PRODUCT DEFECT TO REPAIR OR REPLACEMENT IN ACCORDANCE WITH THE TERMS OF THIS LIMITED WARRANTY AND EXCLUDES ALL LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGE...

Reviews: