FG-200 HSE/FF Modbus - Qui ck Sta rtup Gui de
20
© Softing Industrial Automation GmbH
3.1.7 FF-H1 interface connection
Connect the H1 links to the terminal blocks of the H1 interfaces. Since the FG-200 does not
provide power to the H1 links, a power conditioner and a bus termination is required for
each H1 link. When using a redundant set of two devices, make sure to connect each H1
link to the same channel (CH 1 .. CH 4) on both FG-200s.
The FG-200 provides four Foundation Fieldbus H1 interfaces. These interfaces are named
CH1 to CH4 and are used to connect an FF-H1 bus to the FG-200.
FF H1 bus line channel 1
CH1
Pin
Signal
Description
7
+
Fi
8
S
Fieldbus shield
9
-
Fieldbus -
FF H1 bus line channel 2
CH2
Pin
Signal
Description
10
+
Fi
11
S
Fieldbus shield
12
-
Fieldbus -