Chapter 7 - Special conditions for safe use
© Softing Industrial Automation GmbH
19
7.3
Installation
The commModule MBP must be installed by qualified personnel only.
Ensure that the equipment installed complies with the types of protection relevant to the applicable zones
and categories and with local requirements for electrical equipment used in explosive areas associated
with explosive atmosphere.
The following points must be considered when deploying the unit:
The device must be used as intended by the manufacturer
Do not use this device when damaged.
Do not use this device when certification information is illegible.
Observe storage conditions.
Clean installation space.
Installation done according to instructions.
Do not put stress on the system by bending or torsion.
Connecting improper or non Ex certified equipment invalidates Ex approval of device.
Electrical parameters of connected devices must match the values described in the technical section.
Local requirements for electrical equipment for use with hazardous location associated with explosive
atmosphere shall be considered for installation.
This device has no housing and must be protected in a cabinet against splash water, dirt, moisture
mechanical force exceeding pollution degree 1.
7.4
Isolation and creepage distances
Following creepage and clearance distances and separations must be observed when integrating
commModule MBP.
Pin
Signal
Creepage and clearance
Pin 1 to 36
GPIO, GND, DBG
No requirement on creepage distances between these
signals.
Clearance and creepage distance to all other signals
with level of protection 10V according to table 5 in
IEC 60079-0
Pin 37
FB_P_NF
Clearance and creepage distance to all other signals
except FIELDBUS_N
with level of protection 30V according to table 5 in
IEC 60079-0
Pin 38, 39
FIELDBUS_P, FIELDBUS_N
No requirement on creepage distances between these
signals.
Clearance and creepage distance to all other signals
Summary of Contents for Data Flow commModule MBP
Page 1: ...Softing Industrial Automation GmbH commModule MBP Hardware Manual Version EN 022018 1 00...
Page 23: ...Chapter 8 CE Compliance Softing Industrial Automation GmbH 23...
Page 24: ...commModule MBP Hardware Manual 24 Softing Industrial Automation GmbH...
Page 25: ...Chapter 8 CE Compliance Softing Industrial Automation GmbH 25...
Page 26: ...commModule MBP Hardware Manual 26 Softing Industrial Automation GmbH...
Page 28: ...commModule MBP Hardware Manual 28 Softing Industrial Automation GmbH...
Page 29: ...Chapter 8 CE Compliance Softing Industrial Automation GmbH 29...
Page 30: ...commModule MBP Hardware Manual 30 Softing Industrial Automation GmbH...
Page 31: ...Chapter 8 CE Compliance Softing Industrial Automation GmbH 31...
Page 32: ...commModule MBP Hardware Manual 32 Softing Industrial Automation GmbH...
Page 33: ...Chapter 8 CE Compliance Softing Industrial Automation GmbH 33...
Page 34: ...commModule MBP Hardware Manual 34 Softing Industrial Automation GmbH...
Page 35: ...Chapter 8 CE Compliance Softing Industrial Automation GmbH 35 8 3 Declaration of Conformity...