SUNSYS PCS2 Power Conversion System and Storage from 33 to 200 kVA - Ref.: IOMSUNPCXX04-EN 01
BATTERY TYPE
Set the type of battery connected to the SUNSYS PCS
2
(Generic, Lithium, Lead-acid, etc.).
Depending on the type of battery, after commissioning, some specific items will be shown in the Battery Setting Menu
to guarantee the correct SUNSYS PCS
2
set up.
COUNTRY/GRID CODE SETTING
Set the proper country/grid code according to local regulation.
Grid code compatibility is always being upgraded, please contact SOCOMEC for grid code compatibility (subject to
change without notice).
NOTE: Once the country/grid code has been set the SUNSYS PCS
2
will be automatically config-
ured in compliance with the local standards.
OPTIMISATION MODE SETTING
Not present if Generic Battery is selected.
Set the battery mode of use. It is possible to choose between:
- PERFORMANCE: maximises battery performance (full SOC operating range);
- LIFE: maximises battery life (reduced SOC operating range).
CONTROL MODE SETTING
Set the SUNSYS PCS
2
control mode. It is possible to choose between:
- local (using the control panel);
- external EMS (Energy Manager System);