7. 1.9. Test mode
this mode enables maintenance codes to be displayed in the form of pages marked with a number
For each maintenance page the following information appears:
– on the bottom line, the message "StS Code n° xxx" where xxx corresponds to the page n°,
– on the top two lines, 4 hexadecimal digits corresponding to the maintenance code.
the page is changed using the keys
and
pressing on the
key launches a complete mimic panel test by:
– Switching on all leds,
– displaying all lCd segments,
– operating the buzzer.
This mode does not interrupt the normal operation of STATYS
7. 1.10. Programming mode
This mode is accessed by entering a password:
If the "user" password is inputted, only "user" parameters may be configured.
If the "system" password is inputted, all parameters could be modified.
Choice of preferred source (user access)
display: pS
default value: S1
possible choice: S1 or S2
Modbus link configuration (user access)
display: mod bus
Slave number
display: sla nb
default value: 1
possible choice: 1 to 255
link speed
display: bds
default value: 9600
possible choice: 2400, 4800, 9600 or 19200
link parity
display: par
default value: no
possible choice: odd, eve (even) or no