LINE SETTINGS
|
I-30@4 ID:FOC1D2
WAY
+/DIRECT
V LINE
V3
CT
0600
DETECT
OK
If a load is configured as three-phase or three-phase+neutral, for example, you would have to configure multiple current
sensors (e.g. 3 current sensors for one three-phase load):
LOAD
|
I-30@4 ID:FOC1D2
…
CT SETTINGS
CT2
I02
CT SETTINGS
CT3
I03
CT SETTINGS
…
When you have finished configuring the entire load (L1) (type of load, name, nominal current, current sensors), scroll right
from the “LOAD” line to configure loads 2 and 3 (L2, L3):
LOAD
|
I-30@4 ID:FOC1D2
LOAD
L1
NAME
LOAD 1
TYPE
3P+N_3CT
NOMINAL I (A)
00020
CT1
I01
…
For example, a DIRIS Digiware I-30 with 3 current inputs is best for measuring:
•
1 three-phase load (1 three-phase load L1 using the current inputs I01, I02, I03)
•
3 single-phase loads (1 L1 single-phase load with a current sensor connected to the I01 current input, 1 L2 single-
phase load with a current sensor connected to the I02 current input, 1 L3 single-phase load with a current sensor
connected to the I03 current input).
Numerous other load combinations are possible.
When all the circuits/loads are configured (maximum 3 on one DIRIS Digiware I-30), apply your settings by selecting
"SEND SETTINGS" and click "OK".
LOAD
|
I-30@4 ID:FOC1D2
…
CT3
I03
CT SETTINGS
CT4
I01
CT SETTINGS
SEND SETTINGS