UPS/NTA GB/DELMP_EXPC1C3C6_B
11
2.3 MIMIC CONTROL PANEL
ESC
ENTER
The control panel is composed of:
-
1 mimic panel
-
1 eight-line LCD display (with up to 40
characters)
-
1 four-key intuitive user interface:
1 validation key (ENTER)
1 ESC key
2 scrolling keys (UP/DOWN)
-
1 luminous status bar
2.3.1 Contrast
setting
The display contrast is set by the factory. It is automatically adjusted according to the
temperature of the technical plant. No setting is required.
2.3.2 Luminous status bar
The status bar provides immediate indication about the operating conditions of the system.
The following information can be displayed.
Green bar:
- the load is supplied via the inverter
- the load is supplied via the bypass path if in Eco-mode
Yellow bar:
the load is supplied via the automatic / maintenance bypass
Yellow blinking bar:
maintenance mode or maintenance alarm active
Red bar:
the load is not supplied
Red blinking bar:
the imminent shutdown alarm is given