14
EN
COUNTIS E21/E22 - 545875B - SOCOMEC
8.1.1. Detailed view of menu "SETUP 1"
In menu "SETUP 1" you can select the connection type.
Press SET for 3 seconds using a screwdriver to put the device into programming mode.
The default connection (Wir) is: 3.4.3 = 3 phases, 4 wires, 3 currents. Other possible connections: 3.3.3 = 3 phases, 3 wires, 3
currents or 3.3.2 = 3 phases, 3 wires, 2 currents
SET
N
A
A-V
A
A-V
A
A-V
L1
L2
L3
L1
L2
L3
N
3 x 80A
230/400 VAC 50/60 Hz
1 2 3
4 5
6 7
NC - +
- +
COM RS485
MODBUS
T1/2
>3s
Connection diagram
x1
x1
3.4.3 = 3 phases, 4 wires, 3 currents
3.3.3 = 3 phases, 3 wires, 3 currents
3.3.2 = 3 phases, 3 wires, 2 currents
>3s Exit menu
x1 Confirm
Y
=Save setting and exit
N
=Exit without saving
C
=Continue without saving
8.1.2. View all of the menu "SETUP 2"
In the SETUP 2 menu, press "
" for 3 seconds to put the device into programming mode.
You can go to the different screens by pressing "
":
>3s
Reset partial energy to zero:
Ea+ partial (kWh) Tariff T1, T2
Ea+ partial (kWh)
Ea- partial (kWh) Tariff T1, T2
Ea- partial (kWh)
Eap partial (kVAh)
Er+ partial (kVarh)
Er- partial (kVarh)
Return to the first menu screen, "SETUP 2"