Socomec Innovative Power Solutions 

11 Ubi Road 1, #02-01 Meiban Industrial Building   

Singapore 408723 

http://www.socomec.com

 

2

 

 

3. Description 

 

 

Content 

Parameters 

Standard:  

 

 

IEC62052-11

IEC62053-21 

Rated Voltage:  

 

 

230V 

Rated Current: 

5(100) A 

Impulse Constant:   

1000imp/kWh 

Frequency: 

50-60Hz 

Accuracy Class: 

1.0 

LCD Display: 

LCD 5+1 = 99999.9kW 

Working Temperature: 

-20

65

 

Power Consumption: 

≤8VA

≤0.4W

 

Average Humidity: 

≤75%

 

Maximum Humidity: 

≤95%

 

Start Current: 

0.004Ib 

LED flash: 

Impluse indication, pulse width = 90 ms 

Materials:   

Case: ABS, PC, alloy material 

DIN Rail Clip: ABS resistance 

Summary of Contents for COUNTIS E13X

Page 1: ...distribution system for household and commercial 2 Features and Technical Parameters 2 1 Features It can read grid parameters analyze the energy quality and load condition in the certain time period D...

Page 2: ...ding Singapore 408723 http www socomec com 1 2 Modes for data display a Auto scrolling mode the time interval is 5s b Button mode by external button for data checking The material of the meter case AB...

Page 3: ...EC62053 21 Rated Voltage 230V Rated Current 5 100 A Impulse Constant 1000imp kWh Frequency 50 60Hz Accuracy Class 1 0 LCD Display LCD 5 1 99999 9kW Working Temperature 20 65 Power Consumption 8VA 0 4W...

Page 4: ...Ubi Road 1 02 01 Meiban Industrial Building Singapore 408723 http www socomec com 3 A Impulse indicator B Button for data checking C RS485 Port D L Out E L In F Neutral wire G LCD screen 4 LCD Display...

Page 5: ...omec Innovative Power Solutions 11 Ubi Road 1 02 01 Meiban Industrial Building Singapore 408723 http www socomec com 4 4 2 LCD Parameters Parameters Switch 5 Wiring Connection Note 23 24 25 is for A G...

Page 6: ...485 communication converter doesn t have G port no need to connect For Neutral wire you can connect one N port and connect both 6 Dimensions Height 95 3 mm Width 18 2 mm Depth 72 mm Weight 0 1 kg N W...

Page 7: ...http www socomec com 6 Fig 1 Fig 2 7 3 Install the meter onto the DIN Rail then push the DIN Rail Clip of the meter to fix the meter See details in below Fig 3 and Fig 4 Fig 3 Fig 4 7 4 Do the connect...

Page 8: ...Building Singapore 408723 http www socomec com 7 8 Communication 8 1 This meter supports RS485 Protocol is Modbus RTU mode The default parameters meter ID 1 baudrate 9600bps data bit 8 Parity Even Sto...

Reviews: