4
EN
COUNTIS E03/E04 - 545865A - SOCOMEC
2. HAZARDS AND WARNINGS
The term "device" used in the paragraphs below refers to the COUNTIS E03 / E04.
The assembly, use, servicing and maintenance of this equipment must only be carried out by trained, qualified
professionals.
SOCOMEC shall not be held responsible for failure to comply with the instructions in this manual.
2.1. Risk of electrocution, burns or explosion
•
Only duly authorised and qualified personnel may work or install/uninstall the device.
•
The instructions are valid together with the specific instructions for the device.
•
The device is designed only for its intended purpose as set out in the instructions.
•
Only accessories authorised or recommended by SOCOMEC may be used in association with the device.
•
Before proceeding with installation, maintenance, cleaning, disassembly, connection, or maintenance work,
the device and system must be cut off from the mains to avoid electrocution and damaging the system and
device.
•
This device is not designed to be repaired by the user.
•
For any questions related to the disposal of the device, please contact SOCOMEC.
Failure to comply with the instructions of the device and this safety information can cause bodily injury,
electric shock, burns, death or damage to property.
2.2. Risk of damaging the unit
To ensure that the unit operates correctly, make sure that:
•
The unit is correctly installed.
•
There is a maximum voltage at the voltage input terminals of 276 VAC phase-neutral
•
The network frequency indicated on the device is observed: 50 or 60 Hz.
•
a maximum current 40 A at the current input terminal.
Failure to respect these precautions could cause damage to the unit.
2.3. Responsibility
•
Assembly, connection and use must be carried out in accordance with the installation standards currently in
force.
•
The unit must be installed in accordance with the rules given in this manual.
•
Failure to observe the rules for installing this unit may compromise the device's intrinsic protection.
•
The unit must be positioned within an installation which complies with the standards currently in force.
•
Any cable which needs to be replaced may only be replaced with a cable having the correct rating.