socomec ATyS Quick Start Download Page 1

AT

y

S

Transfer Switch  

UL 1008: Optional Standby Power

quick start

600a, 800a, 1200a

Printing informations:

 1 color Black. White paper 90g/m

2

Printing size: 420x297. Final size 210x297. This page visible first.

Non contractual document.

Subject to change without notice.

www.socomec.com

To download, brochures, catalogues and technical manuals:

www.socomec.com/operating-instructions

 Preliminary operations 

Check the following upon delivery and after removal of the 

packaging:

 Packaging and contents are in good condition.

 The product reference corresponds to the order.

 Contents should include:

Qty 1 x ATyS
Qty 1 x Emergency handle and fixing clip
Quick Start instruction sheet

 Warning 

 

Risk of electrocution, burns or injury to persons and / 

or damage to equipment.
This Quick Start is intended for personnel trained in the 

installation and commissioning of this product. For further 

details refer to the product instruction manual available on 

the SOCOMEC website.

n

  This product must always be installed and commissioned 

by qualified and approved personnel.

n

  Maintenance and servicing operations should be 

performed by trained and authorised personnel.

n

  Do not handle any control or power cables connected to 

the product when voltage may be, or may become present 

on the product, directly through the mains or indirectly 

through external circuits.

 Always use an appropriate voltage detection device to 

confirm the absence of voltage.

 Ensure that no metal objects are allowed to fall in the 

cabinet (risk of electrical arcing).

Failure to observe good enginering practises as well as to 

follow these safety instructions may expose the user and 

others to serious injury or death.

 

Risk of damaging the device

 In case the product is dropped or damaged in any way it 

is recommended to replace the complete product.

 Accessories 

 Bridging bars and connection kits.

 Terminal  screens.

Terminal lugs.

 Spares 

 Motorisation  module

For further details for spares and accessories, please refer 

to the instruction manual in chapter - 

"Spare parts and accessories"

STEP 1

 

Cabinet / Back Plate 

Installation 

STEP 3

 

COMMAND / 

CONTROL terminal 

connections

STEP 2

 

Connecting the 

POWER section 

STEP 4

 

Power SUPPLY 

terminal connections 

STEP 5

 

ChECk 

 

Installation and Commissioning

STEP 6A

 

Control by an external 

order (AUTO)

STEP 6C

 

Padlocking 

STEP 6B

 

Emergency Manual 

Operation

UL 1008

Whilst in manual mode, check the wiring 

and if ok power up the product.

LED “Power” Green: ON

LED Manuel/Defaut Red (Product not 

Available): ON

  

  

  

STEP 5

Check

Ensure that the emergency handle is 

not inserted in the product and turn 

the mode selector to the AUT position.

LED “Power” Green: ON

LED Manuel/Default: OFF

 

___________________________________________________________

STEP 6A

Motorised Operation

To enable control, close contact 312 with 317.
To force the product to 0 position/OFF bridge 

the contact 313 with 317.
For contactor logic bridge contact 316 with 317.
To operate: close the contact corresponding to 

the desired position.

 Imp. ≥60ms        

 maintened

order I

position I

order 0

position 0

order II

position II

Contactor logic

Impulse logic

STEP 6C

Padlocking Mode 

(in position O)

3x

Control / Command Terminals -

 Ensure that the product is in Manual Mode.

STEP 3B

STEP 4

Power Supply Terminal - 

Remove the Top cover to access and connect the terminal - Replace the cover before putting in service.

1

2

3

Connect the product with a cable of section of 24 to 16 AWG.

1

2

30

1302

2

312 313 314 315 316 317 63A64A 24 14 04 13

CONTROL

OUTPUTS

Class CC 

4A fuse

STEP 1A

Installation

Attention: Ensure that the product is installed on a flat rigid surface.

FRAME B6

FRAME B7

600 A

800 A

1200 A

3P

4P

3P

4P

3P

4P

Ref ATyS

97233060

97234060

97233080

97234080

97233120

97234120

Dim. code

1

2

3

4

5

6

 Spares: Motorisation module 

AUT

STEP 6B

Emergency Manual Operation 

AUT

Ref. Spare part motorisation

USED FOR ATyS REFERENCE

97095060

600A

3, 4 P

B6

97233060 / 97234060

97095080

800A

B7

97233080 / 97234080

97095120

1200A

97233120 / 97234120

NOTE: Nominal Aux. Supply Voltage : 208 – 277Vac

546814A

Recommended

Ok

Ok

Clip for 

storage of 

the 

emergency 

handle

STEP 3

STEP 4

90°

90°

II

I

0

Ø 0.15-0.31 in

Ø 4-8 mm

Reviews: