Preliminary operations

Check the following upon delivery and after removal 

of the packaging:

• Packaging and contents are in good condition.

• The product reference corresponds to the order.

• Contents should include:

 

Qty 1 x ATyS FT

 

Qty 1 x C66 Controller

 

Qty 1 x Harness

Warning

 Risk of electrocution, burns or injury to persons 

and / or damage to equipment.

This Quick Start is intended for personnel trained in 

the installation and commissioning of this product. 

For further details refer to the product instruction 

manual available on the SOCOMEC website.

•  This product must always be installed and 

commissioned by qualified and approved personnel.

• 

 Maintenance and servicing operations should be 

performed by trained and authorized personnel.

•  Do not handle any control or power cables connected 

to the product when voltage may be, or may become 

present on the product, directly through the mains or 

indirectly through external circuits.

•  Always use an appropriate voltage detection device 

to confirm the absence of voltage.

• 

 Ensure that no metal objects are allowed to fall in 

the cabinet (risk of electrical arcing).

Failure to observe good engineering practices  as well 

as to follow these safety instructions may expose the 

user and others to serious injury or death.

Risk of damaging the device.

 In case the product is dropped or damaged in any 

way it is recommended to replace the complete 

product. Installation standards must be respected.

Accessories

Accessories are not included and must be 

ordered seperatly

• 

Terminal shrouds (see step 6A).

• 

Additional aux contacts (ref. 96990021).

• 

Digiware I/O 10 (ref. 48290140).

• 

Transformer 480 - 240 VAC (SPARTAN SP350MQMJ).

• 

 Controller 24 VDC aux power supply

 

(6W minimum type SELV) mandatory with I/0 10 Modules.

• 

Power terminal lugs (see step 1D).

For further details refer to the product instruction 

manual under chapter “Spares and Accessories”.

Spares 

• 

ATyS C66 Controller (ref. 16000066).

• 

UL 1008 ATyS FT (ref. 960XXXXX).

• 

Connector kit (ref. 16090002).

• 

Controller Nema 3R gasket (ref. 16090001).

• 

Controller mounting screws (ref. 16090004).

• 

Controller mounting feet (ref. 16090005).

• 

Cable harness without transfomer (ref. 96964000).

• 

Cable harness with transfomer (ref. 96974000).

CORPORATE HQ CONTACT:  

SOCOMEC SAS,  

1-4 RUE DE WESTHOUSE,  

67235 BENFELD, FRANCE

0

: Without solid neutral

1

: With solid neutral

N° of poles

2

: 2P

3

: 3P

4

: 4P

9  6  X  X  X  XXX

For Use on a Flat Surface of a Types 

1, 3R, 12 and/or 12k enclosure.

Non contractual document. Subject to change without notice.

548695E

QUICK START GUIDE

EN

AT

y

S FT

100 A, 200 A, 260 A, 400 A

Installation and Commissioning

Reference configurator

Switch installation

Cabinet / Back 

Plate Installation

STEP 1

Connecting  

the cable harness

STEP 2

Controller 

interface

STEP 3

Operational limits

STEP 4

Manual operation

STEP 5

Accessories

STEP 6

1A

Rating

010

: 100 A

020

: 200 A

026

: 260 A

040

: 400 A

PE

Source 2

Load

Source 1

0

: spare switch for networks up to 480 VAC

8

: ATSE assembly for 480 V.a.c 3 wire network

A

: ATSE Assembly for networks up to 480 VAC

Mounting orientation

Summary of Contents for ATyS FT

Page 1: ...s recommended to replace the complete product Installation standards must be respected Accessories Accessories are not included and must be ordered seperatly Terminal shrouds see step 6A Additional aux contacts ref 96990021 Digiware I O 10 ref 48290140 Transformer 480 240 VAC SPARTAN SP350MQMJ Controller 24 VDC aux power supply 6W minimum type SELV mandatory with I 0 10 Modules Power terminal lugs...

Page 2: ... 10 47 266 30 1 25 31 80 3 85 98 70 1 38 35 20 508 16 406 12 305 2P N 3P 11 85 301 30 1 25 31 80 5 49 133 70 1 38 35 20 508 16 406 12 305 3P N 4P 13 24 336 30 1 25 31 80 6 60 168 70 1 38 35 20 508 16 406 12 305 260 400A 2P 11 67 296 30 1 55 39 30 5 128 60 1 97 50 48 1220 24 610 12 305 2P N 3P 13 63 346 30 1 55 39 30 7 178 60 1 97 50 48 1220 24 610 12 305 3P N 4P 15 60 396 30 1 55 39 30 8 97 228 60...

Page 3: ...831 Contact us 1 6 250 KCMIL 275 31 1 5 16 70 8 8 5mm 1 25 4 100 200 A CMC LA 300R 39542020 2 1 6 300 KCMIL 275 31 1 5 16 70 8 8 5mm 1 12 28 4 39543020 3 39544020 4 260 400 A CMC LA 630R 39542040 2 1 4 600 KCMIL 550 62 1 1 2 310 35 8mm 1 79 45 7 39543040 3 39544040 4 260 400 A Ilsco D3096 Contact us 1 4 600 KCMIL 600 67 8 1 2 310 35 8mm 1 79 45 7 Power cable connections For 100A use 1 0 AWG For 20...

Page 4: ...ers not delivered with the product Fix FASTON connectors according to the table in step 2C Max 2 FASTON per pole Wires must not be in contact with active voltage points such as unused FASTON connections and lugs In order to do so any unused or loose cables must be tensed then fixed on a non conductive part of the transfer switch use cable tie fixation points as shown in the images below 1 Pass wir...

Page 5: ...4 4 5 3 lb in Sensing source 2 SOURCE 2 L1 L2 L3 N Voltage sensing inputs source 2 voltage supply L1 L2 Inputs 71 IN1 SWITCH IN POS1 Do not connect to any external power supply AWG 20 14 0 5 2 5mm 72 IN2 SWITCH IN POS 2 73 IN3 DOOR OPEN 74 IN4 programmable input 4 75 IN5 programmable input 5 76 IN6 programmable input 6 70 Common point for inputs Aux power supply 81 82 negative terminal for aux sup...

Page 6: ...n the configuration will go as follow SMART WIZARD CONFIG For advanced configuration go to parameters menu Language Source config Time date Switch Application Product Name Communication In STEP 5 8 of the wizard config make sure the network detected matches your network In STEP 6 8 make sure the switch technology parameter is set to ATyS FT If a fault is shown on the controller correct the associa...

Page 7: ...he LCD screen that may show distortion below 32 F 0 C Inspection of power contacts WARNING More than one live circuit Disconnect all sources of supply before servicing and or before using the manual operation Clip to maintain cover upright Slide cover to access service handle hole For manual operation operate handle 4 up from S2 to S1 down from S1 to S2 FAST OPERATION Recommendation carry out one ...

Page 8: ...and push back V Place the transparent plastic piece to cover the auxiliary conacts and lock in place in order to protect from direct contacts Use the correct protection according to your auxiliary contact circuit and your load Switch has 2 pre installed auxilliary contacts the kit below is for 2 additional contacts with protection against direct contact Ref 96990021 a b PH2 screwdriver Tightening ...