ATyS C66
AUTO
LCD display
Source and
switch synoptic
Standard code for programming : 1000
Manual operation buttons
and indicator
Communication
indicator LED
Switch not in automatic mode
indicator LED
Automatic button and
LED indicator
Test button and indicator for
load tests / no load tests
Short press for lamp test /
Long press to reset faults
Power, Fault and alarm LED
Navigation buttons
Change dashboard / set screen
as favorite
3
Controller Interface
When powered for the first time the controller will prompt the user to configure using the wizard.
To access the wizard input code 1000 then the configuration will go as follow:
SMART WIZARD CONFIG:
For advanced configuration go to parameters menu.
Language
Source config
Time & date
Switch &
Application
Product Name
Communication
In STEP 5/8 of the wizard config make sure the network detected matches your network.
In STEP 6/8 make sure the “switch technology” parameter is set to “ATyS DT”.
If a fault is shown on the controller, correct the associated fault and clear by doing a long press (>3s) on the lamp test button.
Left side hinge door
Right side hinge door
Mounting the cable harness on the controller
2E
or
For details on the controller connectors refer to step 2D, after inserting the required connectors use the cable tie connection points shown below to
maintain the cables in place:
black cables
red cables
b
b
b
b
b
b
b
b
b
r
r
r
r
r
r
r