socomec ATyS DT Quick Start Manual Download Page 3

Screw Tightening torque 

PH1 / 0.2 Nm 1.77 lb.in

Clip the 

mounting feet in 

the designated 

slot

Screws not delivered with product

5.9

+/-0.4

150

+/-1

6.77 - 7 172 - 178

0.25

6,4

R 0.24

R 6,25

0.12

3

1.53 

±

0,01

39 

±

0,3

 

0.86

22,05 

0.05 

±

0,02

15,5 

±

0,5

135

°

0.07

2

0.31 

±0,004

±0,1

Mount the load terminal lugs on the 

switch terminals before mounting source 

2 terminal lugs.

Backplate mounting

Mounting & connecting controller

1C

Installing terminal lugs (optional accessory)

1D

Use terminal screws and washers supplied with the ATSE

Product 

Rating (A)

Designation

Ref. lugs

Quantity 

per  

reference

Openings 

per lug

Size / Section 

(AWG)

Pressure screw 

torque

Bolt torque

Y

min.

max.

lb.in

Nm

Size in lb.in

Nm

Size

in

mm

100A

Ilsco D0957

Contact us

1

14

1/0

50

5,65

8

70.8 8

5 mm

0.625

15,9

200A

Ilsco D2831

Contact us

 1

6

250 KCMIL

275

31,1

5/16 70.8 8

5 mm

1

25,4

100-200 A

CMC LA-300R

39542020

2

1

6

300 KCMIL

275

31,1

5/16 70.8 8

5 mm

1.12

28,4

39543020

3

39544020

4

260-400 A

CMC LA-630R

39542040

2

1

4

600 KCMIL

550

62,1

1/2

310

35

8 mm

1.79

45,7

39543040 

3

39544040

4

260-400 A

Ilsco D3096

Contact us

1

4

600 KCMIL

600

67,8

1/2

310

35

 

8 mm

1.79

45,7

 Power cable connections : For 100A use 1/0 AWG / For 200A use 250 KCMIL / For 260A use 300 Kcmil / For 400A use 600 Kcmil copper cables.

Mounting & connecting the cable harness

2A

PE

Insert the  4 door mounting 

screws in the designated slot and 

push back to clip in lock in place.

For use on a flat surface of 

Types 1, 3R, 12 and/ or 12K 

enclosure

1

2

Gasket for Type 3R/12

8.66

+/-0.4

220

+/-1

6.30

+/-0.4

160

+/-1

For details on the cable harness wiring diagram and integration see Cable harness Quickstart guide ref 551401.

Cable harness without transformer (ref. 

98964000

) delivered with 

98AX XXXX

 products.

Cable harness for connections with transformer (ref. 

98974000

) delivered with 

988X XXXX

 products.

Note: transformers not delivered with the product.

Door mounting

PE

Summary of Contents for ATyS DT

Page 1: ...standards must be respected Accessories Accessories are not included and must be ordered seperatly Terminal shrouds see step 6A Additional aux contacts ref 96990021 Digiware I O 10 ref 48290140 Transformer 480 240 VAC SPARTAN SP350MQMJ Controller 24 VDC aux power supply 6W minimum type SELV mandatory with I 0 10 Modules Power terminal lugs see step 1D For further details refer to the product instr...

Page 2: ...t view Side view Switch top view Controller dimensions 1B SWITCH DIMENSIONS MINIMUM ENCLOSURE SIZE A B L P H W D in mm in mm in mm in mm in mm in mm in mm 100 200A 3P 11 85 301 30 1 25 31 80 5 49 133 70 1 38 35 36 915 16 406 12 305 3P N 4P 13 24 336 30 1 25 31 80 6 60 168 70 1 38 35 36 915 16 406 12 305 260 400A 3P 13 63 346 30 1 55 39 30 7 178 60 1 97 50 60 1524 24 610 12 305 3P N 4P 15 60 396 30...

Page 3: ...4 100 200 A CMC LA 300R 39542020 2 1 6 300 KCMIL 275 31 1 5 16 70 8 8 5mm 1 12 28 4 39543020 3 39544020 4 260 400 A CMC LA 630R 39542040 2 1 4 600 KCMIL 550 62 1 1 2 310 35 8mm 1 79 45 7 39543040 3 39544040 4 260 400 A Ilsco D3096 Contact us 1 4 600 KCMIL 600 67 8 1 2 310 35 8mm 1 79 45 7 Power cable connections For 100A use 1 0 AWG For 200A use 250 KCMIL For 260A use 300 Kcmil For 400A use 600 Kc...

Page 4: ...e in step 2C Max 2 FASTON per pole Wires must not be in contact with active voltage points such as unused FASTON connections and lugs In order to do so any unused or loose cables must be tensed then fixed on a non conductive part of the transfer switch use cable tie fixation points as shown in the images below 1 Pass wiring harness in the integrated cable duct After all the faston cables have been...

Page 5: ...IN I3 I2 I1 CT neutral CT phase C CT phase B CT phase A CT input 1A or 5A Serial connection RS485 Connection RS485 negative terminal of RS485 bus positive terminal of RS485 bus NC Ground RS485 bus insulated LiYCY sheilded twisted pair 30 14 AWG 0 14 to 1 5 mm 1 9 2 2 Lb in 0 22 0 25 Nm Digiware DIGIBUS Connection point for I O 10 optional accessories must use 24 VDC input RJ 45 digiware cable For ...

Page 6: ...e configuration will go as follow SMART WIZARD CONFIG For advanced configuration go to parameters menu Language Source config Time date Switch Application Product Name Communication In STEP 5 8 of the wizard config make sure the network detected matches your network In STEP 6 8 make sure the switch technology parameter is set to ATyS DT If a fault is shown on the controller correct the associated ...

Page 7: ...and the bottom switch handle to the bottom position Interlocking mechanism The mechanical interlock ensures that S1 and S2 are mutually exclusive and inhibits one switch from being closed unless the other switch is open Warning when manually switching always place one of the two handles in the OPEN position BEFORE switching the second handle 4 1 2 3 OPERATING VOLTAGE 50 60 10 HZ NETWORK MINIMUM CO...

Page 8: ... circuit and your load The ATyS DT switch has 4 pre installed auxiliary contacts two of which are reserved for use for harness This kit includes two additional contacts it is therefore recommended to order two sets of this kit for ATyS DT switches Ref 96990021 a b PH2 screwdriver Tightening torque 17 7 lb in 2 N m PH2 Make sure contact is correctly activated AUXILIARY CONTACT ELECTRICAL CHARACTERI...

Reviews: