COUNTIS E00

COUNTIS E02 - MID

Single-phase energy meter 

Direct - 40 A Pulse

COUNTIS 

E00

/

E02

INSTRUCTION MANUAL

EN

Summary of Contents for 4850 3058

Page 1: ...www socomec com en countis e0x COUNTIS E00 COUNTIS E02 MID Single phase energy meter Direct 40 A Pulse COUNTIS E00 E02 INSTRUCTION MANUAL EN ...

Page 2: ...AIL MOUNTING 9 6 CONNECTION 10 6 1 CONNECTING THE COUNTIS E00 02 10 6 2 CONNECTION TO THE ELECTRICAL NETWORK AND TO THE LOADS 10 7 MID COMPLIANCE 11 8 CONFIGURATION 12 8 1 ON SCREEN CONFIGURATION 12 8 1 1 VIEW ALL OF THE MENU SETUP 12 8 1 2 DETAILED VIEW OF MENU SETUP 13 9 USE 14 9 1 DETAILED VIEW OF THE MAIN MENU 15 9 1 1 DETAILED VIEW OF THE PARTIAL ENERGY METER 16 9 1 2 STARTING UP THE PARTIAL ...

Page 3: ...3 EN COUNTIS E00 E02 547975A SOCOMEC 1 DOCUMENTATION All documentation on the COUNTIS E00 E02 is available online at www socomec com en countis e0x ...

Page 4: ... designed to be repaired by the user For any questions related to the disposal of the device please contact SOCOMEC Failure to comply with the instructions of the device and this safety information can cause bodily injury electric shock burns death or damage to property 2 2 Risk of damaging the unit To ensure that the unit operates correctly make sure that The unit is correctly installed There is ...

Page 5: ... of these instructions thoroughly before commissioning Check the following points as soon as you receive the package containing the unit The packaging is in good condition The unit has not been damaged during transportation The device reference number conforms to your order The package includes 1 device 1 sealing kit for COUNTIS E02 1 Quick Start guide ...

Page 6: ...0 A They are equipped with a pulse output 4 2 Functions Measures and displays total and partial energy Electrical parameter measurements I V f Power power factor Pulse output MID version according to reference Description Reference COUNTIS E00 4850 3058 COUNTIS E02 Version MID 4850 3059 4 3 Front panels 1 Metrological LED 2 ENTER key 3 Information relating to MID certification 4 LCD display 5 Neut...

Page 7: ...sure 3 Unit of measure 4 Main zone in the event of Code XX metrological setting corrupt return to manufacturer 5 Value of the partial meter Flashing meter stopped 6 Imported or exported energy or power 7 Unit of measure 4 5 Dimensions Dual dimensions in mm 0 71 18 0 24 6 1 73 44 2 52 64 3 54 90 1 77 45 ...

Page 8: ...asure LCD display Neutral voltage V V Current I A Power factor PF Active power P kW Reactive power Q kvar Frequency f Hz Direction of current Logged data Total active and reactive energy Ea Er kWh kvarh Partial active and reactive energy Ea Er kWh kvarh Miscellaneous Partial meters P START STOP Status of the pulse output Active inactive ...

Page 9: ...to the safety instructions section 2 Hazards and warnings page 4 Keep away from electromagnetic interference generator systems Avoid vibrations with accelerations greater than 1 g for frequencies lower than 60 Hz 5 2 DIN rail mounting The COUNTIS E00 E02 can be mounted on a 35 mm DIN rail EN 60715TM35 They must be used inside electrical cabinets ...

Page 10: ...anded 0 14 mm2 2 5 mm2 0 27in 6 9mm PZ2 4 5 lb in 0 5 Nm max 6 2 Connection to the electrical network and to the loads The COUNTIS E00 E02 are intended for single phase networks with neutral Pulse output 4 5 Optocoupler pulse outputs Terminals 4 5 must be supplied with voltage between 5 and 27 VDC 27 mA max Network L Phase input L Phase output N Neutral connection L L N N 4 5 L L 40A N 230 VAC 50 ...

Page 11: ... with the MID directive for connection to networks 1P N see 6 2 Connection to the electrical network and to the loads page 10 Fitting terminal covers After connecting the device ensure that the terminal covers are fitted properly and secured by the plastic seals provided with the device MID Declaration of Conformity The MID Declaration of Conformity is available on the website www socomec com en c...

Page 12: ...owing stages Function Where Buttons Press Switch pages within a menu Every page within a menu Realtime Go to SETUP menu Menu page SETUP 3 sec Exit SETUP menu SAVE screen from the SETUP menu 3 sec Start stop the displayed partial meter Partial meter menu 3 sec Reset the displayed partial meter to zero Partial meter menu 3 sec 8 1 1 View all of the menu SETUP In the SETUP menu press for 3 seconds to...

Page 13: ...13 EN COUNTIS E00 E02 547975A SOCOMEC 8 1 2 Detailed view of menu SETUP 3s Reset energy Ea partial Er partial Back to first screen of SETUP menu ...

Page 14: ... energy Partial imported reactive energy 3 sec 3 sec Total imported active energy ______________ Total exported active energy ______________ Total imported reactive energy ______________ Active and reactive power ______________ Voltage ______________ Current ______________ Power factor ______________ Frequency ______________ Set up ______________ Firmware version ______________ Checksum of firmwar...

Page 15: ...in menu Total imported active energy description in chapter 9 1 1 Total exported active energy Total imported reactive energy description in chapter 9 1 1 Active power Reactive power Voltage Current Power factor Frequency Set up Firmware version Checksum of firmware ...

Page 16: ...OMEC 9 1 1 Detailed view of the partial energy meter Total imported active energy Total imported reactive energy 9 1 2 Starting up the partial energy meter 3 sec 3 sec 3 sec 9 1 3 Stopping the partial energy meter 3 sec 3 sec 3 sec x1 ...

Page 17: ...17 EN COUNTIS E00 E02 547975A SOCOMEC 9 1 4 Resetting the partial energy meter to zero 3 sec x1 3 sec ...

Page 18: ...f there are connection or malfunction errors 10 1 Malfunction When messages with the code xx are displayed the meter has malfunctioned and must be replaced 11 ASSISTANCE Causes Solutions Device not working Check the neutral and phase cable connections Error message Check the meter is working OK ...

Page 19: ... current Imin 0 25 A Transition current Itr 0 5 A Reference current Iref 5 A Permanent overload lmax 40 A Intermittent overload 30 Imax for 1 2 cycle OVERLOAD CAPACITY Continuous voltage Un 276 VAC Realtime voltage Un 1 s 300 VAC Continuous current Imax 40 A Realtime current Imax 30 Imax for 1 2 cycle VOLTAGE MEASUREMENTS Range of measurement 230 20 Power consumption 7 5 VA max Permanent overload ...

Page 20: ...0 999 9 V Realtime current 1 display 4 digit 00 00 99 99 A Power factor 1 display 4 digit 0 001 1 000 Frequency 1 display 4 digit 45 00 65 00 Hz SAVING Energy registers In the EEPROM memory ENVIRONMENTAL CONDITIONS Mechanical environment M1 Electromagnetic environment E2 Operating temperature range 25 C to 55 C Storage temperature 25 C to 75 C Humidity 80 Installation Internal box cabinet Vibratio...

Page 21: ... 13 GLOSSARY OF ABBREVIATIONS GB Metrological firmware version CS Checksum of metrological firmware Set up Set up menu RESALL Reset all partial energies SAVE Confirm selection Y Save and exit N Exit without saving C Continue without saving ...