background image

Non-contractual document. © 2016, Socomec SAS. All rights r

eserved.

545873A

CORPORATE HQ CONTACT:  

SOCOMEC SAS 

1-4 RUE DE WESTHOUSE 

67235 BENFELD, FRANCE

www.socomec.com

Summary of Contents for 4850 3047

Page 1: ...COUNTIS E17 COUNTIS E18 MID www socomec com en countis e1x Single phase energy meter Direct 80 A Ethernet COUNTIS E17 E18 INSTRUCTION MANUAL EN ...

Page 2: ...and to the loads 10 7 MID COMPLIANCE 11 8 COMMUNICATION 12 8 1 General information 12 8 2 Communication structure 12 8 3 Communication tables 12 9 CONFIGURATION 13 9 1 Onscreen configuration 13 9 1 1 View all of the menu SETUP 14 9 1 2 Detailed view of menu SETUP 15 9 1 3 Example setting the communication address 16 10 USE 17 10 1 Detailed view of the tariff menu Tar 18 10 2 Detailed view of the t...

Page 3: ...3 EN COUNTIS E17 E18 545873A SOCOMEC 1 DOCUMENTATION All documentation on the COUNTIS E17 E18 is available online at www socomec com en countis e1x ...

Page 4: ...igned to be repaired by the user For any questions related to the disposal of the device please contact SOCOMEC Failure to comply with the instructions of the device and this safety information can cause bodily injury electric shock burns death or damage to property 2 2 Risk of damaging the unit To ensure that the unit operates correctly make sure that The unit is correctly installed There is a ma...

Page 5: ...se instructions thoroughly before commissioning Check the following points as soon as you receive the package containing the unit The packaging is in good condition The unit has not been damaged during transportation The device reference number conforms to your order The package includes 1 device 1 ferrite core 1 sealing kit for COUNTIS E18 1 Quick Start guide ...

Page 6: ...n Ethernet communication bus 4 2 Functions Measures and displays total and partial energy Dual tariff management T1 T2 Electrical parameter measurements I U V f Power power factor TCP Modbus communication MID version according to reference Description Reference COUNTIS E17 4850 3047 COUNTIS E18 Version MID 4850 3048 4 3 Front panels L1 N A A V 1 LCD display 2 ENTER key 3 Neutral connection 4 Singl...

Page 7: ... menu 3 Active communication 4 Device malfunction Replace the device 5 Setup menu 6 Main zone 7 Unit of measure 8 Inductive value 9 Capacitive value 10 Partial meters Flashing partial meter has stopped 11 Tariff display 4 5 Dimensions Dimensions in mm 1 42 36 0 24 6 1 73 44 2 52 64 3 54 90 1 77 45 1 42 36 0 24 6 1 73 44 2 52 64 3 54 90 1 77 45 ...

Page 8: ...reactive inductive and capacitive energy Er kvarh Total active and reactive energy for each tariff T1 T2 Ea Er kWh kvarh Total apparent energy for each tariff T1 T2 Eap kVAh Total reactive inductive and capacitive energy for each tariff T1 T2 Er kvarh Active partial energy for each tariff T1 T2 Ea kWh Partial active and reactive energy Ea Er kWh kvarh Partial apparent energy Eap kVAh Energy balanc...

Page 9: ...to the safety instructions section 2 Hazards and warnings page 4 Keep away from electromagnetic interference generator systems Avoid vibrations with accelerations greater than 1 g for frequencies lower than 60 Hz 5 2 DIN rail mounted The COUNTIS E17 E18 can be mounted on a 35 mm DIN rail EN 60715TM35 They must be used inside electrical cabinets ...

Page 10: ...e electrical network and to the loads The COUNTIS E17 E18 are intended for single phase networks with neutral Ethernet RJ45 The Ethernet cable must pass twice through the ferrite core positioned at least 5 cm away from the device Price list Tariff switch via communication Network L1 A V Phase input L A Phase output N Neutral connection L1 N A A V L L N 80A 230 VAC 50 60 Hz Ethernet ...

Page 11: ... see 6 2 Connection to the electrical network and to the loads page 10 Fitting terminal covers After connecting the device ensure that the terminal covers are fitted properly and secured by the plastic seals provided with the device Communication The information provided via the TCP Modbus COM is transmitted for information only and has no legal value MID Declaration of Conformity The MID Declarat...

Page 12: ...nce with a master slave structure Communication is via TCP Transmission Control Protocol through the Ethernet communication port The default IP address is IP address 192 168 0 4 Subnet Mask 255 255 255 000 Gateway 192 168 0 1 Modbus address 5 A web server lets you access the measurement data The broadcast communication is available for the log that stores the tariff 8 3 Communication tables The co...

Page 13: ...mode is described in the following stages Function Where Buttons Press Switch menus Every page except SETUP menu Double speed x2 0 5 sec Switch pages within a menu Every page within a menu Realtime Go to SETUP menu Menu page SETUP 3 sec Change a value digit SETUP pages realtime Confirm a value digit SETUP pages Double speed x2 0 5 sec Exit SETUP menu SETUP Menu 3 sec Start stop the displayed parti...

Page 14: ... to the different screens 3s IP address 1 IP address 2 IP address 3 IP address 4 Netmask 1 Netmask 2 Netmask 3 Netmask 4 Gateway 1 Gateway 2 Gateway 3 Gateway 4 Reset partial energy to zero Ea partial kWh Tariff T1 T2 Ea partial kWh Ea partial kWh Tariff T1 T2 Ea partial kWh Eap partial kVAh Er partial kVarh Er partial kVarh Back to first screen of SETUP menu ...

Page 15: ...ddress 3 000 001 254 255 IP address 4 000 001 004 254 255 Netmask 1 000 001 254 255 Netmask 2 000 001 254 255 Netmask 3 000 001 254 255 Netmask 4 000 001 254 255 Gateway 1 000 001 192 254 255 Gateway 2 000 001 168 254 255 Gateway 3 000 001 254 255 Gateway 4 000 001 254 255 Reset energy Ea partial Tariff T1 T2 Ea partial Ea partial Tariff T1 T2 Ea partial Eap partial Er partial Er partial Back to f...

Page 16: ...e 14 go to the IP address 1 screen Example changing the communication address to IP1 007 x2 0 5 sec x1 IP address 2 IP address 3 IP address 4 Netmask 1 Netmask 2 Netmask 3 Netmask 4 Gateway 1 Gateway 2 Gateway 3 Gateway 4 Partial Energies Reset 3 x1 x2 0 5 sec x2 x2 0 5 sec x5 x2 0 5 sec x5 XX default value ...

Page 17: ...__________ Tariff 2 Imported and exported active energy Total imported and exported inductive reactive energy Partial exported active energy by tariff Checksum of metrological firmware ______________ ______________ ______________ ______________ Tariff 2 Imported and exported reactive energy Total imported and export ed capacitive reactive energy Partial exported active energy Checksum of non metro...

Page 18: ...d active energy tariff 1 Exported active energy tariff 1 Imported reactive energy tariff 1 Exported reactive energy tariff 1 Imported active energy tariff 2 Exported active energy tariff 2 Imported reactive energy tariff 2 Exported reactive energy tariff 2 Back to first screen of Tar menu ...

Page 19: ...otal exported active energy Total apparent energy Total imported inductive reactive energy Total exported inductive reactive energy Total imported capacitive reactive energy Total exported capacitive reactive energy Total imported reactive energy Total exported reactive energy Back to first screen of tot menu ...

Page 20: ...artial active energy for tariff T2 Partial imported active energy Exported partial active energy for tariff T1 Exported partial active energy for tariff T2 Partial exported active energy Partial imported reactive energy Realtime active power Realtime reactive power Realtime voltage Realtime current Realtime power factor Frequency Back to first screen of P rt menu ...

Page 21: ...21 EN COUNTIS E17 E18 545873A SOCOMEC 10 3 1 Starting up the partial energy meter 3 3 10 3 2 Stopping the partial energy meter 3 3 10 3 3 Resetting the partial energy meter to zero 3 x1 3 ...

Page 22: ...EC 10 4 Detailed view of the menu info Metrological firmware version Non metrological firmware version Checksum of metrological firmware Checksum of non metrological firmware Installed communication port Back to first screen of info menu ...

Page 23: ... appears if there are connection or malfunction errors 11 1 Malfunction If you see this message the meter has malfunctioned and must be replaced 12 ASSISTANCE Causes Solutions Device not working Check the neutral and phase cable connections Error message Check the meter is working OK ...

Page 24: ...onsumption 0 5VA max per phase Startup current Ist 20mA Minimum current Imin 0 25A Transition current Itr 0 5A Reference current Iref 5A Permanent overload lmax 80A Intermittent overload 30 Imax for 1 2 cycle OVERLOAD CAPACITY DC voltage Un 276 VAC Realtime voltage Un 1 s 300 VAC DC current Imax 80 A Realtime current Imax 30 Imax for 1 2 cycle VOLTAGE MEASUREMENTS Range of measurement 230 240V 20 ...

Page 25: ...e reactive power 1 display 4 digit 00 00 99 99 kvar Realtime voltage 1 display 4 digit 000 0 999 9 V Realtime current 1 display 4 digit 00 00 99 99 A Power factor 1 display 4 digit 0 001 1 000 Frequency 1 display 4 digit 45 00 65 00 Hz COMMUNICATION Ethernet Full duplex Protocol Modbus TCP HTTP NTP DHCP Baudrate 10 100 Mbps Web server password Username admin password Admin Username user password u...

Page 26: ... W x H x D mm Modular width of 2 modules DIN 43880 36 x 90 x 64 Installation On DIN rail EN 60715 Connection capacity tightening torque See chapter 6 Connection page 10 Protection index Front IP51 casing IP20 Insulation class Class II EN 50470 1 Weight 215 g ...

Page 27: ...ical firmware tAr Tariff menu tot Total menu P rt Partial and realtime readings menu SEtuP Setup menu rES ALL Reset partial energy SAVE Confirm selection Y Save and exit N Exit without saving C Continue without saving EthSEF Default settings IP1 IP address 1 IP2 IP address 2 IP3 IP address 3 IP4 IP address 4 nET1 Netmask 1 nET2 Netmask 2 nET3 Netmask 3 nET4 Netmask 4 GAt1 Gateway 1 GAt2 Gateway 2 ...

Page 28: ...Non contractual document 2016 Socomec SAS All rights reserved 545873A CORPORATE HQ CONTACT SOCOMEC SAS 1 4 RUE DE WESTHOUSE 67235 BENFELD FRANCE www socomec com ...

Reviews: