SMS SenTRI Data And Installation Instructions Download Page 7

Requirements of cables

The

British Standard BS5839 Part 1 : 2002 Code of practice for

system design, installation, commissioning and maintenance

states the requirements for standard and fire resisting cables in
Clause 26.2 section d and e.
"d)

Standard fire resisting cables

should meet PH 30

classification when tested in accordance with EN50200 and
maintain circuit integrity if exposed to the following test:
- a sample of the cable is simultaneously exposed to flame at a
temperature of 830ºC- 0+40ºC and mechanical shock for 15min,
followed by simultaneous exposure to water spray and
mechanical shock for a further 15min.
e)

Enhanced fire resisting cables

should meet the PH120

classification when tested in accordance with EN 50200 and
maintain circuit integrity if exposed to the following test:
- a single sample of the cable is simultaneously exposed to flame
at a temperature of 930ºC - 0+40ºC and mechanical shock for a
period of 60min, followed by simultaneous exposure to water
spray and mechanical shock for a further 60min."

"

The cables listed in this manual are those that

have been tested for EMC compliance with the system
products.

Loop Cable usage

"

There is a maximum limit of 1Km loop cable

usage allowed per loop circuit. This maximum limit is the
sum of the cable used on main loop circuit, spurs off
main loop circuit, plus cable runs to all input / output
lines off loop powered interface units installed on the
loop.

There is a further maximum limit of 100m cable run
allowed per input/output line off loop powered interface
unit.

Mains Supply cable

The mains supply cable must be a standard fire resisting type
and should meet PH30 classification, such as any of the standard
and enhanced cables listed above.

Repeat indicator to Control panel cable

A maximum of 1Km cable distance is allowed between Control
Panel and Repeat indicator panel

¨

Belden No. 9842 EIA RS485 Applications, O/A
Beldfoil® Braid having two twisted pairs

Loop cable

A loop cable carries both data and power, therefore its selection
is important. Note the following:

¨

In countries where the European EMC directive is in
force, only

EMC Compliant

cables are to be used.

¨

The loop cable usage must not exceed

1Km

. This

includes the cable used on main loop and spur circuits.

¨

Single pair cable must be used. It is

NOT

permissible

to run mixed loops or outgoing and return pairs in a
multi core cable, due to inadequate separation and
possible electrical interference problems.

¨

Each core of the loop cable must be

1.5mm

2

cross

section area.

¨

The cable screen must be

capable

of being earthed at

each system device.

¨

Red

is the preferred cover sheath for fire applications.

¨

The specified loop circuit cables are

also suitable

for

wiring master alarm, auxiliary relay, input/output lines
and mains supply.

Enhanced cables

¨

Mineral insulated cable (MICC) to BS6207:Part 1

¨

Approved Enhanced cable:
Draka Firetuf Plus Enhanced

FTPLUS2EH1.5RD

Standard cables

Approved EMC cables for loop wiring

¨

Draka Firetuf EMC Standard 1.5mm

2

FTEMC2EH1.5RDR

¨

Draka Firetuf

FTZ2E1.5 FIRETUF OHLS *

fire resistant data cable

¨

Raydex CDT

FG950 *

¨

Cavicel SpA

FIRECEL SR 114H *

distributed by Cables Britain

¨

AEI Cables

FIRETEC

*

¨

BICC Pyrotenax

FLAMESIL FRC

*

¨

Datwyler

LIFELINE *

¨

Alcatel cable

PYROLON E *

distributed by Winstonlead

¨

Huber & Suhner

RADOX FR

*

¨

Pirelli

FP200 FLEX

*

¨

Pirelli

FP200 GOLD

*

"

The cables marked * utilise laminated

aluminium tape with a tinned drain wire for electrostatic
screening. Under certain environmental conditions

galvanic action

may take place between the aluminium

and the drain wire. This will severely

degrade EMC

performance

as the foil to drain wire

impedance will

increase

. Armoured variants of these can also be used

for wiring a loop circuit.

7

SenTRI ONE System

Summary of Contents for SenTRI

Page 1: ...4188 979_Issue 2_04 10 SentriONE installation Part of Document pack 2534 235_issue 2 Data and Installation Instructions SenTRI ONE panel based fire detection and alarm system 042bc 14 one...

Page 2: ...oop circuit 20 Master alarm circuits 21 Common Fault contacts 21 Fire Output contacts 22 Repeat indicator panel 22 External Evacuation input 23 Class Change input 23 RS232 Port 23 USB Port 23 Battery...

Page 3: ...arts 46 Control Panels 46 Printer 46 Repeat panels 46 T Breaker and Remote LED 46 Manual call points 46 Keyswitch interface 46 SenTRI Analogue Sensor Sounder and Strobe units 47 Beam sensor 47 Sounder...

Page 4: ...ion to prevent damage to the equipment or a warning to inform of dangerous conditions that may result in injury or death Abbreviations ac Alternating current AS Anti surge C Common CH Channel dc Direc...

Page 5: ...2002 The cables must be installed using cable manufacturers recommended fixing and accessories Fire sensor cover Each fire sensor may be supplied with a plastic dust cover The cover must be fitted to...

Page 6: ...ey mustnot run together for example either close to the Control Panel or in a service duct There should be as much physical separation as possible between the cables and the mechanical protection of t...

Page 7: ...le A maximum of 1Km cable distance is allowed between Control Panel and Repeat indicator panel Belden No 9842 EIA RS485 Applications O A Beldfoil Braid having two twisted pairs Loop cable A loop cable...

Page 8: ...on Load factor per device Maximum devices per loop SENTRI RPT Repeat panel loop powered 3 4 SENADV IP ST XX Low profile range Strobe Red 10 100 SENADV SN X low profile range SENADV IP SN X low profile...

Page 9: ...Interface 1 4 127 127 78299 01NM Tee breaker 0 5 127 The maximum devices per loop and load factor per device have been revised due to changes in product specification A maximum of up to 100 input chan...

Page 10: ...em Devices Manual Call Point T Breaker T End of Line Unit Magnetic door release Conventional Products off interface inputs Alarm sounder Conventional Fire Detector Manual Call Point Loop circuit T 4 I...

Page 11: ...loop fire control panel Up to 127 addressable devices can be connected to a loop circuit devices like sensors call point and interface units Two master alarm circuits RS485 Port to connect to repeat i...

Page 12: ...ately on occurrence of a Fault event The relay is normally energised Master alarm circuits and fuses 2 Master alarm circuits operating at 24 volt nominal 200 mA maximum per circuit MA1 Fuse FS2 250mA...

Page 13: ...cement or equivalent type battery as there is a risk of an explosion if incorrect battery is used Power supply Standard Designed to EN54 4 1997 Mains supply voltage and fuses 230V 50Hz protected by FS...

Page 14: ...and Log book 1 part supplied in a plastic bag fitted to the enclosure How to disassemble the panel to gain access to the Backbox a Open the two captive screws k on the Outer cover j using the allen ke...

Page 15: ...mount the backbox onto a flat wall using suitable fixings 15 SenTRI ONE System Floor level Master Alarms 2 Cable entry points 13 Top 2 Back 3 Panel fixing points top hole is a keyhole 1 7m Fault Relay...

Page 16: ...the upper part k of the module into the backbox and then secure the assembly by tightening the two captive screws l using the allen key Ensure the two PCB fixing screws m that provides earth bonding a...

Page 17: ...tests WITH THE CABLES CONNECTED to the panel and system device terminals Such a test may damage the electronics circuitry in loop devices and at the panel 17 SenTRI ONE System GLAND GLAND BOARD EARTH...

Page 18: ...ALARM DO NOT SWITCH OFF The fire alarm equipment s fused spur unit must be fed from a dedicated switch or protective device at the local mains supply distribution board Mains and battery supply connec...

Page 19: ...DISABLE COMM TOOL P11 RL1 RL2 RED RED RL3 RL4 VE 0V DRN PP10 RX TX 0VISO DRN ISOLATED RS232 NC C NO DRN COMMON FAULT PP4 DRN FIRE OUTPUT PP5 EXT EVAC PP8 VE 0V DRN CLASS CHANGE PP9 L1 0V DRN LOOP END...

Page 20: ...t cover more than the equivalent of one zone as defined in BS5839 Part 1 As every device has a loop isolator the application of more than 32 devices does not require any special consideration Ensure t...

Page 21: ...ered from an independent power supply where required 21 SenTRI ONE System MA1 FS2 250mA MA2 FS3 250mA MAIN CONTROL BOARD PANEL 10K Ohms End of line resistor fitted in the last alarm sounder Convention...

Page 22: ...NELS can be connected directly to the fire panel to its RS485 Port The furthest repeat indicator panel can be installed a maximum of 1Km cable distance away from the fire panel The factory default set...

Page 23: ...nfigurable modes of operation and baud rate which are set during the commissioning of the system The configurable modes include standard default printer universal or Ascom The ports can be used to con...

Page 24: ...ssembly open b Connect the batteries in the manner illustrated m ensuring one of the connection is left disconnected Then fit the batteries inside the enclosure as illustrated n c Fit the connector of...

Page 25: ...ter cover by hooking it over the top edge j of the backbox and then close the bottom of the outer cover k onto the backbox and secure the cover by the captive screws using the allen key All the remain...

Page 26: ...ly Belden No 9842 EIA RS485 Applications O A Beldfoil Braid 1Km maximum cable distance from the control panel to the last repeat indicator panel must have following characteristics Two twisted pairs 2...

Page 27: ...S4 BASE GASKET can be fitted to the base to prevent water damage from dripping water from the ceiling Base labels An optional label SEN BASE LABEL can be fitted to the base The label can be marked up...

Page 28: ...ssible to connect a conventional Manual Call Point non UK application only with a series resistor of value 470 Ohms coupled with an end of line 10Kohms resistor In this case the fire input is fully mo...

Page 29: ...base and rotate it again until it clicks and goes no further the lines on the base and SenTRI device will align To fit a dust cover Place the dust cover onto the tool inside the cradle Offer the cover...

Page 30: ...Cut a 140mm diameter hole in the ceiling tile If required use a Bi Metal Holesaw 140mm or 146mm from www shop4tools co uk Insert the semi flush shroud assembly into the hole in the ceiling tile Hold...

Page 31: ...0 to 70 C Operating temperature 0 to 50 C Relative Humidity Non condensing up to 95 Temperature 5 45 C Emission BS EN50081 1 1992 Part 1 Residential Commercial Light Industry Class B limits Immunity B...

Page 32: ...junction box c Secure the angle bracket assembly onto the junction box using the gasket and angle bracket fixings d The applicable sensor head may now be fitted to the base assembly by twist and lock...

Page 33: ...ues with measurement taken at 90 anechoic fast response Low profile 100dBA 3dBA System 103dBA 3dBA Standard sounder only EN54 Part 3 Messages Tones and Strobe flash rate see instructions supplied with...

Page 34: ...a terminal block to which loop cables are connected Installation instructions 34 LC 0C L1 01 L2 02 LC 0C L1 01 main assembly L2 02 base Sounder Strobe device 3 way red black red black red black Loop...

Page 35: ...mated with protective cover and back box Colour Red similar to RAL3020 Case ABS engineering plastic Indicators Normal Active Green LED for status and find device application Red LED and Yellow tab for...

Page 36: ...he tab to position F and insert the glass A or optional resettable element B h Hook the front cover onto the top edge of the call point assembly and then push the bottom edge down until it click shut...

Page 37: ...g temperature 25 to 70 C Relative Humidity Non condensing Temperature 25 55 C up to 95 Emission BS EN61000 6 3 2001 Residential Commercial Light Industry Class B limits Immunity BS EN50130 4 Part 4 19...

Page 38: ...using the 2 long screws supplied g Hook the front cover onto the top edge of the keyswitch unit and then push the bottom edge down until it click shut Check both hooks on the top of the front cover ar...

Page 39: ...The SenTRI interface modules can be mounted in other equipment housings using the DIN rail mount brackets A module can also be fitted into a plastic box or metal box The boxes have cable termination...

Page 40: ...Can be configured as LED output The cable screens must be connected to an on the chassis or in the metal box If a module is mounted on a then the DIN rail must electrically connected to the earth ter...

Page 41: ...k with or without a delay Input channel can be configured as a switch input of Fire Fault Supervisory non fire or Confirmation signal with input acceptance delay of up to 10 seconds for a Fire input a...

Page 42: ...including surface mount and DIN rail mount EN54 17 2005 and EN54 18 2005 Cables Any suitably rated cable may be used for wiring the output lines to drive the required load For information on cables re...

Page 43: ...condensing Emission BS EN 61000 6 3 2001 Residential Commercial Light Industry Class B limits Immunity BS EN50130 4 1996 Part 4 LVD BS EN 60950 2002 Ingress Protection Metal box IP40 estimated Colour...

Page 44: ...2 12V 2 1Ah sealed lead acid batteries Input zone channels 2 wire inputs for conventional zone circuits Circuits are monitored for Detector fire MCP fire Wiring open circuit fault Wiring short circui...

Page 45: ...ls h Connect the transformer secondary wires to terminal block P7 on the interface board i Place the batteries inside the back box however do not make the connection this is done during commissioning...

Page 46: ...SENTRI RPT Repeat panel EN54 SENTRI RPT BATT Battery pack for Repeat panel for SENTRI RPT T Breaker and Remote LED 78299 01NM T Breaker to create a spur circuit off the main loop SEN LED Remote LED m...

Page 47: ...TRI Removal tool SEN COVER REMOVER SenTRI Dust cover remover tool spare adaptor SEN BASE LABEL SenTRI Label plate pack of 50 Beam sensor SENTRI BEAM SenTRI Beam sensor pair SEN 741 01 Angle bracket wi...

Page 48: ...ox Medium Voltage Mains powered interface unit S4 78302 02NM S4 Mains Powered Interface Unit 4 Channel mains powered interface 78301 01NM Mains powered fire alarm interface require batteries 19104 52...

Page 49: ...Notes 49 SenTRI ONE System...

Page 50: ...Notes Installation instructions 50...

Page 51: ...Notes 51 SenTRI ONE System...

Page 52: ...of via a suitable recycling centre and in accordance with national or local legislation Do not dispose of with your normal household waste Do not burn WEEE Directive At the end of their useful life t...

Reviews: