Smoke Guard 200 Operation & Maintenance Manual Download Page 8

Semi-Annual Testing 

The Smoke Guard system is considered “connected equipment” as defined in NFPA 72.  
As such, the owner or a designated representative shall be responsible for inspecting, 
functional testing, recording of tests, and maintaining the system at intervals not longer 
than 6 months, or as required by the authority having jurisdiction. 

 

 

step 

procedure 

Activate the elevator landing smoke detector connected to the unit per the 
smoke detector manufacturer recommendations.

 

Observe the deployment of the curtain.   

The curtain unwinds smoothly from the housing and stops  
when it meets the floor.  (Some slack in both cables is normal.)

 

 

Visually inspect the curtain assembly. 

There is no damage to the curtain, flexible magnets, rewind 
switch, or the seal at the floor.   

 

Inspect the flexible magnets.   

Both magnets are plumb and cover the auxiliary rails evenly (or 
the elevator frame in the absence of rails). 

 

Press the rewind switch on the face of the curtain. 

NOTE: The system is designed so there is a delay of several seconds 
after the unit has deployed before the rewind switch will operate. 

The curtain rewinds briefly, and then it redeploys (if the smoke 
detector remains in alarm). 

 

Engage the rewind motor by resetting the smoke detector.

 

The curtain rewinds with a uniform roll around the threshold 
pulleys with no telescoping of 1/2 inch or more. 

 

If the unit is a Model 400, the door closes behind the curtain as  
it rolls into the housing.  

If it is a Model 200, the door catches securely when you close it 
manually.

 

 

 

Summary of Contents for 200

Page 1: ...ual testing procedures for your Smoke Guard System 287 N Maple Grove Boise ID 83704 Phone 800 574 0330 208 639 7851 E Mail info smokeguard com Website http www smokeguard com Call your local Smoke Guard System Distributor for answers to questions about your system ...

Page 2: ... installers help ensure that your system functions as designed at the time of installation As with other components of your fire protection system periodic maintenance is required The building owner must inspect and test each Smoke Guard system unit at least once every six months Damage to the housing improper painting of the elevator door frame or other factors could hinder the proper operation o...

Page 3: ...r 5 Operation 6 How the Smoke Guard system works 6 What makes up the Smoke Guard system 6 What to do if the curtain has deployed 7 How to disconnect power to the unit 7 What to do if someone walks through a deployed curtain 7 Semi Annual Testing 8 Record of testing Smoke Guard system 9 Troubleshooting 11 ...

Page 4: ...d is exhausted out of the top The taller the building and the greater the temperature difference between the inside and outside temperatures the greater the air flow The elevator shaft acts like the chimney in a fireplace drawing smoke from a building fire through the gap between the elevator door and frame and exhausting the smoke into the upper floors How does the Smoke Guard system fit into the...

Page 5: ...tions Visual inspection shall ensure that there are no changes that would affect equipment performance such as building modifications occupancy hazards and environmental effects Smoke Guard recognized personnel must perform any alterations or additions to your system System acceptance testing Acceptance tests shall be performed after system components are added or deleted after any modification re...

Page 6: ...e it rewinds fully and remains in ready mode NOTE The system is designed so there is a delay of several seconds after the unit has deployed before the rewind switch will operate Rewind The curtain rewinds automatically when you reset the smoke detector or reestablish power to the unit Pressing the rewind switch rewinds the curtain only temporarily as long as an alarm condition exists What makes up...

Page 7: ...tify Smoke Guard 800 574 0330 for a free service visit How to disconnect power to the unit If you need to disconnect 120 VAC to the unit hook the housing door key provided with the unit around the lip of the housing door to pull it open door opens AWAY from the elevator to reach the service disconnect switch What to do if someone walks through a deployed curtain If someone walks through a deployed...

Page 8: ...he curtain assembly There is no damage to the curtain flexible magnets rewind switch or the seal at the floor 4 Inspect the flexible magnets Both magnets are plumb and cover the auxiliary rails evenly or the elevator frame in the absence of rails 5 Press the rewind switch on the face of the curtain NOTE The system is designed so there is a delay of several seconds after the unit has deployed befor...

Page 9: ...Record of testing Smoke Guard system Installation Date ___________________________________ Test date Unit location Results Inspector s name Inspector s signature ...

Page 10: ...Test date Unit location Results Inspector s name Inspector s signature ...

Page 11: ...correctly Fire alarm technician must install diode provided by Smoke Guard Red LED on control cover is not on No 120 VAC to unit junction box Electrician must provide 120 VAC to housing junction box constant clicking when power supplied bad ground clutch engaging and disengaging repeatedly supply a good ground door won t close ceiling soffit pinches housing distorting door Release pressure on the ...

Reviews: