Smoke Guard 200 Operation & Maintenance Manual Download Page 11

 

Troubleshooting 

Quick tips 

 

PROBLEM 

 

CAUSE 

 

SOLUTION 

System does not respond to 
the rewind switch on the 
curtain. 

Attempt to utilize the switch 
too soon after deployment 

The system is designed with 
a delay to allow the switch to 
adjust to the deployed state. 

Wait several seconds after 
deployment before pressing 
the switch. 

Green LED on control cover 
is not on 

No smoke detector diode 
installed 

OR 

Diode installed incorrectly 

Fire alarm technician must 
install diode provided by 
Smoke Guard. 

Red LED on control cover is 
not on. 

No 120 VAC to unit junction 
box 

Electrician must provide 120 
VAC to housing junction box 

constant clicking when power 
supplied 

bad ground, clutch engaging 
and disengaging repeatedly 

supply a good ground. 

door won’t close 

ceiling/soffit pinches housing 
distorting door 

Release pressure on the 
housing so there is at least a 
1/8” gap between the housing 
and ceiling/soffit. 

 
 
 

Call your local Smoke Guard

 

Distributor 

for answers to questions about your system 

 

or call 

 

Smoke Guard Technical Services 

1-800-215-6138

 

Summary of Contents for 200

Page 1: ...ual testing procedures for your Smoke Guard System 287 N Maple Grove Boise ID 83704 Phone 800 574 0330 208 639 7851 E Mail info smokeguard com Website http www smokeguard com Call your local Smoke Guard System Distributor for answers to questions about your system ...

Page 2: ... installers help ensure that your system functions as designed at the time of installation As with other components of your fire protection system periodic maintenance is required The building owner must inspect and test each Smoke Guard system unit at least once every six months Damage to the housing improper painting of the elevator door frame or other factors could hinder the proper operation o...

Page 3: ...r 5 Operation 6 How the Smoke Guard system works 6 What makes up the Smoke Guard system 6 What to do if the curtain has deployed 7 How to disconnect power to the unit 7 What to do if someone walks through a deployed curtain 7 Semi Annual Testing 8 Record of testing Smoke Guard system 9 Troubleshooting 11 ...

Page 4: ...d is exhausted out of the top The taller the building and the greater the temperature difference between the inside and outside temperatures the greater the air flow The elevator shaft acts like the chimney in a fireplace drawing smoke from a building fire through the gap between the elevator door and frame and exhausting the smoke into the upper floors How does the Smoke Guard system fit into the...

Page 5: ...tions Visual inspection shall ensure that there are no changes that would affect equipment performance such as building modifications occupancy hazards and environmental effects Smoke Guard recognized personnel must perform any alterations or additions to your system System acceptance testing Acceptance tests shall be performed after system components are added or deleted after any modification re...

Page 6: ...e it rewinds fully and remains in ready mode NOTE The system is designed so there is a delay of several seconds after the unit has deployed before the rewind switch will operate Rewind The curtain rewinds automatically when you reset the smoke detector or reestablish power to the unit Pressing the rewind switch rewinds the curtain only temporarily as long as an alarm condition exists What makes up...

Page 7: ...tify Smoke Guard 800 574 0330 for a free service visit How to disconnect power to the unit If you need to disconnect 120 VAC to the unit hook the housing door key provided with the unit around the lip of the housing door to pull it open door opens AWAY from the elevator to reach the service disconnect switch What to do if someone walks through a deployed curtain If someone walks through a deployed...

Page 8: ...he curtain assembly There is no damage to the curtain flexible magnets rewind switch or the seal at the floor 4 Inspect the flexible magnets Both magnets are plumb and cover the auxiliary rails evenly or the elevator frame in the absence of rails 5 Press the rewind switch on the face of the curtain NOTE The system is designed so there is a delay of several seconds after the unit has deployed befor...

Page 9: ...Record of testing Smoke Guard system Installation Date ___________________________________ Test date Unit location Results Inspector s name Inspector s signature ...

Page 10: ...Test date Unit location Results Inspector s name Inspector s signature ...

Page 11: ...correctly Fire alarm technician must install diode provided by Smoke Guard Red LED on control cover is not on No 120 VAC to unit junction box Electrician must provide 120 VAC to housing junction box constant clicking when power supplied bad ground clutch engaging and disengaging repeatedly supply a good ground door won t close ceiling soffit pinches housing distorting door Release pressure on the ...