22
Use only the adapters and vent system listed in Tables 12 and 13.
DO NOT mix vent systems of different types or manufacturers.
Failure to comply could result in severe personal injury, death, or
substantial property damage.
Installations must comply with applicable national, state, and
local codes.
Installation of a polypropylene vent system should adhere to the
vent manufacturer’s installation instructions supplied with the
vent system.
All terminations must comply with listed options in this manual
and be a single-wall vent offering.
The installer must use a specific vent starter adapter at the
flue collar connection. This adapter is supplied by the vent
manufacturer to adapt to its vent system. See Table 13 for
approved vent adapters. Do not use CPVC starter piece.
All vent connections MUST be secured by the vent manufacturer's
joint connector (Figure 20).
Insulation should not be used on polypropylene venting
materials. The use of insulation will cause increased vent wall
temperatures, which could result in vent pipe failure.
Table 13. Approved PolypropyleneTerminations
MODEL
CENTROTHERM INNOFLUE SW
DURAVENT POLYPRO
POLYPROPYLENE
ADAPTER
JOINT
CONNECTOR
SIDEWALL
RETAINING
BRACKET*
SIDEWALL
ADAPTER*
POLYPROPYLENE
ADAPTER
JOINT
CONNECTOR
SIDEWALL
KIT*
150 - 200
ISAAL0303
IANS03
IATP0303
ISTAGL0303
3PPS-AD
3PPS-LB
3PPS-HLK
400 - 600
ISAAL0404
IANS04
IATP0404
ISTAGL0404
4PPS-AD
4PPS-LB
4PPS-HLK
700 - 800
ISAAL0606
Not Required
IATP0606
ISTAGL0606
FSA-6PVCM-6PPS
Not Required
6PPK-HLK
* These parts are only needed if the sidewall termination assembly is used (see Figure 31 on Page 27).
Figure 20. Near Water Heater Polypropylene Venting