background image

14

• 

Seal  -  With  prior  requirements  met,  the  system  should  be 

tested to the procedure listed in parts (3) through (6) of the 

Removal  of  an  Existing  Water  Heater  section  mentioned 

below.

With polypropylene and stainless steel vent, seal and connect 

all pipe and components as specified by the vent manufacturer 

used; with PVC/CPVC vent, see the Installing Vent and Air Piping 

section on Page 20. If any of these conditions are not met, the 

existing system must be updated or replaced for that concern. 

Failure to follow all instructions can result in flue gas spillage and 

carbon monoxide emissions, causing severe personal injury or 

death.

WHEN REMOVING A WATER HEATER FROM 

EXISTING COMMON VENT SYSTEM

Do  not  install  this  water  heater  into  a  common  vent  with  any 

other  appliance. This  will  cause  flue  gas  spillage  or  appliance 

malfunction, resulting in possible severe personal injury, death, 

or substantial property damage. Failure to follow all instructions 

can result in flue gas spillage and carbon monoxide emissions, 

causing severe personal injury or death.
At the time of removal of an existing water heater, the following 

steps shall be followed with each appliance remaining connected 

to  the  common  venting  system  placed  in  operation,  while  the 

other  appliances  remaining  connected  to  the  common  venting 

system are not in operation.
1.  Seal any unused openings in the common venting system.
2.  Visually  inspect  the  venting  system  for  proper  size  and 

horizontal  pitch  and  determine  there  is  no  blockage  or 

restriction, leakage, corrosion, or other deficiencies, which 

could cause an unsafe condition.

3.  Test vent system – Insofar as is practical, close all building 

doors and windows and all doors between the space in which 

the appliances remaining connected to the common venting 

system are located and other spaces of the building. Turn 

on clothes dryers and any appliance not connected to the 

common venting system. Turn on any exhaust fans, such as 

range hoods and bathroom exhausts, so they will operate 

at maximum speed. Do not operate a summer exhaust fan. 

Close fireplace dampers.

4.  Place  in  operation  the  appliance  being  inspected.  Follow 

the lighting instructions. Adjust thermostat so appliance will 

operate continuously.

5.  Test  for  spillage  at  the  draft  hood  relief  opening  after  5 

minutes of main burner operation. Use the flame of a match 

or candle, or smoke from a cigarette, cigar, or pipe.

6.  After it has been determined that each appliance remaining 

connected  to  the  common  venting  system  properly  vents 

when  tested  as  outlined  herein,  return  doors,  windows, 

exhaust fans, fireplace dampers, and any other gas-burning 

appliance to their previous conditions of use.

7.  Any  improper  operation  of  the  common  venting  system 

should  be  corrected  so  the  installation  conforms  with  the 

National  Fuel  Gas  Code,  ANSI  Z223.1/NFPA  54  and/or 

CAN/CSA  B149.1,  Natural  Gas  and  Propane  Installation 

Code.  When  resizing  any  portion  of  the  common  venting 

system,  the  common  venting  system  should  be  resized 

to  approach  the  minimum  size  as  determined  using  the 

appropriate tables in Part 11 of the National Fuel Gas Code, 

ANSI Z223.1/NFPA and/or CAN/CSA B149.1, Natural Gas 

and Propane Installation Code.

CORROSIVE MATERIALS AND CONTAMINATION 

SOURCES
Products to avoid:

• 

Spray cans containing chloro/fluorocarbons

• 

Permanent wave solutions

• 

Chlorinated waxes/cleaners

• 

Chlorine-based swimming pool chemicals

• 

Calcium chloride used for thawing

• 

Sodium chloride used for water softening

•  Refrigerant leaks
• 

Paint or varnish removers

• 

Hydrochloric acid/muriatic acid

• 

Cements and glues

• 

Antistatic fabric softeners used in clothes dryers

• 

Chlorine-type bleaches, detergents, and cleaning 

solvents found in household laundry rooms

• 

Adhesives used to fasten building products and other 

similar products

Areas likely to have contaminants:

• 

Dry cleaning/laundry areas and establishments

• 

Swimming pools

• 

Metal fabrication plants

•  Beauty shops
•  Refrigeration repair shops
• 

Photo processing plants

• 

Auto body shops

• 

Plastic manufacturing plants

• 

Furniture refinishing areas and establishments

• 

New building construction

• 

Remodeling areas

• 

Garages with workshops

WHEN USING AN EXISTING VENT SYSTEM TO 

INSTALL A NEW WATER HEATER

Check the following venting components before installing:

•  Material

 - For materials listed for use with this appliance, see 

Venting Installation section on Page 17. For polypropylene or 

stainless steel venting, an adapter of the same manufacturer 

must be used at the flue collar connection.

•  Size

  -  To  ensure  proper  pipe  size  is  in  place,  see  Table 

8.  Check  to  see  that  this  size  is  used  throughout  the  vent 

system.

•  Manufacturer

  -  For  a  stainless  steel  or  polypropylene 

application,  you  must  use  only  the  listed  manufacturers 

and  their  type  product  listed  in  Tables  12  and  14  for  CAT 

IV positive pressure venting with flue producing condensate.

•  Supports

  -  Non-combustible  supports  must  be  in  place 

allowing a minimum 1/4" rise per foot. The supports should 

adequately  prevent  sagging  and  vertical  slippage,  by 

distributing the vent system weight. For additional information, 

consult the vent manufacturer’s instructions for installation.

•  Terminations

 - Carefully review Venting Installation section 

to  ensure  requirements  for  the  location  of  the  vent  and 

air  terminations  are  met  and  orientation  of  these  fit  the 

appropriate  image  from  the  Horizontal  or  Vertical  options 

listed  in  the  Venting  Installation  section.  For  stainless 

steel  vent,  only  use  terminations  listed  in  Table  16  for  the 

manufacturer of the installed vent.

Summary of Contents for XWH 150

Page 1: ...ATION SERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do n...

Page 2: ...An Existing Vent System To Install A New Water Heater 14 When Removing A Water Heater From Existing Common Vent System 14 Removing A Water Heater From Wood Pallet 15 Gas Conversions 15 Leveling The Wa...

Page 3: ...hazard what can happen if you do not follow the safety message and how to avoid the risk of injury DANGER WARNING CAUTION CAUTION DANGER indicates an imminently hazardous situation which if not avoide...

Page 4: ...ce connected to the hot water system If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow THERE SHOULD BE NO SMOKING OR OPEN...

Page 5: ...re placing water heater in operation Disconnect gas piping at main gas shutoff valve before leak testing heater Install sediment trap in accordance with NFPA 54 or CAN CSA B149 1 Use joint compound or...

Page 6: ...his manual These diagrams will serve to provide the installer with a reference It is essential that all venting water piping gas piping and wiring be installed as shown Particular attention should be...

Page 7: ...7 FEATURES AND COMPONENTS Left Side Inside Out Models 285 Rear View Models 285 Left Side Inside Out Models 150 200 Rear View Models 150 200 MODELS 150 200 MODEL 285...

Page 8: ...13 33 11 40 27 14 15 6 4 8 1 16 3 21 10 36 2 41 5 23 34 20 7 28 19 Left Side Inside Out Models 600 800 Rear View Models 600 800 Left Side Inside Out Models 400 500 Rear View Models 400 500 MODELS 400...

Page 9: ...pecially designed coils for maximum heat transfer while providing protection against flue gas corrosion The coils are encased in a jacket that contains the combustion process 2 Combustion Chamber Acce...

Page 10: ...ANE GAS NATURAL GAS PROPANE GAS NATURAL GAS PROPANE GAS XWH 150 0 22 W C 0 054 kPa 0 23 W C 0 057 kPa 4 W C 1 kPa 8 W C 2 kPa 14 W C 3 49 kPa 14 W C 3 49 kPa XWH 200 0 39 W C 0 09 kPa 0 39 W C 0 09 kP...

Page 11: ...aust venting Use only the vent materials and methods specified in this Instruction Manual 2 Standard XP water heaters are equipped to operate from sea level to 4 500 feet only with no adjustments The...

Page 12: ...ES Clearances from combustible materials 1 Hot water pipes at least 1 4 from combustible materials 2 Vent pipe at least 1 from combustible materials 3 See Figure s 2 and 3 below for other clearance mi...

Page 13: ...om are needed when clearances around the XP water heater are at least equal to the SERVICE clearances shown in Figure s 2 and 3 For spaces that do NOT supply this clearance provide two openings as sho...

Page 14: ...us conditions of use 7 Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code ANSI Z223 1 NFPA 54 and or CAN CSA B149 1 Na...

Page 15: ...er remove the parts box 2 Remove the front door to access the lag bolts in front of the unit see Figure below 3 To remove the water heater from the pallet after removing the front door Remove the two...

Page 16: ...lled Failure to comply will cause a gas leak resulting in severe personal injury or death Model 500 1 Remove the top access covers from the unit no tools required for removal 2 Turn the adjustment scr...

Page 17: ...ore details Figure 11 PVC CPVC Concentric Sidewall Termination Models 150 600 Only See Page 28 for more details Figure 12 Two Pipe Vertical Termination See Page 31 for more details Figure 13 PVC CPVC...

Page 18: ...nsate will not become trapped in a section of vent pipe and therefore reduce the open cross sectional area of the vent INSTALL VENT AND COMBUSTION AIR PIPING This water heater must be vented and suppl...

Page 19: ...missions causing severe personal injury or death SIZING This water heater uses model specific combustion air intake and vent piping sizes as detailed in Table below Table 8 Air Intake Vent Piping Size...

Page 20: ...hrough the roof or through a sidewall Follow the procedures in this manual for the method chosen Refer to the information in this manual to determine acceptable vent and air piping length OPTIONAL ROO...

Page 21: ...Models 700 800 POLYPROPYLENE This product has been approved for use with the Polypropylene vent with the manufacturers listed in Table 12 All terminations must comply with listed options in this manu...

Page 22: ...approved vent adapters Do not use CPVC starter piece All vent connections MUST be secured by the vent manufacturer s joint connector Figure 20 Insulation should not be used on polypropylene venting m...

Page 23: ...d Security Chimney Secure Seal ICC VIC Use of FasNSeal Flex smooth inner wall vent is to be used in vertical or near vertical sections only taking precaution to ensure no sagging occurs of the vent sy...

Page 24: ...manual 2 You must consider the surroundings when terminating the vent and air a Position the vent termination where vapors will not damage nearby shrubs plants or air conditioning equipment or be obje...

Page 25: ...gure 23 c Do not terminate closer than 4 feet horizontally from any electric meter gas meter regulator T P Relief Valve or other equipment Never terminate above or below any of these within 4 feet hor...

Page 26: ...andard constructions per the directions found in this manual 9 Stainless steel terminations are designed to penetrate walls with a thickness up to 9 25 inches of standard construction SIDEWALL DIRECT...

Page 27: ...ngs thoroughly with exterior caulk Figure 31 Polypropylene Sidewall Termination Assembly Figure 32 A Typical Sidewall Termination Assembly Models 150 800 PVC CPVC or Stainless Steel MULTIPLE VENT AIR...

Page 28: ...ATIONS 1 Determine the best location for the termination kit see Figure above 2 Reference the Determine Location section on Page 24 of this manual for general termination considerations 3 Cut one 1 ho...

Page 29: ...dimension D more than 60 inches see Figures 38 and 39 If assembly depth needs to be reduced dimension D can be as short as possible Figure 38 Concentric Vent Dimensional Drawing Models 150 200 NOTE I...

Page 30: ...rminations be made as shown to avoid recirculation of flue gases DO NOT use field supplied couplings to extend pipes Airflow restriction will occur and may cause intermittent operation 8 Cement applia...

Page 31: ...in an up turned coupling as shown in Figure 43 The top of the coupling must be at least 1 foot above the air intake When the vent termination uses a rain cap as illustrated in Figure 44 maintain at le...

Page 32: ...eilings and roofs 5 Provide flashing and sealing boots sized for the vent pipe and air pipe MULTIPLE VENT AIR TERMINATIONS 1 When terminating multiple XP water heaters terminate each vent air connecti...

Page 33: ...e screw assembly method drill a clearance hole in the rain cap and a pilot hole in the vent pipe for the screw size being used Failure to drill adequate holes may cause cracking of PVC components allo...

Page 34: ...or recirculation of combustion products may occur Water may also collect inside the larger combustion air pipe and flow to the burner enclosure Failure to follow this warning could result in product d...

Page 35: ...to the appropriate example Installation must comply with local requirements and with the National Fuel Gas Code The maximum allowable equivalent vent and air intake lengths for this venting arrangemen...

Page 36: ...ystem volume and capacity 6 Install a drain valve at the lowest point of the system 7 This appliance is supplied with a Temperature Pressure Relief Valve sized in accordance with ASME Boiler and Press...

Page 37: ...due to water chemistry generally shows up first in the hot water system because heated water increases the rate of corrosive chemical reactions PIPING COMPONENTS WATER HEATER SYSTEM PIPING Water heat...

Page 38: ...urer s instructions for each system component The installer is responsible for compliance with local codes The piping will not support the weight of the water heater circulator pump Do not attempt to...

Page 39: ...ponsible for compliance with local codes The piping will not support the weight of the water heater circulator pump Do not attempt to support the weight of the water heater circulator pump with the pi...

Page 40: ...urer s instructions for each system component The installer is responsible for compliance with local codes The piping will not support the weight of the water heater circulator pump Do not attempt to...

Page 41: ...ponsible for compliance with local codes The piping will not support the weight of the water heater circulator pump Do not attempt to support the weight of the water heater circulator pump with the pi...

Page 42: ...1 2 PSIG 3 5 kPa c The appliance and its gas connection must be leak tested before placing it in operation GAS CONNECTIONS CONNECTING GAS SUPPLY PIPING 1 Remove the top access panel and refer to Figu...

Page 43: ...hat pipe dope does not block gas flow Failure to apply pipe sealing compound as detailed in this manual can result in severe personal injury death or substantial property damage XP water heaters are t...

Page 44: ...190 1 980 1 820 1 700 4 17 500 12 000 9 660 8 270 7 330 6 640 6 110 5 680 5 330 5 040 4 460 4 050 3 720 3 460 XP water heaters are typically shipped ready to fire on natural gas Check the water heate...

Page 45: ...ignition failure The problem is especially noticeable in NEW Propane LP installations and also in empty tank situations This can also occur when a utility company shuts off service to an area to prov...

Page 46: ...rough the knockouts in the rear of the water heater as shown in Figure 71 2 Connect low voltage wiring to low voltage connection board as shown in Figure 72 on Page 48 of this manual and the water hea...

Page 47: ...age Connection Boards Figure 72 If more than two water heaters are on the Lead Lag daisy chain the wiring from the Lead Lag terminals on the second water heater to the Lead Lag terminals on the third...

Page 48: ...48 Figure 72 Low Voltage Field Wiring Connections...

Page 49: ...rom multiple condensing appliances CONDENSATE DISPOSAL CONDENSATE DRAIN 1 This water heater is a high efficiency appliance that produces condensate 2 The side of the water heater has a 1 2 inch PVC un...

Page 50: ...e Failure to fill the trap could result in severe personal injury or death FINAL CHECKS BEFORE STARTING THE WATER HEATER Read the XP Water Heater Service Handbook to familiarize with Control Module op...

Page 51: ...rs verify conversion 1 Verify propane conversion has been completed per the Propane Conversion instructions DO NOT adjust gas valve outlet pressure The gas valve is factory set for the correct outlet...

Page 52: ...art has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water OPERATING...

Page 53: ...53 OPERATING INSTRUCTIONS FOR MODELS 400 800...

Page 54: ...ol module regulates blower speed to control the water heater firing rate The gas valve senses the amount of air flowing into the water heater and allows only the right amount of gas to flow CONTROL IN...

Page 55: ...t high limit The automatic reset high limit has a set point of 200 F and the manual reset high limit has a maximum set point of 210 F When the outlet temperature exceeds 200 F the automatic high limit...

Page 56: ...for heat is satisfied the control will de energize the gas valve The blower will continue to run during the postpurge 8 The water heater pump will continue to run for its respective pump delay time b...

Page 57: ...LAY Tank Temperature 71 F Operating Setpoint 184 F Status Ignition HELP DISABLE A O Smith XP MENU OFF GAS O N LCD Touch Screen Display Status Icons Main Menu Help Menu Enable Disable Button Figure 75...

Page 58: ...em or when the Enable Disable switch on the display is in Disable position or Building Management system Enable Disable circuit is an open circuit Display will read Status Water Heating Disabled The C...

Page 59: ...er heater components are displayed in this menu Display Settings Temperature units F or C the LCD appearance brightness contrast and backlight delay user adjustable settings are located in this menu H...

Page 60: ...on per Start Up section of this manual Flame inspection stable uniform Flame signal at least 10 microamps at high fire Clean the heat exchanger if flue temperature is more than 54 F above return water...

Page 61: ...ment from inside the water heater and components Remove any obstructions CLEAN CONDENSATE TRAP 1 Inspect the condensate drain line condensate PVC fittings and condensate trap 2 Remove the PVC cap reta...

Page 62: ...a thermal expansion tank waterlogging or undersizing INSPECT IGNITION AND FLAME SENSE ELECTRODES 1 Remove the ignition and flame sense electrodes from the water heater heat exchanger access cover 2 Re...

Page 63: ...anger to thoroughly dry 10 Remove the field supplied rear refractory cover from the back of the combustion chamber of the heat exchanger and reassemble 11 Close isolation valves on piping to isolate w...

Page 64: ...tual switch states may vary from those shown on diagrams depending upon whether utilities are connected or a fault condition is present 2 See wiring diagram for additional notes LOW VOLTAGE 120 VAC HI...

Page 65: ...ptions Replacement high vo ltage spark lead and ribbon cables must be purchased from the factory Use of a non approved spark lead or ribbon cables can lead to operational problems which could result i...

Page 66: ...66 NOTES...

Page 67: ...follow applicable codes Failure to follow printed instructions Abuse misuse accident fire flood Acts of God Improper installation sizing delivery or maintenance Claims related to rust noise smell or t...

Page 68: ...500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 www hotwater com Copyright 2016 A O Smith All rights reserved...

Reviews: