background image

CAUTION

Due to the fact that the sections are top heavy, it is
absolutely necessary that the back section be supported
in such a manner as to prevent its falling and causing
potential serious bodily injury while preparing to add the
next section. One such way would be to insert a piece of
3" x 36" piping in the lower port.

NOTE

Some sections may need shims under support feet to align
with other sections.

Stand the back section in place with the feet on and in the
angle iron rails. Support the section as required to prevent it
from falling forward or rearward. Clean hydronic gasket
recesses and rope groove with a stiff wire brush. Apply
spray-on adhesive (supplied with the boiler) to rope groove
to hold wicking in place during assembly.

CAUTION

Do not spray adhesive into the hydronic seal ports.

Apply a length of wicking avoiding bends and twists. Be sure
ends extend past the cleanout cover opening. (See FIGURE
2) Place the upper and lower hydronic seals in the recessed
section taking care not to dislodge the rope or the hydronic
seals. Inspect the alignment of the sections through the open
ports and, if properly aligned, install the draw rods with nuts
drawn hand-tight. (See FIGURE 3.) Plumb the sections before
applying torque to the upper right and lower left draw rods.
Maintain finger-tight torque on upper left and lower right draw
rods.

FIGURE 2

IMPORTANT

The upper and lower ports should be drawn up metal to
metal around the outside of the hydronic seal. Metal to
metal conditions will not occur at any other location.
Avoid excessive torque on upper left and lower right
draw rods, which may warp the section. See FIGURE 3
for correct alignment of the seal.

Assemble additional sections as described above.

After draw rods are hand tight, torque as shown in TABLE 3.

5.

COMBUSTION AND VENTILATION AIR

An adequate supply of air for the boiler room must be provided
to allow complete combustion of fuel and ventilation of the
room to avoid excessively high ambient temperature. Air inlet
by natural ventilation directly from the outside shall have
total free area of not less than one sq. in. per 14,000 BTU
per hour of input of all fuel burning appliances in the boiler
room.

Where combustion air must be obtained through ducts, see
ANSI/NFPA 31 or ANSI Z223.1 for requirements.

If mechanical combustion air supply is required, the system
must be approved by the local authorities, and should provide
at least 30 CFM per gallon of oil and 0.25 CFM per MBH of
gas input to the boilers.

Ventilation air, if required, must be in addition to the
combustion air quantities called for above.

6.

ASSEMBLY OF SECTIONS

When boilers are delivered to the job site, each item should
be inspected closely for possible shipping damage. Scars or
nicks in the port sealing surfaces may allow leakage. 

Do not

attempt to use any section that has been damaged in the
port seal area.

When ready to commence assembly, recommended on a
level pad, place the angle rails in position parallel with each
other with the 2" legs on the floor and measuring 25-21/32
inches outside dimension. Be sure to align the center of the
boiler with the center line of the pad. If no pad is provided,
shim and grout under the angles to make them level and
provide support along the full length. See FIGURE 1. Clean
hydronic gasket recesses and rope groove with a wire brush,
taking care not to damage machine surface.

See TABLE 2 for proper location of sections.

TABLE 2

F = Front Section
P = Plain intermediate section
H = Heater intermediate section-Optional, must be ordered.
B = Back Section

19A SERIES BOILER

INSTALLATION INSTRUCTIONS

PAGE 4

3 SECT

4 SECT

5 SECT

6 SECT

7 SECT

8 SECT

9 SECT

10 SECT

11 SECT

12 SECT

F

F

F

F

F

F

F

F

F

F

H

P

H

P

H

P

P

P

P

P

B

H

P

H

P

H

H

P

P

P

B

H

P

H

P

P

H

P

P

B

H

P

H

H

P

H

P

B

H

P

P

H

P

H

B

H

H

P

H

P

B

P

H

P

H

B

P

H

P

B

P

H

B

P

B

 HEATING

      SURFACE

CLEANOUT COVER

LOWER PORT

UPPER PORT

CERAMIC ROPE
JOINT SEAL

FLOOR

SECTIONAL VIEW

Summary of Contents for 19A Series

Page 1: ...motive anti freeze in boiler waterways If necessary to use anti freeze be sure to employ a preparation designed for hydronic heating systems such as ethylene or propylene glycol Water treatment is not recommended This boiler uses gaskets to seal the ports of adjoining sections These gaskets are made of a fluorocarbon elastomer designation FKM marketed under the brand name Viton Consult a water tre...

Page 2: ...ng Includes Mounting Plate w Observation Glass and Cover PAGE 2 19A SERIES BOILER INSTALLATION INSTRUCTIONS 13 78105 Burner Mounting Plate Rope 1 4 x 4 75 14 60434 Burner Mounting Plate Insulating Block 14 60430 Burner Mounting Plate Insulating Block Beckett Burner 3 6 Section 15 Upper Port Hydronic Seal 16 Lower Port Hydronic Seal 17 60025 Insulating Ceramic Rope 18 Tie Rod Hardware 19 Front Obse...

Page 3: ...arge cast iron cover plates A slide damper is provided in the flue gas outlet for back pressure adjustment The boilers are supplied completely knocked down for field assembly as factory assembled blocks of sections or completely assembled boiler burner units All items should be inspected for damage upon receipt and any damage reported to the wholesaler and trucker All components should be stored i...

Page 4: ...must be provided to allow complete combustion of fuel and ventilation of the room to avoid excessively high ambient temperature Air inlet by natural ventilation directly from the outside shall have total free area of not less than one sq in per 14 000 BTU per hour of input of all fuel burning appliances in the boiler room Where combustion air must be obtained through ducts see ANSI NFPA 31 or ANSI...

Page 5: ...R LEFT 5 FT LBS STEP 4 LOWER RIGHT 5 FT LBS STEP 5 UPPER RIGHT 25 FT LBS STEP 6 LOWER LEFT 25 FT LBS STEP 7 UPPER RIGHT 50 FT LBS STEP 8 LOWER LEFT 50 FT LBS STEP 9 UPPER LEFT 10 FT LBS STEP 10 LOWER RIGHT 10 FT LBS Prepare additional intermediate sections and install in the same manner described above Be sure each section is properly sealed against water leakage and flue gas exfiltration Be certa...

Page 6: ...he 5 16 x 1 1 2 studs and hex nuts furnished in screw seats in the back section Apply self adhesive insulating tape Items 21 and 22 in Parts detail drawing on Page 2 to smoke hood flange and damper angle Item 23 Fasten the slide damper in the open position for starting the burner adjustment process See FIGURE 6 for recommended L coil piping and FIGURE 7 for SM9 18 single and or dual piping arrange...

Page 7: ...NION GATE VALVE TEMPERING VALVE FLOW LIMITING VALVE TEMPERATURE GAUGE OPERATING CONTROL TANKLESS HEATER TEMPERED WATER SUPPLY COLD WATER INLET The sealing rope should be placed in the groove on the boiler side of the plate using adhesive to hold it in place The insulation block has a burner opening and a cutout for the observation opening Locate the block with the high temperature facing on the fi...

Page 8: ...OUT COVERS Be sure the rope seals are in place around the groove in the cleanout cover plate Install the plates on the boiler sections carefully to insure proper sealing all around using the 5 16 x 2 special anchor bolt and 5 16 hex head nuts After periodic flue cleaning replace nuts at 10 lbs torque Use Hi Temp silicone caulk to seal covers air tight 14 REAR OBSERVATION PORTS 7 12 SECTIONS INSTRU...

Page 9: ...WAYS A STEAM BOILERS NOTE The boiler should be cleaned before connecting system piping and installing steam trim 1 Plug unused openings all around the boiler leaving a valved overflow pipe connected to the safety valve tapping Also provide a valved blow down connection to one of the bottom tappings 2 The fuel burning equipment should be installed and made ready to operate in accordance with the bu...

Page 10: ...T CONN FRONT VIEW SIDE VIEW TOP VIEW 12 ADAPTER COLLAR 11 12 SECTION ONLY SERIES 19A BOILER STEAM TAPPING AND CONTROL LOCATIONS 3 SUPPLY TAPS 3 4 41 1 4 A 1 TAP AIR REMOVAL CONN OPT LWCO B 1 1 4 TAP SAFETY VALVE C 1 TAP OPTIONAL LWCO D 3 4 TAP OPER TEMP CONN A B VENT CONNECTION 3 4 TAP STD MAN RESET HIGH LIMIT 3 A 4 SUPPLY CLEANOUTS 3 RETURN TAP OPTIONAL INSPECTION TAPPINGS 3 4 TAP OPT OPT INSP TA...

Page 11: ... monoxide Hot gases from appliance venting system pipes or chimney escaping into the living space Flames coming out around the appliance Yellow colored flames in the appliance Stale or smelly air The presence of soot or carbon in or around the appliance Very high unexplained humidity inside the building If any of the symptoms of CO poisoning occur or if any of the signs of carbon monoxide are pres...

Page 12: ...WESTCAST INC 260 NORTH ELM STREET WESTFIELD MA 01085 TEL 413 562 9631 FAX 413 562 3799 ...

Reviews: