FieldServer  

FS-8700-22 DeviceNet Slave Adapter Driver 

Driver Manual  

(Supplement to the FieldServer Instruction Manual)

 

 

 

 

 

 

 

 

 

 

 

 

 

APPLICABILITY & EFFECTIVITY 

Effective for all systems manufactured after December 2017. 

Summary of Contents for FieldServer FS-8700-22

Page 1: ...cument Revision 1 B FieldServer FS 8700 22 DeviceNet Slave Adapter Driver Driver Manual Supplement to the FieldServer Instruction Manual APPLICABILITY EFFECTIVITY Effective for all systems manufacture...

Page 2: ...pport needs related to the FieldServer product Sierra Monitor Corporation 1991 Tarob Court Milpitas CA 95035 Website www sierramonitor com U S Support Information 1 408 964 4443 1 800 727 4377 Email s...

Page 3: ...s 6 5 Configuring the FieldServer as a DeviceNet Slave 7 5 1 DeviceNet Settings 7 5 2 Server Side Connection Parameters 8 5 3 Server Side Node Parameters 8 5 4 Server Side Map Descriptor Parameters 9...

Page 4: ...onnection of up to 512 Bytes in each direction to the FieldServer Max Nodes Supported FieldServer Mode Nodes Comments Server 1 The FieldServer can only emulate one DeviceNet Slave station 2 DRIVER SCO...

Page 5: ...Negative supply voltage black 2 CAN_L CAN_L Bus line blue 3 SHIELD Cable Shield bare 4 CAN_H CAN_H Bus line white 5 V Positive Supply Voltage red 3 1 Hardware Connection Tips Hints Use the recommende...

Page 6: ...gal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format Float Bit Uint16 Sint16 Uint32...

Page 7: ...ations the driver independent FieldServer buffers need to be declared in the Data Arrays section the FieldServer virtual node s needs to be declared in the Server Side Nodes section and the data to be...

Page 8: ...0K 500K Example Server Side Connections Connections Adapter Protocol DNet_Slave_Baudrate DNet X30_DNet_Slave 500K 5 3 Server Side Node Parameters Section Title Nodes Column Title Function Legal Values...

Page 9: ...alues Node_Name Name of Node One of the node names specified in Server Node Descriptor above DeviceNet_Data_Type Data Type of local buffer BYTE WORD DWORD FLOAT BOOL Address Byte offset into local buf...

Page 10: ...le Status LED 4 Reserved Appendix A 2 Using RSNetWorx Refer to the RSNetWorx document on the HMS website NOTE Establishing I O communication between AnyBus S DeviceNet using RsNetWorx for DeviceNet Ap...

Page 11: ...ere is no 24VDC supply on the DeviceNet Network or if the power supply current is not enough to support the entire network then the FieldServer will report that any device configured in the config fil...

Page 12: ...MAC ID and Baud Rate The MAC ID and baud rate can be set in the FieldServer s CSV file using the System_Station_Address and DNet_Slave_Baudrate parameters or it can be set with the DIP switches NOTE...