-56-
No.PF
※※
-OMS0002-B
■
[F98] Output check
The operation of the output can be checked by switching the output ON/OFF by pressing a button, without
the need for a flow of fluid.
<Operation>
Press the
or
button in function selection mode to display [F98] on the main display.
[tESt] is displayed on the sub display.
Press the
button.
Output check
[tESt] is displayed on the main display.
[The current set value] flashes on the sub display.
Press the
or
button to select.
An increase or decrease in flow will have no effect on the output while
the output check is being performed.
Check of OUT1
[1oUt] is displayed on the main display.
[The current set value] flashes on the sub display.
Press the
or
button to select.
Changing the display between ON and OFF using
the
or
button also changes the output status.
Select [NoRMAL].
Press the
button to set.
Select [FoRCE].
Press the
button to set.
Press the
button.
(With OUT2)
Check of OUT2
[2oUt] is displayed on the main display.
[The current set value] flashes on the sub display.
OUT2 can be set using the same procedure as
OUT1.
For the analogue output type, 5 V or 20 mA is
output when [on], and 1 V or 4 mA is output when [oFF].
Press the
button.
(Without OUT2)
Press the
button.
[F98] Setting of output check completed.
Return to function selection mode.