-82-
No.PF
※※
-OMY0002
●
Product individual parameters (continued)
Index
Sub
index
Access
1
Parameter
Data
type
2
Initial
value
Data
storage
3
Set value
Remarks
dec
hex
7000 0x1B58
0
W
Com
m
u
n
icat
io
n
OU
T
o
u
tp
u
t
te
st
OUT Test
U8
-
N
0:
Normal output
1:
Fixed output
The PD becomes 1 when a fixed
output has been received.
7010 0x1B62
0
W
Toggle
(Toggle output)
U8
-
N
0: Measured value
16: OUT1
17: OUT2
80: Analogue output
224: Diagnostic bit
255: Error bit
Connected with hardware output
7100 0x1BBC
0
R
M
e
a
su
re
m
e
n
t
re
lat
e
d
Analogue output
value
U8
0
Y
Voltage output:
0.1V increments
Current output:
1mA increments
8000 0x1F40
0
R
Inclination of flow rate
PD a
F32
-
N
Refer to "Inclination
and intercept".
(page
8010 0x1F4A
0
R
Flow rate PD
intercept b
F32
-
N
Refer to "Inclination
and intercept".
(page
8020 0x1F54
0
R
Flow peak value
S16
0
N
-200 to 4200
The conversion method from the
communication value to the actual
measurement value is the same as
the method for process data.
8030 0x1F5E
0
R
Flow bottom value
S16
0
N
8040 0x1F68
0
R
Accumulated
mantissa
F32
-
N
0 to 9999
Accumulated PD × Accumulated
value conversion factor
= Current accumulated flow value
0
R
Accumulated index
F32
-
N
0 to 6
1: "R" means Read and "W" means Write.
2: Refer to the table below for the symbol.
Symbol
Data type
(IO-Link standard)
Data length
Bit [byte]
Description
U8
UIntegerT
8 [1]
Unsigned integer
U16
16 [2]
S16
IntegerT
16 [2]
Signed integer
F32
Float32T
32 [4]
Floating point number
C32
StringT
32 [4]
String
3: "Y" indicates that the parameter setting data is saved to the master, and "N" indicates that the parameter is not saved.
4: Read/write to un-selectable items will be rejected depending on the product No.