-79-
No.PF
※※
-OMY0002
●
Product individual parameters
Index
Sub
index
Access
1
Parameter
Data
type
2
Initial
value
Data
storage
3
Set value
Remarks
dec
hex
160 00A0
0
R
Complete product number
C32
ALL
0x00
N
Arbitrary data
1000 0x03E8
0
R/W
Unit
(Unit setting)
U8
0
Y
0: L (L/min)
1: Ft (cfm)
When the unit selection function is
not included,
a read/write to an un-selectable item
is rejected.
1010 0x03F2
0
R/W
CoL
(Selection of display colour)
U8
2
Y
0: rEd (Constantly red)
1: Grn (Constantly green)
2: 1SoG
(OUT1 turns green at ON)
3: 1Sor
(OUT1 turns red at ON)
4: 2SoG
(OUT2 turns green at ON)
5: 2Sor
(OUT2 turns green at ON)
Setting of display colour
1020 0x03FC
0
R/W
NorP
(Selection of switch output
PNP/NPN)
U8
1
Y
0: NPN
1: PNP
Setting of switch output specification
1030 0x0406
0
R/W
i_o
(select switch output/
external input)
U8
1
Y
0: oUt (switch output)
1: in (external input)
Setting OUT2 output specification
setting
1070 0x042E
0
R/W
rEF
(reference condition)
U8
1
Y
0: Std
(Standard condition)
1: PNP
(reference condition)
Measurement Units criteria setting
1210 0x04BA
1
R/W
OUT
1
se
tt
in
g
oUt1
(Selection output mode)
U8
0
Y
0: HYS (Hysteresis)
1: Wind
(Window comparator)
2: AC
(Accumulated output)
3: PLS
(Accumulated pulse)
4: Err (Error output)
5: oFF (Output OFF)
Setting of OUT1 output mode
2
R/W
1ot
(Selection of output type)
U8
0
Y
0: 1_P (Normal output)
1: 1_n (Reverse output)
Setting of OUT1 output normal and
reserved output.
1220 0x04C4
1
R/W
S
e
t
OU
T
1
switc
h
p
o
int
.
P_1(n_1)
(Selection of output
set value)
S16 2000
Y
Setting range
-200 to 4200
Setting of OUT1 output set value
(Hysteresis)
2
R/W
H_1
(Setting of OUT1
hysteresis)
S16
200
Y
Setting range
0 to 4400
Setting of OUT1 hysteresis
(Hysteresis)
3
R/W
P1L(n1L)
(Lower limit of
window
comparator)
S16 1200
Y
Setting range
-200 to 4200
Setting of OUT1 output set value
(Lower limit of window comparator)
4
R/W
P1H(n1H)
(Upper limit of
window comparator)
S16 2400
Y
Setting range
-200 to 4200
Setting of OUT1 output set value
(Upper limit of window comparator)
5
R/W
WH1
(Window comparator
hysteresis)
S16
400
Y
Setting range
0 to 2200
Setting of OUT1 hysteresis
(Window comparator)
6
R/W
dtH1
(Delay time at ON)
S16
0
Y
Setting range
0 to 6000
Setting of OUT1 delay time at ON
10 ms increment
7
R/W
dtL1
(Delay time at OFF)
S16
0
Y
Setting of OUT1 delay time at OFF
10 ms increment