5 Adjustments
5-45
5.5.3 One-parameter Tuning Example
The following procedure is used for one-parameter tuning on the condition that the tuning mode is
set to 2 or 3. This mode is used to reduce positioning time.
Step
Measuring Instrument Display Example
Operation
1
Measure the positioning time after setting the moment of iner-
tia ratio (Pn103) correctly. Tuning will be completed if the
specifications are met here. The tuning results will be saved in
the DRIVER.
2
The positioning time will become shorter if the FF level is
increased. The tuning will be completed if the specifications
are met. The tuning results will be saved in the DRIVER. If
overshooting occurs before the specifications are met, go to
step 3.
3
Overshooting will be reduced if the FB level is increased. If the
overshooting is eliminated, go to step 4.
4
The graph shows overshooting generated with the FF level
increased after step 3. In this state, the overshooting occurs, but
the positioning settling time is shorter. The tuning will be com-
pleted if the specifications are met. The adjustment results are
saved in the DRIVER. If overshooting occurs before the
specifications are met, repeat steps 3 and 4.
If vibration occurs before the overshooting is eliminated, the
vibration will be suppressed by the automatic notch filter and
anti-resonance control.
Note: The vibration frequencies may not be detected if the
vibration is too small. If that occurs, forcibly detect the
vibration frequencies.
5
The adjustment results are saved in the DRIVER.
Summary of Contents for LECYU Series
Page 30: ...1 Outline 1 9 1 4 3 Three phase 200 V LECYU2 V9 Models ...
Page 65: ...3 Wiring and Connection 3 11 3 Wiring Example with DC Power Supply Input DRIVER ...
Page 92: ...3 Wiring and Connection 3 38 External Dimensions Units mm 1 FN Type by Schaffner EMC Inc ...
Page 93: ...3 Wiring and Connection 3 39 2 FN Type ...
Page 143: ...4 Operation 4 44 ...