-21-
No.PS
※※
-OMM0005-G
<Operation>
[Hysteresis mode]
1, Press the
button once in measurement mode.
2, [P_1] or [n_1] and the set value are displayed in turn.
3, Press the
or
button to change the set value.
The
button is to increase and the
button is to decrease.
Press the
button once to increase by one digit, and press it continuously to keep increasing the set
value.
Press the
button once to decrease by one digit, and press it continuously to keep decreasing the
set value.
4, Press the
button to finish the setting.
For models with 2 outputs, [P_2] or [n_2] will be displayed. Set as above.
The Pressure switch operates within a set pressure range (from P1L to P1H) during window comparator
mode. Set P1L (switch lower limit) and P1H (switch upper limit) using the setting procedure above.
When reversed output is selected, [n1L] and [n1H] are displayed.
Zero clear of Display
The display is reset to zero when the
and
buttons are pressed simultaneously for
1 second. For the first operation, always perform zero clear with no pressure applied.