HRX-OM-K003
Chapter 8 Appendix
8.5 BAND/READY function
HRW Series
8-12
8.5 BAND/READY function
Sets BAND to TEMP SP value, and notifies TEMP PV value reaches within
BAND range by the operation display panel or the communication.
See section “5.3.9 Initial Setting screen” on page 5-7, “5.3.11 Option screen” on
page 5-9 for the procedure of the setting.
When the setting is ON
Allows the setting of the BAND and REDY TIME. Allows the setting of the
communication output.
Figure 8-8 BAND/READY function
Examples of Setting
TEMP SP: 20°C
BAND: 2°C
READY TIME: 60sec.
“TEMP READY” is displayed on the operation display panel 60-sec. after
TEMP PV value becomes 18°C to start output by communication.
Necessary condition is that TEMP PV value after 60sec. is 20+/-2.0°C or
less. See “5.3.4 Status screen 3”on page 5-4 for the details of display
position.
When the setting is OFF
BAND/READY function becomes invalid.
BAND
TEMP SP
TEMP PV
TEMP READY not
display/not output
TEMP READY
display/output
READY
TIME
Summary of Contents for HRW002-H
Page 6: ...HRX OM K003 Table of Contents HRW Series TOC 4...
Page 22: ...HRX OM K003 Chapter 1 Safety 1 8 Material Safety Data Sheet MSDS HRW Series 1 16...
Page 24: ...HRX OM K003 Chapter 2 Name of Each Section 2 1 Name of Each Section HRW Series 2 2...
Page 60: ...HRX OM K003 Chapter 5 System Operation 5 4 Examples of System Operation HRW Series 5 16...
Page 64: ...HRX OM K003 Chapter 6 Error Message and Troubleshooting 6 2 Troubleshooting HRW Series 6 4...
Page 86: ......